98
Table 6.2 Error Code List for AnACPU (Continue)
Error
Massage
Error
Code
(D9008)
Detailed
Error
Code
(D9091)
CPU
States
Error and Cause
Corrective Action
134
The
CHG
instruction was
included in the program
and executed though
no sub program was
provided.
Read the error step
using a peripheral
device and delete the
CHG instruction
circuit block.
"CAN'T
EXECUTE
(P)"
(Checked
at
execution
of
instruction.)
13
135
STOP
(1)
LEDA/B IX
and
LEDA/B IXEND
instructions are not
paired.
(2) There are 33 or
more sets of
LEDA/B IX
and
LEDA/B IXEND
instructions.
(1) Read the error step
using a peripheral
device, check
contents and correct
program of the step.
(2) Reduce the number
of sets of
LEDA/B IX
and
LEDA/B IXEND
instructions to 32 or
less.
141 Instructions
(including
NOP ) other than
LDX ,
LDIX ,
ANDX and
ANIX are included
in the
CHK instruction
circuit block.
142
Multiple
CHK
instructions are given.
143
The number of contact
points in the
CHK instruction
circuit block exceeds
150.
"CHK
FORMAT
ERR"
(Checked
at
STOP/PAU
SE
→
RUN.)
14
144
STOP
The
LEDA CHK
instructions are not
paired with the
LEDA CHKEND
instructions, or 2 or
more pairs of them are
given.
Check the program of
the
CHK instruction and
correct it referring to
contents of detailed
error codes.