6 INSTALLATION AND WIRING
6.3 Installation Environment and Installation Position
55
6
6.3
Installation Environment and Installation Position
Installation environment
Installation location
Do not install the I/O module to the place where:
• Ambient temperature is outside the range of 0 to 55
;
• Ambient humidity is outside the range of 10 to 90% RH;
• Condensation occurs due to rapid temperature change;
• Corrosive gas or combustible gas is present;
• Conductive powder such as dust and iron powder, oil mist, salinity, or organic solvent is filled;
• The I/O module is exposed to direct sunlight;
• A strong electric field or strong magnetic field is generated; and
• The I/O module is subject to vibration and shock.
Installation surface
Install the I/O module on the flat surface. When the installation surface is uneven, excessive force is applied to the printed-
circuit board and may cause a defect.
Installation position
When installing the I/O module in a control panel, provide clearance of 60mm or longer (1) between the module and the sides
of control panel or neighboring modules to ensure good ventilation and an easy module change.
(1)
(1)
(1)
(1)
(1)
(1)
(1)
Summary of Contents for NZ2MFB1-32D
Page 2: ......
Page 14: ...12 1 PRODUCT LINEUP 1 3 I O Combined Module MEMO ...
Page 16: ...14 2 PART NAMES MEMO ...
Page 43: ...4 PROCEDURES BEFORE OPERATION 41 4 MEMO ...
Page 45: ...5 SYSTEM CONFIGURATION 43 5 MEMO ...
Page 76: ...74 9 PROGRAMMING 9 2 Program Example Program example ...
Page 78: ...76 10 MAINTENANCE AND INSPECTION MEMO ...
Page 119: ...APPX Appendix 8 External Dimensions 117 A MEMO ...
Page 121: ...I 119 MEMO ...
Page 125: ......