background image

22

10. Maintenance

10.1.  Gas charge

[Fig. 10-1] (P.12)

Ⓐ 

Indoor unit

Ⓑ 

Union

Ⓒ 

Liquid pipe

Ⓓ 

Gas pipe

Ⓔ 

Stop valve

Ⓕ 

Outdoor unit

Ⓖ 

Refrigerant gas cylinder operating valve

Ⓗ 

Refrigerant gas cylinder for R410A with siphon

Ⓘ 

Refrigerant (liquid)

Ⓙ 

Electronic scale for refrigerant charging

Ⓚ 

Charge hose (for R410A)

Ⓛ 

Gauge manifold valve (for R410A)

Ⓜ 

Service port

1.  Connect gas cylinder to the service port of stop valve (3-way).

2.  Execute air purge of the pipe (or hose) coming from refrigerant gas 

cylinder.

3.  Replenish  specified  amount  of  refrigerant,  while  running  the  air 

conditioner for cooling.

Note: 

In case of adding refrigerant, comply with the quantity specified for the refrigerating 

cycle.

 Caution:

•  Do not discharge the refrigerant into the atmosphere. 

  Take  care  not  to  discharge  refrigerant  into  the  atmosphere  during 

installation, reinstallation, or repairs to the refrigerant circuit.

•  For additional charging, charge the refrigerant from liquid phase of the gas 

cylinder. 

  If the refrigerant is charged from the gas phase, composition change may 

occur in the refrigerant inside the cylinder and the outdoor unit. In this 

case, ability of the refrigerating cycle decreases or normal operation can be 

impossible. However, charging the liquid refrigerant all at once may cause 

the compressor to be locked. Thus, charge the refrigerant slowly.

To maintain the high pressure of the gas cylinder, warm the gas cylinder with warm 

water (under 40°C) during cold season. But never use naked fire or steam.

9.  Test run

For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.

LED 1 (power for microcomputer)

Indicates whether control power is supplied. Make sure that this LED is always lit.

LED 2 (power for remote controller)

Indicates whether power is supplied to the remote controller. This LED lights only in the case of

the indoor unit which is connected to the outdoor unit refrigerant address “0”. 

LED 3 (communication between indoor and outdoor units)

Indicates state of communication between the indoor and outdoor units. Make sure that this LED is
always blinking.

9.4.  AUTO RESTART FUNCTION

Indoor controller board

This model is equipped with the AUTO RESTART FUNCTION.

When the indoor unit  is controlled with the remote controller, the operation mode, set temperature, and the fan speed are memorized by the indoor controller board.

The auto restart function sets to work the moment the power has restored after power failure, then, the unit will restart automatically.

Set the AUTO RESTART FUNCTION using the remote controller. (Mode no.01)

On the wireless remote controller with conditions above, following phenomena takes place.

•  No signals from the remote controller are accepted.

•  OPE lamp is blinking.

•  The buzzer makes a short ping sound.

Note:

Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)

11. Specifications

Model

PEA-RP100GAA

PEA-RP125, 140GAA

Power input

kW

0.21

0.49

Current

A

1.83

3.84

Air flow rate
(Hi-Lo)

50Pa

m

3

/min

42-34

60-48

100Pa

54-43

150Pa

52-41

Sound level at 50Pa

(Hi-Lo)

dB(A)

42-39

45-42

Weight

kg

63

63

Summary of Contents for Mr.Slim PEA-RP100

Page 1: ...NSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit Air Conditioners PEA RP100 125 140GAA ORIGINAL English FOR INSTALLER ...

Page 2: ...t without inlet duct When hanging the indoor unit directly without inlet duct When connecting inlet duct When installing the suspension fixtures prior to installation of the indoor unit without inlet duct When hanging the indoor unit directly without inlet duct Electric box Access door 2 Access door 1 Ceiling Access door 2 Ceiling beam Supply air Intake air Electric box Min 300mm Min 500mm Min 500...

Page 3: ...ter of gravity 5 1 98 680 200 1300 235 Ⓐ Ⓐ Ⓑ 4 1 A 30 B Ⓐ Ⓑ Ⓐ 1 A 30 B 10 Ⓐ Fig 5 1 2 Fig 5 1 3 Ⓐ Nut Ⓑ Washer Ⓐ Be sure to attach a U shaped washer 4 washers in total 6 øB øA ⓐ ⓑ Fig 6 1 ⓐ Indoor unit ⓑ Outdoor unit 6 1 Model A B PEA RP100 125 140 ø15 88 ø9 52 ...

