background image

15

6.  Refrigerant piping work

6.2.4.  Flaring work

[Fig. 6-2-4] (P.4)

 Flaring tool

 Die

 Copper tube

 Flare nut

 Yoke

•  Carry out flaring work using flaring tool.

Pipe diameter

(mm)

Dimension

A (mm)

B

       (mm)

When the tool for R410A is used

Clutch type

9.52

0 - 0.5

13.2

15.88

0 - 0.5

19.7

Firmly hold copper tube in a die in the dimension shown in the table at above.

6.2.5.  Check

[Fig. 6-2-5] (P.4)

 Smooth all around 

 Scratch on flared plane

 Inside is shining without any scratches 

 Cracked 

 Even length all around 

 Uneven

 Too much 

 Bad examples

 Tilted

•  Compare the flared work with a figure in right side hand.

•  If flare is noted to be defective, cut off the flared section and do flaring work again.

6.3.  Pipe connection

[Fig. 6-3-1] (P.4)

•  Apply a thin coat of refrigeration oil on the seat surface of pipe.

•  For connection first align the center, then tighten the first 3 to 4 turns of flare nut.

•  Use tightening torque table below as a guideline for indoor unit side union joint 

section, and tighten using two wrenches. Excessive tightening damages the flare 

section.

Copper pipe O.D.

(mm)

Flare nut O.D.

(mm)

Tightening torque

 (N·m)

ø9.52

22

34 - 42

ø15.88

29

68 - 82

 Warning:

Be careful of flying flare nut! (Internally pressurized)

Remove the flare nut as follows:

1.  Loosen the nut until you hear a hissing noise.

2.  Do not remove the nut until the gas has been completely released (i.e., 

hissing noise stops).

3.  Check that the gas has been completely released, and then remove the nut.

Outdoor unit connection

Connect pipes to stop valve pipe joint of the outdoor unit in the same manner 

applied for indoor unit.

•  For  tightening  use  a  torque  wrench  or  spanner,  and  use  the  same  tightening 

torque applied for indoor unit.

Refrigerant pipe insulation

•  After connecting refrigerant piping, insulate the joints (flared joints) with thermal 

insulation tubing.

[Fig. 6-3-2] (P.4)

 Pipe cover (small) (accessory)

 Caution:

  Pull out the thermal insulation on the refrigerant piping at the site, insert the flare nut to 

flare the end, and replace the insulation in its original position.

  Take care to ensure that condensation does not form on exposed copper piping.

 Liquid end of refrigerant piping  

  Gas end of refrigerant piping

 Site refrigerant piping 

  Main body

 Pipe cover (large) (accessory) 

  Thermal insulation (field supply)

 Pull 

  Flare nut

 Return to original position 

  Ensure that there is no gap here

 Plate on main body 

  Band (accessory)

 Ensure that there is no gap here. Place join upwards.

+0

-0.4

6.1.  Refrigerant pipe

[Fig. 6-1] (P.3)

 Indoor unit

 Outdoor unit

 Refer to the Instruction Manual that came with the outdoor unit for the restrictions on

 the height difference between units and for the amount of additional refrigerant 

 charge. 

Avoid the following places for installation where air conditioner trouble is liable to 

occur.

•  Where there is too much oil such as for machine or cooking.

•  Salty environment as seaside areas.

•  Hot-spring areas.

•  Where sulfide gas exists.

•  Other special atmospheric areas.

•  This unit has flared connections on both indoor and outdoor sides. 

[Fig. 6-1]

•  Insulate both refrigerant and drainage piping completely to prevent condensation.

Piping preparation

•  Refrigerant pipes of 3, 5, 7, 10 and 15 m are available as optional items.

(1) Table below shows the specifications of pipes commercially available.

Model

Pipe

Outside diameter

Min wall 

thickness

Insulation 

thickness

Insulation 

material

mm

inch

PEA- 

RP100, 

125, 140

For liquid

9.52

3/8

0.8 mm

8 mm

Heat resisting 

foam plastic 

0.045 specific 

gravity

For gas

15.88

5/8

1.0 mm

8 mm

(2) Ensure that the 2 refrigerant pipes are well insulated to prevent condensation.

