3 SPECIFICATIONS
3.1 General Specifications
15
3
3
SPECIFICATIONS
This chapter describes the specifications of the I/O module.
3.1
General Specifications
*1 Do not use or store the I/O module under pressure higher than the atmospheric pressure of altitude 0m. Doing so may cause
malfunction. When using the I/O module under pressure, please consult your local Mitsubishi representative.
*2 When the programmable controller is used at altitude above 2000m, the withstand voltage performance and the upper limit of the
operating ambient temperature decrease. Please consult your local Mitsubishi representative.
*3 If the environment satisfies the operating ambient temperature, operating ambient humidity and other conditions, the module can be
used even outside the control panel.
*4 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within premises.
Category
applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to
the rated voltage of 300V is 2500V.
*5 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used.
Pollution degree 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be expected
occasionally.
To ensure that this product complies with the EMC Directive, refer to the following.
Page 108 EMC and Low Voltage Directives
Item
Specifications
Operating ambient temperature
0 to 55
Storage ambient temperature
-25 to 75
Operating ambient humidity
5 to 95%RH, non-condensing
Storage ambient humidity
Vibration resistance
Compliant with JIS
B 3502 and IEC
61131-2
Frequency
Constant
acceleration
Half amplitude
Sweep count
Under intermittent
vibration
5 to 8.4Hz
3.5mm
10 times each in X,
Y, and Z directions
8.4 to 150Hz
9.8m/
Under continuous
vibration
5 to 8.4Hz
1.75mm
8.4 to 150Hz
4.9m/
Shock resistance
Compliant with JIS B 3502 and IEC 61131-2 (147m/
, 3 times each in X, Y, and Z directions)
Operating atmosphere
No corrosive gases, flammable gases, less conductive dust
Operating altitude
0 to 2000m
Installation location
Inside a control panel
Overvoltage category
or less
Pollution degree
2 or less
Equipment class
Class
Summary of Contents for NZ2MFB1-32D
Page 2: ......
Page 14: ...12 1 PRODUCT LINEUP 1 3 I O Combined Module MEMO ...
Page 16: ...14 2 PART NAMES MEMO ...
Page 43: ...4 PROCEDURES BEFORE OPERATION 41 4 MEMO ...
Page 45: ...5 SYSTEM CONFIGURATION 43 5 MEMO ...
Page 76: ...74 9 PROGRAMMING 9 2 Program Example Program example ...
Page 78: ...76 10 MAINTENANCE AND INSPECTION MEMO ...
Page 119: ...APPX Appendix 8 External Dimensions 117 A MEMO ...
Page 121: ...I 119 MEMO ...
Page 125: ......