Page 4: ...ping Ⓓ Gas end of refrigerant piping Ⓔ Site refrigerant piping Ⓕ Main body Ⓖ Pipe cover large accessory Ⓗ Thermal insulation field supply Ⓘ Pull Ⓙ Flare nut Ⓚ Return to original position Ⓐ Ⓑ Ⓒ Ⓓ Ⓕ Ⓖ Ⓔ Ⓗ Ⓗ Ⓚ Ⓛ Ⓙ Ⓘ Ⓙ Ⓞ Ⓞ Ⓝ Ⓝ 20 20 20 20 Fig 6 2 1 Fig 6 2 4 Fig 6 2 2 Fig 6 2 3 ⓐ Flare nut ⓑ Copper tube ⓐ Burr ⓑ Copper tube pipe ⓒ Spare reamer ⓓ Pipe cutter Fig 6 2 5 Fig 6 3 1 ⓐ Flaring tool ⓑ Die ⓒ C...

Page 5: ...Air outlet Ⓒ Access door Ⓓ Ceiling surface Ⓔ Canvas duct Ⓕ Keep duct work length 850 or more Ⓖ Connect common reference potential wire between duct work to air conditioner Ⓐ Inlet duct flange Ⓑ Return air temperature sensor Ⓒ Sensor protection plate Ⓓ Sensor fixture Ⓔ Inlet duct Ⓔ S1 S1 S1 S2 S2 S2 S2 S2 S2 S3 S3 1 1 2 2 S3 S1 S2 L TB4 TB TB15 CND CND CN3C CN3C CN22 N S3 Ⓐ Ⓑ Ⓒ Ⓕ Ⓖ Ⓓ Indoor Control...

Page 6: ...2 1 Fig 8 2 2 8 Ⓐ Ⓑ Ⓒ Ⓓ Ⓔ Ⓙ Ⓗ Ⓕ Ⓖ Ⓘ 1 2 M1 M2 S Ⓛ Ⓚ Fig 8 2 5 Ⓐ Indoor terminal block Ⓑ Earth wire green yellow Ⓒ Indoor outdoor unit connecting wire 3 core 1 5 mm2 or more Ⓓ Outdoor terminal block Ⓔ Power supply cord 2 0 mm2 or more Connecting cable Cable 3 core 1 5 mm2 in conformity with Design 245 IEC 57 Indoor terminal block Outdoor terminal block Ⓐ Always install an earth wire 1 core 1 5 mm2 ...

Page 7: ...ller cord through the cut out upper case then seal the cut out notch with putty similarly as above Ⓒ Wall Ⓓ Conduit Ⓔ Lock nut Ⓕ Bushing Ⓖ Switch box Ⓗ Remote controller cord Ⓘ Seal with putty Ⓙ Wood screw Ⓕ Ⓐ Ⓗ Ⓒ Ⓓ Ⓔ Ⓖ Ⓘ Ⓘ Ⓘ Ⓗ Ⓑ Ⓙ Ⓗ B 1 B 2 Fig 8 3 2 8 Ⓐ AB TB6 Ⓑ Ⓐ To the terminal block on the indoor unit Ⓑ TB6 No polarity Fig 8 3 3 30 46 30 30 120 83 5 Ⓐ Ⓑ Ⓒ Ⓐ Remote controller profile Ⓑ Require...

Page 8: ... Ⓒ Ⓐ Fix tightly with tape Ⓑ Remote controller wire Ⓒ Order wire Indoor unit Fig 8 4 2 Fig 8 4 5 Ⓗ Ⓙ Ⓘ When using the switch box When installing directly on the wall Ⓐ 150 mm 5 15 16 inch Ⓑ Remote controller wire Ⓒ Wiring pipe Ⓓ Locknut Ⓗ Seal around here with putty Ⓘ Remote controller wire Ⓙ Seal around here with putty Ⓔ Bushing Ⓕ Switch box Ⓖ Seal around here with putty Ⓒ Ⓓ Ⓑ Ⓕ Ⓔ Ⓖ Ⓐ Wall 8 8 4 ...

Page 9: ...e lower case directly on the wall or the ceiling use wood screws Insert the minus screwdriver toward the arrow pointed and wrench it to remove the cover A flat screwdriver whose width of blade is between 4 and 7mm 5 32 9 32inch must be used Fig 8 4 9 Ⓐ Hang the cover to the upper hooks 2 places Mount the cover to the lower case Ⓐ Cross section of upper hooks ...

Page 10: ...er 0 Pair number 1 Pair number 2 Pair number 3 Pair number 0 Pair number 1 Pair number 2 Pair number 3 Pair number 0 Pair number 0 Pair number 0 Pair number 0 Ⓐ CN2A CN3C SW2 SW1 JP1 JP2 JP3 JP41 JP42 CN22 CN2L CNXA2 CN32 SWE CN20 CN90 CN105 CN41 CN4F CN51 CNXB2 CNXC2 CN44 ON OFF Indoor controller board ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK CHEC...

