background image

17

8.1.  Power supply

8.1.1.  Indoor unit power supplied from outdoor unit

[Fig. 8-1] (P.5)

 Outdoor unit power supply

 Earth leakage breaker

 Wiring circuit breaker or isolating switch

 Outdoor unit

 Indoor unit/outdoor unit connecting cords

 Remote controller (option)

 Indoor unit

Field electrical wiring

Indoor unit model

PEA

Wiring Wire No. 

×

 size (mm

2

)

Indoor unit power supply (Heater) 

Indoor unit power supply (Heater) earth 

Indoor unit-Outdoor unit 

×

 1.5 (polar)

Indoor unit-Outdoor unit earth 

×

 Min. 1.5

Remote controller-Indoor unit  

*1

×

 0.3 (Non-polar)

Circuit rating

Indoor unit (Heater) L-N  

*2

Indoor unit-Outdoor unit S1-S2  

*2

230 V AC

Indoor unit-Outdoor unit S2-S3 

*2

24 V DC

Remote controller-Indoor unit  

*2

14 V DC

*1. The 10 m wire is attached in the remote controller accessory. Max. 500 m

*2. The figures are NOT always against the ground.
  S3 terminal has 24 V DC against S2 terminal. However between S3 and S1, these terminals 

are not electrically insulataed by the transformer or other device.

Notes:  1.  Wiring size must comply with the applicable local and national 

code.

 

2.  Power supply cords and indoor unit/outdoor unit connecting 

cords shall not be lighter than polychloroprene sheathed flexible 

cord. (Design 245 IEC57)

 

3.  Install an earth longer than other cables.

•  PEA-RP∙GAA  has  two  power  boards  and  two  control  boards  respectively. 

 

(AB in Fig. 8-1)

  Check the wiring details on the plate affixed to the unit and be sure not to wire 

incorrectly.

•  PEA-RP∙GAA  has  two  control  boards. Therefore,  “No.1”  unit  or  “No.2”  unit  is 

displayed on the remote controller when an initial setup is performed or an error 

occurs.

  Control Board A is not always No.1 unit and Control Board B is not always No.2 

unit. Check the both control boards in case of a malfunction of the fan motor or 

the sensor.

•  Connect the connectors of external input/output devices to the circuit board to 

which the remote controller is connected.

8.  Electrical work

8.2.  Indoor wire connection

Please identify the model name of the operation manual attached on the terminal 

block box with that shown on the rating name plate.

1.  Remove the screw (2pcs) holding the cover to dismount the cover. 

[Fig. 8-2-1] (P.6)

 Screw holding cover (2pcs) 

 Cover

2.  Open knockout holes

  (Recommend to use a screwdriver or the like for this work.)

[Fig. 8-2-2] (P.6)

 Terminal block box 

 Knockout hole

 Remove

3.  Fix indoor unit/outdoor unit connecting wire to terminal block box by using buffer 

bushing for tensile force. (PG connection or the like.) Connect remote controller 

cable to terminal block through the knockout hole of terminal block box using 

ordinary bushing.

[Fig. 8-2-3] (P.6)

 Use PG bushing to keep the weight of the cable and external force from being applied to 

the power supply terminal connector. Use a cable tie to secure the cable.

 Indoor unit/outdoor unit connecting wire 

 Use ordinary bushing

 Remote controller cable 

 Tensile force

[Fig. 8-2-4] (P.6)

 Terminal block for indoor/outdoor unit connecting wire

 Terminal block for remote controller cable

4.  After wiring is complete, make sure again that there is no slack on the 

connections, and attach the cover onto the terminal block box in the reverse 

order of removal. 

 Warning:

•  Attach the electrical part cover securely. If it is attached incorrectly, it could 

result in a fire, electric shock due to dust, water, etc.

•  Use the specified indoor/outdoor unit connecting wire to connect the 

indoor and outdoor units and fix the wire to the terminal block securely so 

that no stress is applied to the connecting section of the terminal block.  

Incomplete connection or fixing of the wire could result in a fire.

•  Do not pinch the cables or wires when attaching the terminal block box 

cover. Doing so may cause a risk of disconnection.

•  When accommodating the terminal block box, make sure that the connectors 

on the box side are not removed. If removed, it cannot operate normally.

[Fig. 8-2-5] (P.6)

 Indoor terminal block

 Earth wire (green/yellow)

 Indoor/outdoor unit connecting wire 3-core 1.5 mm

2

 or more

 Outdoor terminal block

 Power supply cord : 2.0 mm

or more

 Connecting cable

  Cable 3-core 1.5 mm

2

, in conformity with Design 245 IEC 57.

