background image

16

6.  Refrigerant piping work

6.4.  Purging procedures leak test

PURGING PROCEDURES

Connect the refrigerant pipes (both the liquid and gas pipes) between the indoor 

and the outdoor units.

Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe.

(The  stop  valve  will  not  work  in  its  initial  state  fresh  out  of  the  factory  (totally 

closed with cap on).)

Connect the gage manifold valve and the vacuum pump to the service port of the 

stop valve on the gas pipe side of the outdoor unit.

Run the vacuum pump. (Vacuumize for more than 15 minutes.)

Check the vacuum with the gage manifold valve, then close the gage manifold 

valve, and stop the vacuum pump.

Leave it as is for one or two minutes. Make sure the pointer of the gage manifold 

valve remains in the same position. Confirm that the pressure gage show -0.101MPa 

(-760 mmHg).

1. Remove and discard the rubber bung which is inserted in the end of the unit piping.
2. Flare the end of the site refrigerant piping.
3. Pull out the thermal insulation on the site refrigerant piping and replace the 

insulation in its original position.

Cautions On Refrigerant Piping

 

Be sure to use non-oxidative brazing for brazing to ensure that no foreign 

matter or moisture enter into the pipe.

 

Be sure to apply refrigerating machine oil over the flare connection 

seating surface and tighten the connection using a double spanner.

 

Provide a metal brace to support the refrigerant pipe so that no load is 

imparted to the indoor unit end pipe. This metal brace should be provided 

50 cm away from the indoor unit’s flare connection.

Pipe length :

7 m maximum

No gas charge is needed.

Pipe length exceeding 7 m 

Charge the prescribed  

amount of gas.

Remove the gage manifold valve quickly from the service port of the stop valve.

After refrigerant pipes are connected and evacuated, fully open all stop valves on 

gas and liquid pipe sides.

Operating without fully opening lowers the performance and causes trouble.

Hexagonal wrench

*4 to 5 turns

Stop valve

(or the vacuum 

pump with the 

function to 

prevent the back 

flow)

Gauge manifold 

valve (for R410A)

Pressure gauge

    (for R410A)

Compound pressure 

gauge (for R410A)

-0.101MPa  

(-760 mmHg)

Handle 

Low

Handle High

Window

Charge hose 

(for R410A)

Vacuum 

pump

Adapter for 

preventing 

the back flow

Charge hose 

(for R410A)

Service port

Stop 

valve

*Close

*Open

Stop valve

Tighten the cap to the service port to obtain the initial status.

Retighten the cap

Leak test

6.5.  Drain piping work

[Fig. 6-5] (P.4)

 Insulator 

 Drain pipe R1

 Drain pan 

   70 mm

   2 

×

 

   70 mm 

   35 mm

 Downward slope 20 mm/m or more 

 Drain trap

 The drain pipe should extend below this level.

 Open drain

•  In connecting duct, insert canvas duct between unit and duct.

•  Use incombustible material for duct parts.

•  Provide full insulation to inlet duct flange, outlet duct flange and outlet duct to 

prevent condensation.

•  Be sure to apply the air filter near the air inlet grille.

•  Before connecting an inlet duct, install the air filter in the inlet grille.

[Fig. 7-1-1] (P.5)

 Air inlet 

 Air outlet

 Access door 

 Ceiling surface

 Canvas duct 

 Keep duct-work length 850 or more

 Connect common reference potential wire between duct-work to air conditioner

 Caution:

•  Inlet duct of 850 mm or more should be construted.

 

To connect the air conditioner main body and the duct for potential 

equalization. 

•  To reduce the risk of injury from metal sheet edges, wear protective gloves.

•  Install sufficient thermal insulation to prevent condensation forming on 

outlet duct flanges and outlet ducts.

•  To avoid electrical noise interference, do not run transmission lines at 

the bottom of the unit.

•  Return air temperature sensor when an inlet duct is installed.

  A return air temperature sensor is installed on the inlet duct flange.  Before 

connecting an inlet duct, this sensor must be removed and installed in the 

specified position.