Page 11: ...ACK DAY MONITOR SET CLOCK ON OFF Ⓐ Ⓑ Ⓓ Ⓒ Ⓖ Ⓔ Ⓕ Ⅰ Ⅱ Ⅲ Ⅳ Ⅰ Ⅰ Ⅳ Ⅱ Ⓐ Filter button Enter button Ⓑ TEST button Ⓒ Set Time button Ⓓ Timer On Off button Set Day button Ⓔ Mode selection button Ⓕ Set temperature button Ⓖ Timer Menu button Monitor Set button Mode number Setting number Refrigerant address Unit number Ⅰ Ⅱ Ⅲ Ⅳ CHECK CHECK CHECK CHECK ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOU...

Page 12: ...pe Ⓓ Gas pipe Ⓔ Stop valve Ⓕ Outdoor unit Ⓖ Refrigerant gas cylinder operating valve Ⓗ Refrigerant gas cylinder for R410A with siphon Ⓘ Refrigerant liquid Ⓙ Electronic scale for refrigerant charging Ⓚ Charge hose for R410A Ⓛ Gauge manifold valve for R410A Ⓜ Service port 10 1 ...

Page 13: ...er to avoid a hazard Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the service panel in the outdoor unit are not attached securely it could result in a fire or an electric shock due to dust water etc Be sure to use the part provided or specified parts for the installation work The use of...

Page 14: ...n a space of less than 500mm is available below the unit between the unit and the ceiling At least 300 mm of space should be left below the unit as shown in Fig 3 2 4 Fig 3 2 5 Create access door 3 below the electric box and the unit as shown in Fig 3 2 6 Fig 3 2 1 P 2 Fig 3 2 2 P 2 Fig 3 2 3 P 2 Fig 3 2 4 P 2 Fig 3 2 5 P 2 Fig 3 2 6 P 2 3 3 Indoor unit accessories The unit is provided with the fo...

Page 15: ...rant piping Ⓕ Main body Ⓖ Pipe cover large accessory Ⓗ Thermal insulation field supply Ⓘ Pull Ⓙ Flare nut Ⓚ Return to original position Ⓛ Ensure that there is no gap here Ⓜ Plate on main body Ⓝ Band accessory Ⓞ Ensure that there is no gap here Place join upwards 0 0 4 6 1 Refrigerant pipe Fig 6 1 P 3 ⓐ Indoor unit ⓑ Outdoor unit Refer to the Instruction Manual that came with the outdoor unit for t...

Page 16: ...nting the back flow Charge hose for R410A Service port Stop valve Close Open Stop valve Tighten the cap to the service port to obtain the initial status Retighten the cap Leak test 6 5 Drain piping work Fig 6 5 P 4 Ⓐ Insulator Ⓑ Drain pipe R1 Ⓒ Drain pan Ⓓ 70 mm Ⓔ 2 Ⓕ 70 mm Ⓕ 35 mm Ⓖ Downward slope 20 mm m or more Ⓗ Drain trap Ⓘ The drain pipe should extend below this level Ⓙ Open drain In connect...

Page 17: ...ly If it is attached incorrectly it could result in a fire electric shock due to dust water etc Use the specified indoor outdoor unit connecting wire to connect the indoor and outdoor units and fix the wire to the terminal block securely so that no stress is applied to the connecting section of the terminal block Incomplete connection or fixing of the wire could result in a fire Do not pinch the c...

Page 18: ...ll portion inside the bottom case oblique section by a knife or a nipper Take out the connected remote controller wire to the terminal block through this space 6 Install the lower case on the switch box or directly on the wall Fig 8 4 8 P 9 Mounting the cover Fig 8 4 9 P 9 Caution Insert the cover securely until the clicking sound is made If not doing so the cover may fall 8 4 Remote controller wi...

Page 19: ...nit number Press the TEMP button Ⓒ and Ⓓ to set the unit number to 07 Direct the wireless remote controller toward the receiver of the indoor unit and press the Minute button Ⓑ Selecting a mode Enter 08 to change the external static pressure setting using the Ⓒ and Ⓓ buttons Direct the wireless remote controller toward the receiver of the indoor unit and press the Hour button Ⓐ Current setting num...

Page 20: ...d is switched Check operation of the outdoor unit fan Release test run by pressing the ON OFF button Stop Register a telephone number The telephone number of the repair shop sales office etc to contact if an error occurs can be registered in the remote controller The telephone number will be displayed when an error occurs For registration procedures refer to the operation manual for the indoor uni...

Page 21: ...ical manual for the outdoor unit 1 If the beeper does not sound again after the initial two beeps to confirm the self check start signal was received and the OPERATION INDICATOR lamp does not come on there are no error records 2 If the beeper sounds three times continuously beep beep beep 0 4 0 4 0 4 sec after the initial two beeps to confirm the self check start signal was received the specified ...

Page 22: ...on But never use naked fire or steam 9 Test run For description of each LED LED1 2 3 provided on the indoor controller refer to the following table LED 1 power for microcomputer Indicates whether control power is supplied Make sure that this LED is always lit LED 2 power for remote controller Indicates whether power is supplied to the remote controller This LED lights only in the case of the indoo...

Page 23: ......

Page 24: ...Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN KD79M111H02 ...

Reviews: