196
APPX
Appendix 1 Error Code List
Error code related to data communication (4000H to 4FFFH)
The table below lists the error codes detected by other than the self-diagnostic function of CPU module.
The error codes are not stored in SD0 since these error are not detected by the self-diagnostic function.
Error
code
Error name
Error details and cause
Corrective action
4001H
Common error
An unsupported request was executed.
(The request was issued to CPU module which does not
support the request.)
• Check the command data of SLMP/MC protocol.
• Check the CPU module name selected with an engineering
tool.
• Check the target CPU module name.
4002H
Common error
An unsupported request was executed.
• Check the command data of SLMP/MC protocol.
• Check the CPU module name selected with an engineering
tool.
• Execute the request again.
If the same error code is displayed again, the possible cause is
a hardware failure of the CPU module. Please consult your
local Mitsubishi representative.
4003H
Common error
Command for which a global request cannot be performed was
executed.
Check the command data of SLMP/MC protocol.
4004H
Common error
A request was issued to the system file.
Check the command data of SLMP/MC protocol.
4005H
Common error
The volume of data to be handled by the specified request is
too large.
Check the command data of SLMP/MC protocol.
4008H
Common error
The CPU module is BUSY.
(The buffer is not empty.)
Execute the request again after arbitrary period of time has
elapsed.
4010H
CPU module
operation
related error
Because the CPU module is in the RUN state, the request
cannot be executed.
Execute the request after placing the CPU module into the
STOP state.
4013H
CPU module
operation
related error
Because the CPU module is not in the STOP state, the request
cannot be executed.
Execute the request after placing the CPU module into the
STOP state.
4021H
File related
error
The specified drive (memory) does not exist, or has an error.
• Check the status of the specified drive (memory).
• Back up the data in the CPU module, and then initialize the
memory.
4022H
File related
error
The file with the specified file name or file number does not
exist.
Check the specified file name and file number.
4023H
File related
error
The file name and file number of the specified file do not match.
Delete the file, and then create a file again.
4024H
File related
error
The specified file cannot be handled.
Do not access the specified file.
4025H
File related
error
The specified file is currently processing a request from
another engineering tool.
Forcibly execute the request. Or, execute it again once the
processing from another engineering tool has been completed.
4026H
File related
error
Specifying the file password set to the target drive (memory) is
required.
Specify the file password set to the target drive (memory), and
access it.
4027H
File related
error
The specified range exceeded the file size.
Check the specified range, and access within the range.
4028H
File related
error
The same file already exists.
Forcibly execute the request. Or, change the file name and
execute the request again.
4029H
File related
error
The specified file capacity cannot be reserved.
Review the specified file capacity, and execute the request
again.
402AH
File related
error
The specified file has an error.
Back up the data in the CPU module, and then initialize the
memory.
402BH
File related
error
The request cannot be executed in the specified drive
(memory).
Execute the request again after placing the CPU module into
the STOP state.
402CH
File related
error
The request cannot be executed currently.
Execute it again after a while.
4030H
Device
specification
error
The specified device name cannot be handled.
Check the specified device name.
4031H
Device
specification
error
• The specified device number is out of range.
• The CPU module does not support the specified device
name.
• Check the specified device number.
• Check the device assignment of the CPU module.
• Check the specified device name.
Summary of Contents for MELSEC iQ-R C R12CCPU-V
Page 1: ...MELSEC iQ R C Controller Module User s Manual Application R12CCPU V ...
Page 2: ......
Page 23: ...1 EXECUTING PROGRAMS 1 3 I O Access Timing 21 1 MEMO ...
Page 32: ...30 3 MEMORY CONFIGURATION OF C Controller Module 3 4 Files MEMO ...
Page 257: ...I 255 MEMO ...
Page 261: ......