95
Table 6.2 Error Code List for AnACPU (Continue)
Error
Massage
Error
Code
(D9008)
Detailed
Error
Code
(D9091)
CPU
States
Error and Cause
Corrective Action
111
Capacity settings of the
main and sub
programs,
microcomputer
program, file register
comments, status
latch, sampling trace
and extension file
registers are not within
the usable range of the
CPU.
112
Total of the set capacity
of the main and sub
programs, file register
comments, status
latch, sampling trace
and extension file
registers exceeds
capacity of the memory
cassette.
Read parameters in the
CPU memory, check the
contents, make
necessary corrections
and write them again to
the memory.
113
Latch range set by
parameters or setting
of M, L or S is
incorrect.
114
Sum check error
115
Either of settings of the
remote RUN/
PAUSE contact point
by parameters,
operation mode at
occurrence of error,
annunciator indication
mode, or STOP
→
RUN indication mode is
incorrect.
116 The
MNET-MINI
automatic refresh
setting by parameters
is incorrect.
117
Timer setting by
parameters is incorrect.
"PARAMET
ER
ERROR"
(Checked
at power on
and at
STOP/PAU
SE
→
RUN.)
11
118
STOP
Counter setting by
parameters is incorrect.
Read parameters in the
CPU memory, check the
contents, make
necessary corrections
and write them again to
the memory
Summary of Contents for Melsec A Series
Page 90: ...77 MEMO ...
Page 149: ......