6
8.2
Ⓕ
Use PG bushing to keep the weight of the cable and external force from being applied to
the power supply terminal connector. Use a cable tie to secure the cable.
Ⓖ
Indoor unit/outdoor unit connecting wire
Ⓗ
Use ordinary bushing
Ⓘ
Remote controller cable
Ⓙ
Tensile force
Ⓚ
Terminal block for indoor/outdoor unit connecting wire
Ⓛ
Terminal block for remote controller cable
[Fig. 8-2-3]
[Fig. 8-2-4]
Ⓒ
Terminal block box
Ⓓ
Knockout hole
Ⓔ
Remove
Ⓐ
Screw holding cover (2pc)
Ⓑ
Cover
[Fig. 8-2-1]
[Fig. 8-2-2]
8
Ⓐ
Ⓑ
Ⓒ
Ⓓ
Ⓔ
Ⓙ
Ⓗ
Ⓕ
Ⓖ
Ⓘ
1
2
M1
M2
S
Ⓛ
Ⓚ
[Fig. 8-2-5]
Ⓐ
Indoor terminal block
Ⓑ
Earth wire (green/yellow)
Ⓒ
Indoor/outdoor unit connecting wire
3-core 1.5 mm
2
or more
Ⓓ
Outdoor terminal block
Ⓔ
Power supply cord : 2.0 mm
2
or more
①
Connecting cable
Cable 3-core 1.5 mm
2
, in conformity
with Design 245 IEC 57.
②
Indoor terminal block
③
Outdoor terminal block
Ⓐ
④
Always install an earth wire (1-core 1.5 mm
2
)
longer than other cables
⑤
Remote controller cable
Wire No
×
size (mm
2
) : Cable 2C
×
0.3
This wire accessory of remote controller
(wire length : 10m, non-polar. Max. 500m)
⑥
Wired remote controller (option)
⑦
Power supply cord
C a b l e 3 - c o r e 2 . 0 m m
2
o r m o r e , i n
conformity with Design 245 IEC 57.
1 2
⑥
⑤
②
④
③
⑦
L N
①
Ⓒ
Ⓓ
Ⓑ
Ⓔ