4 BASIC FUNCTIONS
4.3 Remote Operation Function
Remote PAUSE
Change the C Controller module status to PAUSE externally while the RESET/STOP/RUN switch is on the RUN position. Use
this function to retain the output (Y) of the C Controller module in the RUN state in such system as process control.
Executing remote operations
The following methods are available to execute remote PAUSE:
■
Using CW Configurator
Refer to the following manual.
CW Configurator Operating Manual
■
Using a user program
Execute the C Controller module dedicated function (CCPU_Control) to perform remote PAUSE.
MELSEC iQ-R C Controller Module Programming Manual
■
Using SLMP
Refer to the following manual.
SLMP Reference Manual
Precautions
The user program does not stop executing even if the C Controller module is in the remote PAUSE state. To change the
processing according to the operating status of the C Controller module, use the C Controller module dedicated function
(CCPU_GetCpuStatus) in the program.
Remote RESET
Reset the C Controller module externally while the module is in the STOP state (including the case in which the module is
stopped due to an error). Even when the RESET/STOP/RUN switch is on the RUN position, the C Controller module can be
reset while the module is in STOP state.
Enabling remote RESET
Before performing remote RESET, enable the remote RESET.
[CPU Parameter]
[Operation Related Setting]
[Remote Reset Setting]
Window
Displayed items
Item
Description
Setting range
Default
Remote Reset
Set whether to enable remote RESET.
• Disable
• Enable
Disable
Summary of Contents for MELSEC iQ-R C R12CCPU-V
Page 1: ...MELSEC iQ R C Controller Module User s Manual Application R12CCPU V ...
Page 2: ......
Page 23: ...1 EXECUTING PROGRAMS 1 3 I O Access Timing 21 1 MEMO ...
Page 32: ...30 3 MEMORY CONFIGURATION OF C Controller Module 3 4 Files MEMO ...
Page 257: ...I 255 MEMO ...
Page 261: ......