![Mitsubishi Electric MELSEC iQ-R C R12CCPU-V User Manual Download Page 199](http://html.mh-extra.com/html/mitsubishi-electric/melsec-iq-r-c-r12ccpu-v/melsec-iq-r-c-r12ccpu-v_user-manual_239137199.webp)
APPX
Appendix 1 Error Code List
197
A
4032H
Device
specification
error
The specified device modification is incorrect. Or, the device
names (TS, TC, SS, SC, CS, or CC) which cannot be used for
random read/random write (in word units)/monitor registration/
monitor command of SLMP/MC protocol have been specified.
• Check the specified device modification method.
• Check the specified device name.
4033H
Device
specification
error
Data cannot be written to the specified device since it is for
system use.
Do not write data to the specified device. Or, do not turn it ON/
OFF.
4040H
Intelligent
function
module
specification
error
The request cannot be executed to the specified intelligent
function module.
Check whether the specified module is an intelligent function
module which has the buffer memory.
4041H
Intelligent
function
module
specification
error
The access range exceeded the buffer memory range of the
specified intelligent function module.
Check the start address and number of access points, and
access within the range that exists in the intelligent function
module.
4042H
Intelligent
function
module
specification
error
The specified intelligent function module cannot be accessed.
• Check whether the specified intelligent function module
operates normally.
• Check whether the specified module has hardware failure.
4043H
Intelligent
function
module
specification
error
The specified intelligent function module does not exist.
Check the I/O number of the specified intelligent function
module.
4044H
Intelligent
function
module
specification
error
A bus error occurred during the access to an intelligent function
module.
Check whether the specified intelligent function module, other
modules, or base unit have hardware failure.
4050H
Protect error
The request cannot be executed because the write protect
switch of the SD memory card is ON.
Turn OFF the write protect switch of the SD memory card.
4052H
Protect error
Data cannot be written since the specified file attribute is the
read-only.
Do not write data to the specified file. Or, change the file
attribute.
4053H
Protect error
An error occurred when writing data to the specified drive
(memory).
Check the specified drive (memory). Or, write data again after
changing the target drive (memory).
4054H
Protect error
An error occurred when deleting data from the specified drive
(memory).
Check the specified drive (memory). Or, delete data again after
changing the target drive (memory).
4080H
Other error
Request data error
Check the specified request data.
4082H
Other error
The specified command cannot be executed since it is being
executed.
Execute the command again once the request from another
engineering tool has been completed.
408BH
Other error
A remote request cannot be executed.
• Execute the request again after placing the CPU module in
the state where a remote request can be executed.
• For the remote reset operation, set "Remote Reset" to
"Enable" with the parameter.
4121H
File related
error
The specified drive (memory) or file does not exist.
Check the specified drive (memory) or file, and execute the
request again.
4122H
File related
error
The specified drive (memory) or file does not exist.
Check the specified drive (memory) or file, and execute the
request again.
4123H
File related
error
The specified drive (memory) has an error.
Initialize the memory, and restore the drive (memory) to its
normal state.
4124H
File related
error
The specified drive (memory) has an error.
Initialize the memory, and restore the drive (memory) to its
normal state.
4125H
File related
error
The specified drive (memory) or file is currently being
processed.
Execute it again after a while.
4129H
File related
error
The request cannot be executed since the specified drive
(memory) is ROM.
Change the target drive (memory), and execute the request
again.
412AH
File related
error
The request cannot be executed since the specified drive
(memory) is ROM.
Change the target drive (memory), and execute the request
again.
412BH
File related
error
The specified drive (memory) is write-prohibited.
Change the write-protect conditions or drive (memory), and
execute the request again.
Error
code
Error name
Error details and cause
Corrective action
Summary of Contents for MELSEC iQ-R C R12CCPU-V
Page 1: ...MELSEC iQ R C Controller Module User s Manual Application R12CCPU V ...
Page 2: ......
Page 23: ...1 EXECUTING PROGRAMS 1 3 I O Access Timing 21 1 MEMO ...
Page 32: ...30 3 MEMORY CONFIGURATION OF C Controller Module 3 4 Files MEMO ...
Page 257: ...I 255 MEMO ...
Page 261: ......