Appendix 6 EMC and Low Voltage Directives
■
Grounding the cable clamp
Use shielded cables for external wiring and ground the shields of the external wiring cables to the control panel with the
AD75CK cable clamp (manufactured by Mitsubishi Electric Corporation). (Ground the shield section 20 to 30cm away from
the module.)
For detail on AD75CK, refer to the following.
AD75CK-type Cable Clamping Instruction Manual
■
External power supply
• Use a CE-marked product for an external power supply and always ground the FG terminal. (External power supply used
for the tests conducted by Mitsubishi Electric Corporation: TDK-Lambda DLP-120-24-1, IDEC PS5R-SF24, PS5R-F24)
• Use a power cable of 10m or shorter when connecting it to the module power supply terminal.
• Use a power cable of 30m or shorter when connecting it to the external power supply for output part.
(1) Module
(2) Inside a control panel
AD75CK
(1)
(2)
(2)
20 to 30 cm