7.  Duct work

[Fig. 7-1-2] (P.5)

 Inlet duct flange 

 Return air temperature sensor

 Sensor protection plate 

 Sensor fixture

 Inlet duct

  Pull out the sensor, and remove the sensor fixture and protection plate.  (The 

protection plate must be discarded.)

  Connect the inlet duct.

  Drill a sensor hole (ø12.5 dia.) on the side on the duct.

  Assemble the sensor and fixture.

•  When pulling out the sensor, do not pull it by the lead wire. Doing so may result 

in wire breakage.

•  Before  connecting  the  inlet  duct,  make  sure  that  the  sensor,  its  fixture  and 

protection plate are removed.

•  The  sensor  removed  in  step 

 must be re-installed in the position specified 

in the drawing. Installation of the sensor in an incorrect position may result in 

malfunction.

Mount holes for outlet duct flange and inlet duct.

[Fig. 7-1-3] (P.5)

 Inlet duct flange

 Outlet duct flange

 Top of the unit

Summary of Contents for Mr.Slim PEA-RP100

Page 1: ...NSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit Air Conditioners PEA RP100 125 140GAA ORIGINAL English FOR INSTALLER ...

Page 2: ...t without inlet duct When hanging the indoor unit directly without inlet duct When connecting inlet duct When installing the suspension fixtures prior to installation of the indoor unit without inlet duct When hanging the indoor unit directly without inlet duct Electric box Access door 2 Access door 1 Ceiling Access door 2 Ceiling beam Supply air Intake air Electric box Min 300mm Min 500mm Min 500...

Page 3: ...ter of gravity 5 1 98 680 200 1300 235 Ⓐ Ⓐ Ⓑ 4 1 A 30 B Ⓐ Ⓑ Ⓐ 1 A 30 B 10 Ⓐ Fig 5 1 2 Fig 5 1 3 Ⓐ Nut Ⓑ Washer Ⓐ Be sure to attach a U shaped washer 4 washers in total 6 øB øA ⓐ ⓑ Fig 6 1 ⓐ Indoor unit ⓑ Outdoor unit 6 1 Model A B PEA RP100 125 140 ø15 88 ø9 52 ...

Page 4: ...ping Ⓓ Gas end of refrigerant piping Ⓔ Site refrigerant piping Ⓕ Main body Ⓖ Pipe cover large accessory Ⓗ Thermal insulation field supply Ⓘ Pull Ⓙ Flare nut Ⓚ Return to original position Ⓐ Ⓑ Ⓒ Ⓓ Ⓕ Ⓖ Ⓔ Ⓗ Ⓗ Ⓚ Ⓛ Ⓙ Ⓘ Ⓙ Ⓞ Ⓞ Ⓝ Ⓝ 20 20 20 20 Fig 6 2 1 Fig 6 2 4 Fig 6 2 2 Fig 6 2 3 ⓐ Flare nut ⓑ Copper tube ⓐ Burr ⓑ Copper tube pipe ⓒ Spare reamer ⓓ Pipe cutter Fig 6 2 5 Fig 6 3 1 ⓐ Flaring tool ⓑ Die ⓒ C...

Page 5: ...Air outlet Ⓒ Access door Ⓓ Ceiling surface Ⓔ Canvas duct Ⓕ Keep duct work length 850 or more Ⓖ Connect common reference potential wire between duct work to air conditioner Ⓐ Inlet duct flange Ⓑ Return air temperature sensor Ⓒ Sensor protection plate Ⓓ Sensor fixture Ⓔ Inlet duct Ⓔ S1 S1 S1 S2 S2 S2 S2 S2 S2 S3 S3 1 1 2 2 S3 S1 S2 L TB4 TB TB15 CND CND CN3C CN3C CN22 N S3 Ⓐ Ⓑ Ⓒ Ⓕ Ⓖ Ⓓ Indoor Control...

