II
Restrictions ]
- 43 -
HWE0804A
GB
1. Refrigerant
pipe
size
(1) Diameter of the refrigerant pipe between the outdoor unit and the first branch (outdoor unit pipe size)
(2) Size of the refrigerant pipe between the first branch and the indoor unit (indoor unit pipe size)
(3) Size of the refrigerant pipe between the branches for connection to indoor units
Outdoor unit set name
(total capacity)
Liquid pipe size (mm) [inch]
Gas pipe size (mm) [inch]
72 model
ø9.52 [3/8"]
ø19.05 [3/4"]
96 model
ø9.52 [3/8"]
*1
*1. Use ø12.7 [1/2"] pipes if the piping length exceeds 90 m [295 ft].
ø22.2 [7/8"]
120 model
ø9.52 [3/8"]
*2
*2. Use ø12.7 [1/2"] pipes if the piping length exceeds 40 m [131 ft].
ø22.2 [7/8"]
144 model
ø12.7 [1/2"]
ø28.58 [1-1/8"]
168 model
ø15.88 [5/8"]
ø28.58 [1-1/8"]
192 model
ø15.88 [5/8"]
ø28.58 [1-1/8"]
216 model
ø15.88 [5/8"]
ø28.58 [1-1/8"]
240 model
ø15.88 [5/8"]
ø28.58 [1-1/8"]
264 - 312 model
ø19.05 [3/4"]
ø34.93 [1-3/8"]
336 - 360 model
ø19.05 [3/4"]
ø41.28 [1-5/8"]
model
Pipe diameter (mm) [inch]
06 - 15 models
Liquid pipe
ø6.35 [1/4"]
Gas pipe
ø12.7 [1/2"]
18 - 54 models
Liquid pipe
ø9.52 [3/8"]
Gas pipe
ø15.88 [5/8"]
72 model
Liquid pipe
ø9.52 [3/8"]
Gas pipe
ø19.05 [3/4"]
96 model
Liquid pipe
ø9.52 [3/8"]
Gas pipe
ø22.2 [7/8"]
Total capacity of the
downstream units
Liquid pipe size (mm) [inch]
Gas pipe size (mm) [inch]
- 54
ø9.52 [3/8"]
ø15.88 [5/8"]
P55 - P72
ø9.52 [3/8"]
ø19.05 [3/4"]
P72 - P108
ø9.52 [3/8"]
ø22.2 [7/8"]
P109 - P144
ø12.7 [1/2"]
ø28.58 [1-1/8"]
P145 - P240
ø15.88 [5/8"]
ø28.58 [1-1/8"]
P241 - P308
ø19.05 [3/4"]
ø34.93 [1-3/8"]
P309 -
ø19.05 [3/4"]
ø41.28 [1-5/8"]
Summary of Contents for PUHY-P120YHMU-A
Page 1: ......
Page 9: ...HWE0804A GB ...
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 55: ... 46 ...
Page 71: ... 62 ...
Page 73: ... 64 ...
Page 81: ... 72 ...
Page 83: ... 74 ...
Page 89: ... 80 ...
Page 95: ... 86 ...
Page 97: ... 88 ...
Page 123: ... 114 ...
Page 157: ... 148 ...
Page 279: ... 270 ...
Page 281: ... 272 ...
Page 326: ......