 Indoor terminal block

 Outdoor terminal block

 Always install an earth wire (1-core 1.5 mm

2

) longer than other cables

 Remote controller cable

  Wire No 

×

 size (mm

2

) : Cable 2C 

×

 0.3

  This wire accessory of remote controller

  (wire length : 10 m, non-polar. Max. 500 m)

 Wired remote controller (option)

 Power supply cord

    Cable 3-core 2.0 mm

2

 or more, in conformity with Design 245 IEC 57.

•  Perform wiring as shown in 

[Fig. 8-2-5] (P.6)

. (Procure the cable locally.) 

  Make sure to use cables of the correct polarity only.

•  Connect the terminal blocks as shown in  

[Fig. 8-2-5] (P.6)

.

 Caution:

•  Use care not to make mis-wiring. 

•  Firmly tighten the terminal screws to prevent them from loosening.

•  After tightening, pull the wires lightly to confirm that they do not move.

8.3.  Remote controller (wired remote controller (option))

8.3.1.  For wired remote controller

1)  Installing procedures

(1) Select an installing position for the remote controller.

The temperature sensors are located on both remote controller and indoor unit.

 

Procure the following parts locally:

  Two piece switch box

  Thin copper conduit tube

  Lock nuts and bushings

[Fig. 8-3-1] (P.7)

 Remote controller profile

 Required clearances surrounding the remote controller

 Installation pitch

(2) Seal  the  service  entrance  for  the  remote  controller  cord  with  putty  to  prevent 

possible invasion of dew drops, water, cockroaches or worms.

[Fig. 8-3-2] (P.7)

 For installation in the switch box:

 For direct installation on the wall select one of the following:

•  Prepare  a  hole  through  the  wall  to  pass  the  remote  controller  cord  (in  order  to  run  the 

remote controller cord from the back), then seal the hole with putty.

•  Run the remote controller cord through the cut-out upper case, then seal the cut-out notch 

with putty similarly as above.

 Wall 

 Switch box

 Conduit 

 Remote controller cord

 Lock nut 

 Seal with putty

 Bushing 

 Wood screw

B-1.  To lead the remote controller cord from the back of the controller:

B-2.  To run the remote controller cord through the upper portion:

(3) For direct installation on the wall

2)  Connecting procedures

  Connect the remote controller cord to the terminal block.

[Fig. 8-3-3] (P.7)

 To the terminal block on the indoor unit

 TB6 (No polarity)

 Set the dip switch No.1 shown below when using two remote controller’s for the 

same group.

3)  Function selection of remote controller

If two remote controllers are connected, set one to “Main” and the other to “Sub”. 

For  setting  procedures,  refer  to  “Function  selection  of  remote  controller”  in  the 

operation manual for the indoor unit.

Summary of Contents for Mr.Slim PEA-RP100

Page 1: ...NSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit Air Conditioners PEA RP100 125 140GAA ORIGINAL English FOR INSTALLER ...

Page 2: ...t without inlet duct When hanging the indoor unit directly without inlet duct When connecting inlet duct When installing the suspension fixtures prior to installation of the indoor unit without inlet duct When hanging the indoor unit directly without inlet duct Electric box Access door 2 Access door 1 Ceiling Access door 2 Ceiling beam Supply air Intake air Electric box Min 300mm Min 500mm Min 500...

Page 3: ...ter of gravity 5 1 98 680 200 1300 235 Ⓐ Ⓐ Ⓑ 4 1 A 30 B Ⓐ Ⓑ Ⓐ 1 A 30 B 10 Ⓐ Fig 5 1 2 Fig 5 1 3 Ⓐ Nut Ⓑ Washer Ⓐ Be sure to attach a U shaped washer 4 washers in total 6 øB øA ⓐ ⓑ Fig 6 1 ⓐ Indoor unit ⓑ Outdoor unit 6 1 Model A B PEA RP100 125 140 ø15 88 ø9 52 ...

Page 4: ...ping Ⓓ Gas end of refrigerant piping Ⓔ Site refrigerant piping Ⓕ Main body Ⓖ Pipe cover large accessory Ⓗ Thermal insulation field supply Ⓘ Pull Ⓙ Flare nut Ⓚ Return to original position Ⓐ Ⓑ Ⓒ Ⓓ Ⓕ Ⓖ Ⓔ Ⓗ Ⓗ Ⓚ Ⓛ Ⓙ Ⓘ Ⓙ Ⓞ Ⓞ Ⓝ Ⓝ 20 20 20 20 Fig 6 2 1 Fig 6 2 4 Fig 6 2 2 Fig 6 2 3 ⓐ Flare nut ⓑ Copper tube ⓐ Burr ⓑ Copper tube pipe ⓒ Spare reamer ⓓ Pipe cutter Fig 6 2 5 Fig 6 3 1 ⓐ Flaring tool ⓑ Die ⓒ C...

