Table 6.2 Error Code List for AnACPU (Continue)
Error
Massage
Error
Code
(D9008)
Detailed
Error
Code
(D9091)
CPU
States
Error and Cause
Corrective Action
505 (1)
Station
number
specified by the
LEDA/B LRDP
LEDA/B LWTP
,
LRDP ,
LWTP
instructions is not a
local station.
(2) Head I/O number
specified by the
LEDA/B RFRP
LEDA/B RTOP
,
RFRP ,
RTOP
instructions is not of
a remote station.
506
Head I/O number
specified by the
LEDA/B RFRP
LEDA/B RTOP
,
RFRP ,
RTOP
instructions is not of a
special function
module.
Read the error step
using a peripheral
device and check and
correct program of the
step.
"OPERATI
ON
ERROR"
(Checked
at
execution
of
instruction.)
50
507
Stop or
Continu
e (set
by
parame
ter)
(1) When the AD57(S1)
or AD58 was
executing
instructions in
divided processing
mode, other
instructions were
executed to either of
them.
(2) When an AD57(S1)
or AD58 was
executing
instructions in
divided processing
mode, other
instructions were
executed in divided
mode to another
AD57(S1) or AD58.
Read the error step
using a peripheral
device and provide
interlock with special
relay M9066 or modify
program structure so
that, when the AD57(S1)
or AD58 is executing
instructions in divided
processing mode, other
instructions may not be
executed to either of
them or to another
AD57(S1) or AD58 in
divided mode.