4 BASIC FUNCTIONS
4.7 Inter-module Synchronization Function
55
4
Parameter setting
Set a module configuration diagram with CW Configurator to configure the inter-module synchronization setting.
[System Parameter]
[Synchronization Setting within the Modules]
[Synchronization Setting within the Modules]
Operating procedure
Displayed items
*1 The setting range for the inter-module synchronization cycle differs depending on modules. (
Manual for respective modules)
1.
Select "Use" for "Use Inter-module
Synchronization Function in System".
2.
Click the "Detailed Setting" for "Select
Synchronous Target Unit between Unit".
3.
Select "Synchronize" for the module to be
synchronized.
4.
Set the inter-module synchronization cycle in
"Synchronous Fixed Scan Interval Setting
within the Modules".
5.
When writing parameters, write both of the
system parameter and module parameter.
6.
Configure the setting for the synchronous
master when a local station of CC-Link IE Field
Network module is to be synchronized. (The
setting is not required for a master station.)
Item
Description
Setting range
Default
Use Inter-module Synchronization Function in System
Set whether or not to use the inter-module
synchronization function.
• Not Use
• Use
Not Use
Select Synchronous
Target Unit between Unit
Detailed Setting
Set the module to be synchronized.
• Do not Synchronize
• Synchronize
Do not
Synchronize
Synchronous Fixed
Scan Interval Setting
within the Modules
0.05 ms Unit Setting
Set whether or not to set the inter-module
synchronization cycle in 0.05 ms units.
• Not Set
• Set
Not Set
Fixed Scan Interval Setting
(Not Set by 0.05ms)
Select the inter-module synchronization cycle from
the list when it is not set in 0.05 ms units.
• 0.222 ms
• 0.444 ms
• 0.888 ms
• 1.777 ms
• 3.555 ms
• 7.111 ms
0.888 ms
Fixed Scan Interval Setting
(Set by 0.05 ms)
Set the inter-module synchronization cycle when it is
set in 0.05 ms units.
0.10 to 10.00 ms (in 0.05
ms units)
0.50 ms
Synchronous Master
Setting within the
Modules
Synchronous Master Setting
of CC IE Field
When "Set" is selected, a master station of CC-Link
IE Field Network module is the synchronous master.
When "Not Set" is selected, the CPU module (the
leftmost CPU module for multiple CPU configuration)
is the synchronous master.
• Not Set
• Set
Not Set
Mounted Slot No.
Set the mounting slot number for the master station
of CC-Link IE Field Network module to be set as the
synchronous master.
0 to 11
0
Summary of Contents for MELSEC iQ-R C R12CCPU-V
Page 1: ...MELSEC iQ R C Controller Module User s Manual Application R12CCPU V ...
Page 2: ......
Page 23: ...1 EXECUTING PROGRAMS 1 3 I O Access Timing 21 1 MEMO ...
Page 32: ...30 3 MEMORY CONFIGURATION OF C Controller Module 3 4 Files MEMO ...
Page 257: ...I 255 MEMO ...
Page 261: ......