Page 5: ...Air outlet Ⓒ Access door Ⓓ Ceiling surface Ⓔ Canvas duct Ⓕ Keep duct work length 850 or more Ⓖ Connect common reference potential wire between duct work to air conditioner Ⓐ Inlet duct flange Ⓑ Return air temperature sensor Ⓒ Sensor protection plate Ⓓ Sensor fixture Ⓔ Inlet duct Ⓔ S1 S1 S1 S2 S2 S2 S2 S2 S2 S3 S3 1 1 2 2 S3 S1 S2 L TB4 TB TB15 CND CND CN3C CN3C CN22 N S3 Ⓐ Ⓑ Ⓒ Ⓕ Ⓖ Ⓓ Indoor Control...

Page 6: ...2 1 Fig 8 2 2 8 Ⓐ Ⓑ Ⓒ Ⓓ Ⓔ Ⓙ Ⓗ Ⓕ Ⓖ Ⓘ 1 2 M1 M2 S Ⓛ Ⓚ Fig 8 2 5 Ⓐ Indoor terminal block Ⓑ Earth wire green yellow Ⓒ Indoor outdoor unit connecting wire 3 core 1 5 mm2 or more Ⓓ Outdoor terminal block Ⓔ Power supply cord 2 0 mm2 or more Connecting cable Cable 3 core 1 5 mm2 in conformity with Design 245 IEC 57 Indoor terminal block Outdoor terminal block Ⓐ Always install an earth wire 1 core 1 5 mm2 ...

Page 7: ...ller cord through the cut out upper case then seal the cut out notch with putty similarly as above Ⓒ Wall Ⓓ Conduit Ⓔ Lock nut Ⓕ Bushing Ⓖ Switch box Ⓗ Remote controller cord Ⓘ Seal with putty Ⓙ Wood screw Ⓕ Ⓐ Ⓗ Ⓒ Ⓓ Ⓔ Ⓖ Ⓘ Ⓘ Ⓘ Ⓗ Ⓑ Ⓙ Ⓗ B 1 B 2 Fig 8 3 2 8 Ⓐ AB TB6 Ⓑ Ⓐ To the terminal block on the indoor unit Ⓑ TB6 No polarity Fig 8 3 3 30 46 30 30 120 83 5 Ⓐ Ⓑ Ⓒ Ⓐ Remote controller profile Ⓑ Require...

Page 8: ... Ⓒ Ⓐ Fix tightly with tape Ⓑ Remote controller wire Ⓒ Order wire Indoor unit Fig 8 4 2 Fig 8 4 5 Ⓗ Ⓙ Ⓘ When using the switch box When installing directly on the wall Ⓐ 150 mm 5 15 16 inch Ⓑ Remote controller wire Ⓒ Wiring pipe Ⓓ Locknut Ⓗ Seal around here with putty Ⓘ Remote controller wire Ⓙ Seal around here with putty Ⓔ Bushing Ⓕ Switch box Ⓖ Seal around here with putty Ⓒ Ⓓ Ⓑ Ⓕ Ⓔ Ⓖ Ⓐ Wall 8 8 4 ...

Page 9: ...e lower case directly on the wall or the ceiling use wood screws Insert the minus screwdriver toward the arrow pointed and wrench it to remove the cover A flat screwdriver whose width of blade is between 4 and 7mm 5 32 9 32inch must be used Fig 8 4 9 Ⓐ Hang the cover to the upper hooks 2 places Mount the cover to the lower case Ⓐ Cross section of upper hooks ...

Page 10: ...er 0 Pair number 1 Pair number 2 Pair number 3 Pair number 0 Pair number 1 Pair number 2 Pair number 3 Pair number 0 Pair number 0 Pair number 0 Pair number 0 Ⓐ CN2A CN3C SW2 SW1 JP1 JP2 JP3 JP41 JP42 CN22 CN2L CNXA2 CN32 SWE CN20 CN90 CN105 CN41 CN4F CN51 CNXB2 CNXC2 CN44 ON OFF Indoor controller board ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK CHEC...

Page 11: ...ACK DAY MONITOR SET CLOCK ON OFF Ⓐ Ⓑ Ⓓ Ⓒ Ⓖ Ⓔ Ⓕ Ⅰ Ⅱ Ⅲ Ⅳ Ⅰ Ⅰ Ⅳ Ⅱ Ⓐ Filter button Enter button Ⓑ TEST button Ⓒ Set Time button Ⓓ Timer On Off button Set Day button Ⓔ Mode selection button Ⓕ Set temperature button Ⓖ Timer Menu button Monitor Set button Mode number Setting number Refrigerant address Unit number Ⅰ Ⅱ Ⅲ Ⅳ CHECK CHECK CHECK CHECK ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOU...

Page 12: ...pe Ⓓ Gas pipe Ⓔ Stop valve Ⓕ Outdoor unit Ⓖ Refrigerant gas cylinder operating valve Ⓗ Refrigerant gas cylinder for R410A with siphon Ⓘ Refrigerant liquid Ⓙ Electronic scale for refrigerant charging Ⓚ Charge hose for R410A Ⓛ Gauge manifold valve for R410A Ⓜ Service port 10 1 ...

Page 13: ...er to avoid a hazard Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the service panel in the outdoor unit are not attached securely it could result in a fire or an electric shock due to dust water etc Be sure to use the part provided or specified parts for the installation work The use of...

Page 14: ...n a space of less than 500mm is available below the unit between the unit and the ceiling At least 300 mm of space should be left below the unit as shown in Fig 3 2 4 Fig 3 2 5 Create access door 3 below the electric box and the unit as shown in Fig 3 2 6 Fig 3 2 1 P 2 Fig 3 2 2 P 2 Fig 3 2 3 P 2 Fig 3 2 4 P 2 Fig 3 2 5 P 2 Fig 3 2 6 P 2 3 3 Indoor unit accessories The unit is provided with the fo...

Page 15: ...rant piping Ⓕ Main body Ⓖ Pipe cover large accessory Ⓗ Thermal insulation field supply Ⓘ Pull Ⓙ Flare nut Ⓚ Return to original position Ⓛ Ensure that there is no gap here Ⓜ Plate on main body Ⓝ Band accessory Ⓞ Ensure that there is no gap here Place join upwards 0 0 4 6 1 Refrigerant pipe Fig 6 1 P 3 ⓐ Indoor unit ⓑ Outdoor unit Refer to the Instruction Manual that came with the outdoor unit for t...

Page 16: ...nting the back flow Charge hose for R410A Service port Stop valve Close Open Stop valve Tighten the cap to the service port to obtain the initial status Retighten the cap Leak test 6 5 Drain piping work Fig 6 5 P 4 Ⓐ Insulator Ⓑ Drain pipe R1 Ⓒ Drain pan Ⓓ 70 mm Ⓔ 2 Ⓕ 70 mm Ⓕ 35 mm Ⓖ Downward slope 20 mm m or more Ⓗ Drain trap Ⓘ The drain pipe should extend below this level Ⓙ Open drain In connect...

Page 17: ...ly If it is attached incorrectly it could result in a fire electric shock due to dust water etc Use the specified indoor outdoor unit connecting wire to connect the indoor and outdoor units and fix the wire to the terminal block securely so that no stress is applied to the connecting section of the terminal block Incomplete connection or fixing of the wire could result in a fire Do not pinch the c...

Page 18: ...ll portion inside the bottom case oblique section by a knife or a nipper Take out the connected remote controller wire to the terminal block through this space 6 Install the lower case on the switch box or directly on the wall Fig 8 4 8 P 9 Mounting the cover Fig 8 4 9 P 9 Caution Insert the cover securely until the clicking sound is made If not doing so the cover may fall 8 4 Remote controller wi...

Page 19: ...nit number Press the TEMP button Ⓒ and Ⓓ to set the unit number to 07 Direct the wireless remote controller toward the receiver of the indoor unit and press the Minute button Ⓑ Selecting a mode Enter 08 to change the external static pressure setting using the Ⓒ and Ⓓ buttons Direct the wireless remote controller toward the receiver of the indoor unit and press the Hour button Ⓐ Current setting num...

Page 20: ...d is switched Check operation of the outdoor unit fan Release test run by pressing the ON OFF button Stop Register a telephone number The telephone number of the repair shop sales office etc to contact if an error occurs can be registered in the remote controller The telephone number will be displayed when an error occurs For registration procedures refer to the operation manual for the indoor uni...

Page 21: ...ical manual for the outdoor unit 1 If the beeper does not sound again after the initial two beeps to confirm the self check start signal was received and the OPERATION INDICATOR lamp does not come on there are no error records 2 If the beeper sounds three times continuously beep beep beep 0 4 0 4 0 4 sec after the initial two beeps to confirm the self check start signal was received the specified ...

Page 22: ...on But never use naked fire or steam 9 Test run For description of each LED LED1 2 3 provided on the indoor controller refer to the following table LED 1 power for microcomputer Indicates whether control power is supplied Make sure that this LED is always lit LED 2 power for remote controller Indicates whether power is supplied to the remote controller This LED lights only in the case of the indoo...

Page 23: ......

Page 24: ...Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN KD79M111H02 ...

Reviews: