60
4 BASIC FUNCTIONS
4.10 Output Mode Setting Function from STOP to RUN
4.10
Output Mode Setting Function from STOP to RUN
This function sets the mode of the output (Y) when C Controller module operating status is switched from STOP to RUN.
[CPU Parameter]
[Operation Related Setting]
[Output Mode Setting of STOP to RUN]
Window
Displayed items
Output the Output (Y) Status before STOP
After the output (Y) status before the operating status turns into STOP state is output, the user program is executed.
Clear the Output (Y)
The output (Y) is turned OFF, and the output (Y) status is output after the program operations are executed.
Precautions
The following shows the considerations on outputs when changing the status from STOP to RUN after forcing the output (Y)
ON at STOP status.
■
"Output the Output (Y) Status before STOP" is selected
• When the output (Y) is forced ON when the operating status is STOP, the status before it stopped is output.
• If the output (Y) is OFF before entering the STOP state, the ON state is not retained.
■
"Clear the Output (Y)" is selected
• When the output (Y) is forced ON when the operating status is STOP, the ON state is retained.
Item
Description
Setting range
Default
Output Mode Setting of
STOP to RUN
Set the operation of the output (Y)
when the operating status is switched
from STOP to RUN.
• Output the Output (Y) Status before
STOP
• Clear the Output (Y)
Output the Output (Y) Status before
STOP
Summary of Contents for MELSEC iQ-R C R12CCPU-V
Page 1: ...MELSEC iQ R C Controller Module User s Manual Application R12CCPU V ...
Page 2: ......
Page 23: ...1 EXECUTING PROGRAMS 1 3 I O Access Timing 21 1 MEMO ...
Page 32: ...30 3 MEMORY CONFIGURATION OF C Controller Module 3 4 Files MEMO ...
Page 257: ...I 255 MEMO ...
Page 261: ......