Page 6: ...2 1 Fig 8 2 2 8 Ⓐ Ⓑ Ⓒ Ⓓ Ⓔ Ⓙ Ⓗ Ⓕ Ⓖ Ⓘ 1 2 M1 M2 S Ⓛ Ⓚ Fig 8 2 5 Ⓐ Indoor terminal block Ⓑ Earth wire green yellow Ⓒ Indoor outdoor unit connecting wire 3 core 1 5 mm2 or more Ⓓ Outdoor terminal block Ⓔ Power supply cord 2 0 mm2 or more Connecting cable Cable 3 core 1 5 mm2 in conformity with Design 245 IEC 57 Indoor terminal block Outdoor terminal block Ⓐ Always install an earth wire 1 core 1 5 mm2 ...

Page 7: ...ller cord through the cut out upper case then seal the cut out notch with putty similarly as above Ⓒ Wall Ⓓ Conduit Ⓔ Lock nut Ⓕ Bushing Ⓖ Switch box Ⓗ Remote controller cord Ⓘ Seal with putty Ⓙ Wood screw Ⓕ Ⓐ Ⓗ Ⓒ Ⓓ Ⓔ Ⓖ Ⓘ Ⓘ Ⓘ Ⓗ Ⓑ Ⓙ Ⓗ B 1 B 2 Fig 8 3 2 8 Ⓐ AB TB6 Ⓑ Ⓐ To the terminal block on the indoor unit Ⓑ TB6 No polarity Fig 8 3 3 30 46 30 30 120 83 5 Ⓐ Ⓑ Ⓒ Ⓐ Remote controller profile Ⓑ Require...

Page 8: ... Ⓒ Ⓐ Fix tightly with tape Ⓑ Remote controller wire Ⓒ Order wire Indoor unit Fig 8 4 2 Fig 8 4 5 Ⓗ Ⓙ Ⓘ When using the switch box When installing directly on the wall Ⓐ 150 mm 5 15 16 inch Ⓑ Remote controller wire Ⓒ Wiring pipe Ⓓ Locknut Ⓗ Seal around here with putty Ⓘ Remote controller wire Ⓙ Seal around here with putty Ⓔ Bushing Ⓕ Switch box Ⓖ Seal around here with putty Ⓒ Ⓓ Ⓑ Ⓕ Ⓔ Ⓖ Ⓐ Wall 8 8 4 ...

Page 9: ...e lower case directly on the wall or the ceiling use wood screws Insert the minus screwdriver toward the arrow pointed and wrench it to remove the cover A flat screwdriver whose width of blade is between 4 and 7mm 5 32 9 32inch must be used Fig 8 4 9 Ⓐ Hang the cover to the upper hooks 2 places Mount the cover to the lower case Ⓐ Cross section of upper hooks ...

Page 10: ...er 0 Pair number 1 Pair number 2 Pair number 3 Pair number 0 Pair number 1 Pair number 2 Pair number 3 Pair number 0 Pair number 0 Pair number 0 Pair number 0 Ⓐ CN2A CN3C SW2 SW1 JP1 JP2 JP3 JP41 JP42 CN22 CN2L CNXA2 CN32 SWE CN20 CN90 CN105 CN41 CN4F CN51 CNXB2 CNXC2 CN44 ON OFF Indoor controller board ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK CHEC...

Page 11: ...ACK DAY MONITOR SET CLOCK ON OFF Ⓐ Ⓑ Ⓓ Ⓒ Ⓖ Ⓔ Ⓕ Ⅰ Ⅱ Ⅲ Ⅳ Ⅰ Ⅰ Ⅳ Ⅱ Ⓐ Filter button Enter button Ⓑ TEST button Ⓒ Set Time button Ⓓ Timer On Off button Set Day button Ⓔ Mode selection button Ⓕ Set temperature button Ⓖ Timer Menu button Monitor Set button Mode number Setting number Refrigerant address Unit number Ⅰ Ⅱ Ⅲ Ⅳ CHECK CHECK CHECK CHECK ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOU...

Page 12: ...pe Ⓓ Gas pipe Ⓔ Stop valve Ⓕ Outdoor unit Ⓖ Refrigerant gas cylinder operating valve Ⓗ Refrigerant gas cylinder for R410A with siphon Ⓘ Refrigerant liquid Ⓙ Electronic scale for refrigerant charging Ⓚ Charge hose for R410A Ⓛ Gauge manifold valve for R410A Ⓜ Service port 10 1 ...

Page 13: ...er to avoid a hazard Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the service panel in the outdoor unit are not attached securely it could result in a fire or an electric shock due to dust water etc Be sure to use the part provided or specified parts for the installation work The use of...

Page 14: ...n a space of less than 500mm is available below the unit between the unit and the ceiling At least 300 mm of space should be left below the unit as shown in Fig 3 2 4 Fig 3 2 5 Create access door 3 below the electric box and the unit as shown in Fig 3 2 6 Fig 3 2 1 P 2 Fig 3 2 2 P 2 Fig 3 2 3 P 2 Fig 3 2 4 P 2 Fig 3 2 5 P 2 Fig 3 2 6 P 2 3 3 Indoor unit accessories The unit is provided with the fo...

Page 15: ...rant piping Ⓕ Main body Ⓖ Pipe cover large accessory Ⓗ Thermal insulation field supply Ⓘ Pull Ⓙ Flare nut Ⓚ Return to original position Ⓛ Ensure that there is no gap here Ⓜ Plate on main body Ⓝ Band accessory Ⓞ Ensure that there is no gap here Place join upwards 0 0 4 6 1 Refrigerant pipe Fig 6 1 P 3 ⓐ Indoor unit ⓑ Outdoor unit Refer to the Instruction Manual that came with the outdoor unit for t...

Page 16: ...nting the back flow Charge hose for R410A Service port Stop valve Close Open Stop valve Tighten the cap to the service port to obtain the initial status Retighten the cap Leak test 6 5 Drain piping work Fig 6 5 P 4 Ⓐ Insulator Ⓑ Drain pipe R1 Ⓒ Drain pan Ⓓ 70 mm Ⓔ 2 Ⓕ 70 mm Ⓕ 35 mm Ⓖ Downward slope 20 mm m or more Ⓗ Drain trap Ⓘ The drain pipe should extend below this level Ⓙ Open drain In connect...

Page 17: ...ly If it is attached incorrectly it could result in a fire electric shock due to dust water etc Use the specified indoor outdoor unit connecting wire to connect the indoor and outdoor units and fix the wire to the terminal block securely so that no stress is applied to the connecting section of the terminal block Incomplete connection or fixing of the wire could result in a fire Do not pinch the c...

Page 18: ...ll portion inside the bottom case oblique section by a knife or a nipper Take out the connected remote controller wire to the terminal block through this space 6 Install the lower case on the switch box or directly on the wall Fig 8 4 8 P 9 Mounting the cover Fig 8 4 9 P 9 Caution Insert the cover securely until the clicking sound is made If not doing so the cover may fall 8 4 Remote controller wi...

Page 19: ...nit number Press the TEMP button Ⓒ and Ⓓ to set the unit number to 07 Direct the wireless remote controller toward the receiver of the indoor unit and press the Minute button Ⓑ Selecting a mode Enter 08 to change the external static pressure setting using the Ⓒ and Ⓓ buttons Direct the wireless remote controller toward the receiver of the indoor unit and press the Hour button Ⓐ Current setting num...

Page 20: ...d is switched Check operation of the outdoor unit fan Release test run by pressing the ON OFF button Stop Register a telephone number The telephone number of the repair shop sales office etc to contact if an error occurs can be registered in the remote controller The telephone number will be displayed when an error occurs For registration procedures refer to the operation manual for the indoor uni...

Page 21: ...ical manual for the outdoor unit 1 If the beeper does not sound again after the initial two beeps to confirm the self check start signal was received and the OPERATION INDICATOR lamp does not come on there are no error records 2 If the beeper sounds three times continuously beep beep beep 0 4 0 4 0 4 sec after the initial two beeps to confirm the self check start signal was received the specified ...

Page 22: ...on But never use naked fire or steam 9 Test run For description of each LED LED1 2 3 provided on the indoor controller refer to the following table LED 1 power for microcomputer Indicates whether control power is supplied Make sure that this LED is always lit LED 2 power for remote controller Indicates whether power is supplied to the remote controller This LED lights only in the case of the indoo...

Page 23: ......

Page 24: ...Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN KD79M111H02 ...

Reviews: