IX
Troubleshooting ]
- 183 -
HWE0804A
GB
1. Error
Code
Overcurrent error due to short-circuited motor (Detail code 105)
2. Error definition and error detection method
When a short is detected on the load side just before starting the inverter operation.
3. Cause, Check method and remedy
In the case of 4250
In the case of 4255
Refer to section -6- "Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.
1. Error
Code
Heatsink overheat protection at startup
2. Error definition and error detection method
The heatsink temperature (THHS) remains at or above TOH for 10 minutes or more at inverter startup.
3. Cause, check method and remedy
Same as 4230 error
1. Error
Code
Heatsink overheat protection at startup
2. Error definition and error detection method
The heatsink temperature (THHS) remains at or above 100°C [212°F] for 10 minutes or more at inverter startup.
3. Cause, check method and remedy
Same as 4230 error
4250
4255
Cause
Check method and remedy
(1)
Short - circuited compressor
Refer to IX [4] -6- (2) [2].
(2)
Output wiring
Check for a short circuit.
Cause
Check method and remedy
(1)
Short - circuited fan motor
Refer to IX [4] -6- (2) [5].
(2)
Output wiring
Check for a short circuit.
4260
(THMU-A)
Model
TOH
P72, P96 models
100°C [212°F]
P120 model
90°C [194°F]
4260
(YHMU-A)
Summary of Contents for PUHY-P120YHMU-A
Page 1: ......
Page 9: ...HWE0804A GB ...
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 55: ... 46 ...
Page 71: ... 62 ...
Page 73: ... 64 ...
Page 81: ... 72 ...
Page 83: ... 74 ...
Page 89: ... 80 ...
Page 95: ... 86 ...
Page 97: ... 88 ...
Page 123: ... 114 ...
Page 157: ... 148 ...
Page 279: ... 270 ...
Page 281: ... 272 ...
Page 326: ......