88
11 TROUBLESHOOTING
11.4 Examples of Troubles with the I/O Module
A load momentarily turns on from off when the system is powered off
■
Cause
When an inductive load is connected, [2] Load may turn on from off due to a sneak current of back EMF at [1] Shutoff.
ON
OFF
ON
OFF
Y0
Y1
COM+
CTL-
Y0
Y1
COM-
CTL+
[2]
[2]
Load
Load
Load
Load
Output module
- Back electromotive force + [3]
+ Back electromotive force - [3]
Output module
Sink output
[1] Shut off
[1] Shut off
Source output