VIII
Test Run Mode ]
- 129 -
HWE0804A
GB
Operation
Outdoor unit model
PUHY-P192TSHMU-A
PUHY-P72THMU-A
PUHY-P120THMU-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7 °C /19.4 °C [80 °F/67 °F]
Outdoor
35 °C / - [95 °F/ - ]
Indoor
unit
No. of connected
units
Unit
4
No. of units in opera-
tion
4
Model
-
48/48/48/48
Piping
Main pipe
m [ft]
5 [16-3/8]
Branch pipe
10 [32-3/4]
Total pipe length
45 [147-5/8]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
22 [49]
Outdoor
unit
Electric current
A
44.1
Voltage
V
230
Compressor frequency
Hz
52
74
LEV open-
ing
Indoor unit
Pulse
387/387/387/387
SC (LEV1)
100
100
LEV2
1400
1400
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi]
2.76/0.93 [400/135]
2.76/0.93 [400/135]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
69 [156]
73 [163]
Heat exchanger out-
let (TH3)
44 [111]
40 [104]
Accumulator inlet
10 [50]
10 [50]
Accumulator outlet
10 [50]
10 [50]
SCC outlet (TH6)
24 [75]
20 [68]
Compressor inlet
17 [63]
15 [59]
Compressor shell
bottom
47 [117]
42 [108]
Indoor
unit
LEV inlet
23 [73]
[19] [66]
Heat exchanger
outlet
10 [50]
[10] [50]
Summary of Contents for PUHY-P120YHMU-A
Page 1: ......
Page 9: ...HWE0804A GB ...
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 55: ... 46 ...
Page 71: ... 62 ...
Page 73: ... 64 ...
Page 81: ... 72 ...
Page 83: ... 74 ...
Page 89: ... 80 ...
Page 95: ... 86 ...
Page 97: ... 88 ...
Page 123: ... 114 ...
Page 157: ... 148 ...
Page 279: ... 270 ...
Page 281: ... 272 ...
Page 326: ......