66
8 FUNCTIONS
8.2 Output HOLD/CLEAR Setting Function
8.2
Output HOLD/CLEAR Setting Function
When the I/O module is disconnected from data link, or the CPU module operating status is STOP, whether to hold or clear
the last output value can be set by this function.
Output HOLD/CLEAR setting and its operation
When HOLD or CLEAR is set for an output, the output is turned on or off as follows.
If a moderate or major error has occurred in the I/O module, output turns off regardless of the output HOLD/CLEAR setting.
Setting method
1.
Set HOLD or CLEAR using the function setting switch 4 of I/O module.
The setting status of output HOLD/CLEAR setting can be checked by bit3 of detailed module information (upper).
For details, refer to the following.
Page 105 Detailed module information (upper)
Operating status
Output HOLD/CLEAR setting
HOLD
Output HOLD/CLEAR setting
CLEAR
Last output status
OFF
Last output status
ON
Last output status
OFF
Last output status
ON
Data link in operation
CPU module in RUN
OFF
ON
OFF
ON
CPU module in STOP
OFF
ON
OFF
OFF
CPU module in PAUSE
OFF
ON
OFF
ON
CPU module in RESET
OFF
ON
OFF
OFF
CPU module suspended by
error
OFF
ON
OFF
OFF
During disconnection/cyclic stop
OFF
ON
OFF
OFF
Function setting switch 4
Output HOLD/CLEAR setting
4
OFF
CLEAR (default)
ON
HOLD
Summary of Contents for NZ2MFB1-32D
Page 2: ......
Page 14: ...12 1 PRODUCT LINEUP 1 3 I O Combined Module MEMO ...
Page 16: ...14 2 PART NAMES MEMO ...
Page 43: ...4 PROCEDURES BEFORE OPERATION 41 4 MEMO ...
Page 45: ...5 SYSTEM CONFIGURATION 43 5 MEMO ...
Page 76: ...74 9 PROGRAMMING 9 2 Program Example Program example ...
Page 78: ...76 10 MAINTENANCE AND INSPECTION MEMO ...
Page 119: ...APPX Appendix 8 External Dimensions 117 A MEMO ...
Page 121: ...I 119 MEMO ...
Page 125: ......