(3) Refrigerant pipe bending radius must be 10 cm or more.

 Caution:

Using careful insulation of specified thickness. Excessive thickness prevents 

storage behind the indoor unit and smaller thickness causes dew drippage.

6.2.  Flaring work

•  Main cause of gas leakage is defect in flaring work.

  Carry out correct flaring work in the following procedure.

6.2.1.  Pipe cutting

[Fig. 6-2-1] (P.4)

 Copper tubes

 Good

 No good

 Tilted

 Uneven

 Burred

•  Using a pipe cutter cut the copper tube correctly.

6.2.2.  Burrs removal

[Fig. 6-2-2] (P.4)

 Burr

 Copper tube/pipe

 Spare reamer

 Pipe cutter

•  Completely remove all burrs from the cut cross section of pipe/tube.

•  Put the end of the copper tube/pipe to downward direction as you remove burrs 

in order to avoid burrs drop in the tubing.

6.2.3.  Putting nut on

[Fig. 6-2-3] (P.4)

 Flare nut

 Copper tube

•  Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/

tube having completed burr removal.

  (not possible to put them on after flaring work)

Summary of Contents for Mr.Slim PEA-RP100

Page 1: ...NSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit Air Conditioners PEA RP100 125 140GAA ORIGINAL English FOR INSTALLER ...

Page 2: ...t without inlet duct When hanging the indoor unit directly without inlet duct When connecting inlet duct When installing the suspension fixtures prior to installation of the indoor unit without inlet duct When hanging the indoor unit directly without inlet duct Electric box Access door 2 Access door 1 Ceiling Access door 2 Ceiling beam Supply air Intake air Electric box Min 300mm Min 500mm Min 500...

Page 3: ...ter of gravity 5 1 98 680 200 1300 235 Ⓐ Ⓐ Ⓑ 4 1 A 30 B Ⓐ Ⓑ Ⓐ 1 A 30 B 10 Ⓐ Fig 5 1 2 Fig 5 1 3 Ⓐ Nut Ⓑ Washer Ⓐ Be sure to attach a U shaped washer 4 washers in total 6 øB øA ⓐ ⓑ Fig 6 1 ⓐ Indoor unit ⓑ Outdoor unit 6 1 Model A B PEA RP100 125 140 ø15 88 ø9 52 ...

Page 4: ...ping Ⓓ Gas end of refrigerant piping Ⓔ Site refrigerant piping Ⓕ Main body Ⓖ Pipe cover large accessory Ⓗ Thermal insulation field supply Ⓘ Pull Ⓙ Flare nut Ⓚ Return to original position Ⓐ Ⓑ Ⓒ Ⓓ Ⓕ Ⓖ Ⓔ Ⓗ Ⓗ Ⓚ Ⓛ Ⓙ Ⓘ Ⓙ Ⓞ Ⓞ Ⓝ Ⓝ 20 20 20 20 Fig 6 2 1 Fig 6 2 4 Fig 6 2 2 Fig 6 2 3 ⓐ Flare nut ⓑ Copper tube ⓐ Burr ⓑ Copper tube pipe ⓒ Spare reamer ⓓ Pipe cutter Fig 6 2 5 Fig 6 3 1 ⓐ Flaring tool ⓑ Die ⓒ C...

Page 5: ...Air outlet Ⓒ Access door Ⓓ Ceiling surface Ⓔ Canvas duct Ⓕ Keep duct work length 850 or more Ⓖ Connect common reference potential wire between duct work to air conditioner Ⓐ Inlet duct flange Ⓑ Return air temperature sensor Ⓒ Sensor protection plate Ⓓ Sensor fixture Ⓔ Inlet duct Ⓔ S1 S1 S1 S2 S2 S2 S2 S2 S2 S3 S3 1 1 2 2 S3 S1 S2 L TB4 TB TB15 CND CND CN3C CN3C CN22 N S3 Ⓐ Ⓑ Ⓒ Ⓕ Ⓖ Ⓓ Indoor Control...

