Table 6.3 Error Code List for AnUCPU (Continue)
Error
Massage
Error
Code
(D9008)
Detailed
Error
Code
(D9091)
CPU
States
Error and Cause
Corrective Action
445
There are 2 or more
interrupt modules
loaded.
Reduce the interrupt
modules to 1 or less.
446
Modules assigned by
parameters for
MNT/MINI automatic
refresh from the
peripheral device do
not conform with the
types of station
modules actually
linked.
Perform again module
assignment for
MNT/MINI automatic
refresh with parameters
according to actually
linked station modules.
The number of modules
of I/O assignment
registration (number of
loaded modules) per
one CPU module for the
special function
modules which can use
dedicated instructions is
larger than the specified
limit. (Total of the
number of computers
shown below is larger
than 1344.)
Reduce the number of
loaded special function
modules.
(AD59
×
5)
(AD57(S1)/AD58
×
8)
(AJ71C24(S3/S6/S8)
×
10)
(AJ71UC24
×
10)
(AJ71C21(S1) (S2)
×
29)
+
((AJ71PT32(S3) in
extension mode x 125)
447
Total >
1344
"SP.UNIT
LAY.ERR."
44
448*
STOP
(1) Five or more
network modules
have been installed.
(2) A total of five or
more of network
modules and data
link modules have
been installed.
Make the total of the
installed network
modules and data link
modules four or less.