3 SPECIFICATIONS
3.2 Performance Specifications
19
3
NZ2MFB1-32D DC input module
*1 If the input response time is set to "0ms", the actual input response time is 80
s at OFF
ON, and 160
s at ON
OFF.
*2 It is the noise immunity of when the input response time setting value is other than "0ms". Note that the module is easily affected by
noise if "0ms" is set.
*3 Only one wire can be connected to a terminal of the terminal block for module power supply and FG. Multiple wires cannot be connected
to a terminal. Connecting two or more wires may cause a poor contact.
*4 It is recommended to use the bar solderless terminal for wiring.
Item
NZ2MFB1-32D
Station type
Slave station
Number of input points
32 points
Rated input voltage
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Rated input current
6.0mA TYP. (for 24VDC)
Isolation method
Photocoupler isolation
Max. number of simultaneous input points
100%
ON voltage/ON current
15VDC or more/4mA or more
OFF voltage/OFF current
5VDC or less/1.7mA or less
Input resistance
3.8k
Input response time
OFF
ON
0ms
/0.2ms/1ms/1.5ms/5ms/10ms/20ms/70ms
(Initial setting: 10ms)
ON
OFF
Input type
Positive common/negative common shared type
Withstand voltage
500VAC for 1 minute between all DC external terminals and the ground
Insulation resistance
10M
or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise immunity
Noise voltage 500Vp-p, noise width 1
s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
Protection degree
IP2X
Wiring method for common
32 points/common (two points) (1-wire, screw terminal block type)
External interface
Communication part
RJ45 connector
Module power supply part
Terminal block for module power supply and FG (Two-piece spring clamp terminal block (push-in
type))
I/O part
34-point one-piece terminal block
Tightening torque range for terminal screw (M3
5.2 screw): 0.59 to 0.88N
m
Applicable DIN rail
TH35-7.5Fe, TH35-7.5Al (compliant with IEC 60715)
Applicable wire size
For power supply
Stranded wire: 0.3 to 1.5
(22 to 16 AWG), terminal slot size: 2.8mm
2.0mm
For I/O
Core: 0.3 to 2.0
(22 to 14 AWG)
Applicable solderless
terminal
Terminal block for module
power supply and FG
Page 59 Applicable solderless terminal
Terminal block for input
Page 62 Applicable solderless terminal
Number of occupied stations
One station
Reference response time
1ms
Communication cable
An Ethernet cable that meets the 100BASE-TX standard
For details, refer to the following.
CC-Link IE Field Network Basic Reference Manual
Module power supply
Voltage
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Current
71mA or less (24VDC, all points ON)
Weight
0.30kg
Summary of Contents for NZ2MFB1-32D
Page 2: ......
Page 14: ...12 1 PRODUCT LINEUP 1 3 I O Combined Module MEMO ...
Page 16: ...14 2 PART NAMES MEMO ...
Page 43: ...4 PROCEDURES BEFORE OPERATION 41 4 MEMO ...
Page 45: ...5 SYSTEM CONFIGURATION 43 5 MEMO ...
Page 76: ...74 9 PROGRAMMING 9 2 Program Example Program example ...
Page 78: ...76 10 MAINTENANCE AND INSPECTION MEMO ...
Page 119: ...APPX Appendix 8 External Dimensions 117 A MEMO ...
Page 121: ...I 119 MEMO ...
Page 125: ......