Page 6: ...2 1 Fig 8 2 2 8 Ⓐ Ⓑ Ⓒ Ⓓ Ⓔ Ⓙ Ⓗ Ⓕ Ⓖ Ⓘ 1 2 M1 M2 S Ⓛ Ⓚ Fig 8 2 5 Ⓐ Indoor terminal block Ⓑ Earth wire green yellow Ⓒ Indoor outdoor unit connecting wire 3 core 1 5 mm2 or more Ⓓ Outdoor terminal block Ⓔ Power supply cord 2 0 mm2 or more Connecting cable Cable 3 core 1 5 mm2 in conformity with Design 245 IEC 57 Indoor terminal block Outdoor terminal block Ⓐ Always install an earth wire 1 core 1 5 mm2 ...

Page 7: ...ller cord through the cut out upper case then seal the cut out notch with putty similarly as above Ⓒ Wall Ⓓ Conduit Ⓔ Lock nut Ⓕ Bushing Ⓖ Switch box Ⓗ Remote controller cord Ⓘ Seal with putty Ⓙ Wood screw Ⓕ Ⓐ Ⓗ Ⓒ Ⓓ Ⓔ Ⓖ Ⓘ Ⓘ Ⓘ Ⓗ Ⓑ Ⓙ Ⓗ B 1 B 2 Fig 8 3 2 8 Ⓐ AB TB6 Ⓑ Ⓐ To the terminal block on the indoor unit Ⓑ TB6 No polarity Fig 8 3 3 30 46 30 30 120 83 5 Ⓐ Ⓑ Ⓒ Ⓐ Remote controller profile Ⓑ Require...

Page 8: ... Ⓒ Ⓐ Fix tightly with tape Ⓑ Remote controller wire Ⓒ Order wire Indoor unit Fig 8 4 2 Fig 8 4 5 Ⓗ Ⓙ Ⓘ When using the switch box When installing directly on the wall Ⓐ 150 mm 5 15 16 inch Ⓑ Remote controller wire Ⓒ Wiring pipe Ⓓ Locknut Ⓗ Seal around here with putty Ⓘ Remote controller wire Ⓙ Seal around here with putty Ⓔ Bushing Ⓕ Switch box Ⓖ Seal around here with putty Ⓒ Ⓓ Ⓑ Ⓕ Ⓔ Ⓖ Ⓐ Wall 8 8 4 ...

Page 9: ...e lower case directly on the wall or the ceiling use wood screws Insert the minus screwdriver toward the arrow pointed and wrench it to remove the cover A flat screwdriver whose width of blade is between 4 and 7mm 5 32 9 32inch must be used Fig 8 4 9 Ⓐ Hang the cover to the upper hooks 2 places Mount the cover to the lower case Ⓐ Cross section of upper hooks ...

Page 10: ...er 0 Pair number 1 Pair number 2 Pair number 3 Pair number 0 Pair number 1 Pair number 2 Pair number 3 Pair number 0 Pair number 0 Pair number 0 Pair number 0 Ⓐ CN2A CN3C SW2 SW1 JP1 JP2 JP3 JP41 JP42 CN22 CN2L CNXA2 CN32 SWE CN20 CN90 CN105 CN41 CN4F CN51 CNXB2 CNXC2 CN44 ON OFF Indoor controller board ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK CHEC...

Page 11: ...ACK DAY MONITOR SET CLOCK ON OFF Ⓐ Ⓑ Ⓓ Ⓒ Ⓖ Ⓔ Ⓕ Ⅰ Ⅱ Ⅲ Ⅳ Ⅰ Ⅰ Ⅳ Ⅱ Ⓐ Filter button Enter button Ⓑ TEST button Ⓒ Set Time button Ⓓ Timer On Off button Set Day button Ⓔ Mode selection button Ⓕ Set temperature button Ⓖ Timer Menu button Monitor Set button Mode number Setting number Refrigerant address Unit number Ⅰ Ⅱ Ⅲ Ⅳ CHECK CHECK CHECK CHECK ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOU...

Page 12: ...pe Ⓓ Gas pipe Ⓔ Stop valve Ⓕ Outdoor unit Ⓖ Refrigerant gas cylinder operating valve Ⓗ Refrigerant gas cylinder for R410A with siphon Ⓘ Refrigerant liquid Ⓙ Electronic scale for refrigerant charging Ⓚ Charge hose for R410A Ⓛ Gauge manifold valve for R410A Ⓜ Service port 10 1 ...

Page 13: ...er to avoid a hazard Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the service panel in the outdoor unit are not attached securely it could result in a fire or an electric shock due to dust water etc Be sure to use the part provided or specified parts for the installation work The use of...

Page 14: ...n a space of less than 500mm is available below the unit between the unit and the ceiling At least 300 mm of space should be left below the unit as shown in Fig 3 2 4 Fig 3 2 5 Create access door 3 below the electric box and the unit as shown in Fig 3 2 6 Fig 3 2 1 P 2 Fig 3 2 2 P 2 Fig 3 2 3 P 2 Fig 3 2 4 P 2 Fig 3 2 5 P 2 Fig 3 2 6 P 2 3 3 Indoor unit accessories The unit is provided with the fo...

Page 15: ...rant piping Ⓕ Main body Ⓖ Pipe cover large accessory Ⓗ Thermal insulation field supply Ⓘ Pull Ⓙ Flare nut Ⓚ Return to original position Ⓛ Ensure that there is no gap here Ⓜ Plate on main body Ⓝ Band accessory Ⓞ Ensure that there is no gap here Place join upwards 0 0 4 6 1 Refrigerant pipe Fig 6 1 P 3 ⓐ Indoor unit ⓑ Outdoor unit Refer to the Instruction Manual that came with the outdoor unit for t...

Page 16: ...nting the back flow Charge hose for R410A Service port Stop valve Close Open Stop valve Tighten the cap to the service port to obtain the initial status Retighten the cap Leak test 6 5 Drain piping work Fig 6 5 P 4 Ⓐ Insulator Ⓑ Drain pipe R1 Ⓒ Drain pan Ⓓ 70 mm Ⓔ 2 Ⓕ 70 mm Ⓕ 35 mm Ⓖ Downward slope 20 mm m or more Ⓗ Drain trap Ⓘ The drain pipe should extend below this level Ⓙ Open drain In connect...

Page 17: ...ly If it is attached incorrectly it could result in a fire electric shock due to dust water etc Use the specified indoor outdoor unit connecting wire to connect the indoor and outdoor units and fix the wire to the terminal block securely so that no stress is applied to the connecting section of the terminal block Incomplete connection or fixing of the wire could result in a fire Do not pinch the c...

Page 18: ...ll portion inside the bottom case oblique section by a knife or a nipper Take out the connected remote controller wire to the terminal block through this space 6 Install the lower case on the switch box or directly on the wall Fig 8 4 8 P 9 Mounting the cover Fig 8 4 9 P 9 Caution Insert the cover securely until the clicking sound is made If not doing so the cover may fall 8 4 Remote controller wi...

Page 19: ...nit number Press the TEMP button Ⓒ and Ⓓ to set the unit number to 07 Direct the wireless remote controller toward the receiver of the indoor unit and press the Minute button Ⓑ Selecting a mode Enter 08 to change the external static pressure setting using the Ⓒ and Ⓓ buttons Direct the wireless remote controller toward the receiver of the indoor unit and press the Hour button Ⓐ Current setting num...

Page 20: ...d is switched Check operation of the outdoor unit fan Release test run by pressing the ON OFF button Stop Register a telephone number The telephone number of the repair shop sales office etc to contact if an error occurs can be registered in the remote controller The telephone number will be displayed when an error occurs For registration procedures refer to the operation manual for the indoor uni...

Page 21: ...ical manual for the outdoor unit 1 If the beeper does not sound again after the initial two beeps to confirm the self check start signal was received and the OPERATION INDICATOR lamp does not come on there are no error records 2 If the beeper sounds three times continuously beep beep beep 0 4 0 4 0 4 sec after the initial two beeps to confirm the self check start signal was received the specified ...

Page 22: ...on But never use naked fire or steam 9 Test run For description of each LED LED1 2 3 provided on the indoor controller refer to the following table LED 1 power for microcomputer Indicates whether control power is supplied Make sure that this LED is always lit LED 2 power for remote controller Indicates whether power is supplied to the remote controller This LED lights only in the case of the indoo...

Page 23: ......

Page 24: ...Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN KD79M111H02 ...

Reviews: