English

Standard installation examples

Installing the Lossnay unit

1. Preparing the anchor bolts

Mount the washers (outer diameter of >21 mm for M10, >24 mm for
M12) and nuts onto the pre-recessed anchor bolts (M10 or M12), as
shown in the figure below.

2. Attaching the duct connecting flanges

Use the supplied screws to secure the duct connecting flanges to
the Lossnay unit.

Model

Distance

LGH-15 to 65 RX

5

1 m or more

LGH-80 and 100 RX

5

2.5 m or more

LGH- 150 and 200 RX

5

3 m or more

The parts can also be installed upside down.
Remove the maintenance cover, rotate the parts
by 180°, and re-install.

Duct length

Installation method

Anchor bolt (M10 or M12)

Nut

Washer

Nut

EA
(exhaust air outlet)

Inspection opening
(450x450 or 600x600 mm)

SA

(supply air)

Supply air grille
(not included)

Deep hood
(to prevent rain water
from seeping in)

Downward gradient of duct:
1/30 or more (toward wall side)
and provision of distance in table
below (to prevent rain water from
seeping in)

Duct

Anchor bolt (to be provided by user)

RA

(return air)

Return air grille
(not included)

OA
(outside air intake)

Lossnay unit

Anchor bolt

Ceiling suspension fixture

Duct connecting flange
 (Accessory parts)

Mounting screw
(Accessory parts)

Mounting
screw

Duct connecting flange
 (Accessory parts)

Models LGH-15 to 100 RX

5

Models LGH-150 and 200 RX

5

Lossnay unit

Return air grille

(not Included)

Maintenance space

Inspection opening

EA (exhaust air outlet)

OA (outside air intake)

Supply air grille
(not included)

  * Except the 150 and 200 RX

5

.

Remote controller
(optional parts)

EA
(exhaust
air outlet)

OA
(outside
air intake)

* It can be installed by inverting the top and the bottom.

After installing the duct
connecting flange, remove
the maintenance cover.
Turn the cover by 180˚,
and then reinstall it.

Maintenance
space

Lossnay

unit

Inspection
opening

EA
(exhaust
air outlet)

OA
(outside
air intake)

EA
(exhaust
air outlet)

OA
(outside
air intake)

Lossnay unit

Electrically operated damper
(Protection against the intrusion of cold air while Lossnay is stopped in winter)
(To be provided by the customer)

In a region where there is risk of freezing in winter, it is recommended
to install an Electrically operated damper, or the like, in order to
prevent the intrusion of (cold) outdoor air while Lossnay is stopped.

Washer

Nut

Models LGH-15 to 100 RX

5

Models LGH-150 and 200 RX

5

Ceiling suspension fixture

Anchor bolt
(M10 or M12)

Washer

Washer

Nut

CAUTION

Before attaching the duct connecting flanges, check that no
foreign matter (scraps of paper, vinyl, etc.) has found its way
inside to Lossnay unit.

Attach the duct connecting flanges with the packing at the SA
and RA sides.

3. Mounting Lossnay unit

(1) Hang the ceiling suspension fixtures on the anchor bolts and

adjust in such a way that Lossnay unit is level.

(2) Tighten up securely using double nuts.

CAUTION

  • When suspending Lossnay unit from the ceiling, do not handle

it in such a way that force will be applied to the control box.

  • Install the anchor bolts to ensure the product's weight or

earthquake load. (Correctly rated wire / chain may also be used)

Summary of Contents for Lossnay LGH-150RX5-E

Page 1: ...s a result of incomplete combustion Do not use at a place where it is exposed to high temperatures 40 C or higher naked flames or in environment with combustible fumes It could cause fire Do not use in an environment such as a chemical factory where hazardous gases such as acidic gases alkaline gases organic solvent fumes paint fumes or gases containing corrosive components are generated It could ...

Page 2: ...200 RX5 Model A B C D Weight kg LGH 150 RX5 1004 690 690 1045 105 LGH 200 RX5 1231 917 917 1272 118 Unit mm Accessory parts Duct connecting flanges x4 Mounting screws x16 Slim Lossnay connection cable gray two wires x1 Ceiling suspension fixture 4 15 x 30 oval SA supply air RA return air EA exhaust air outlet OA outside air intake Core air filter High Efficiency filter fan maintenance space Lossna...

Page 3: ...de air intake Supply air grille not included Except the 150 and 200 RX5 Remote controller optional parts EA exhaust air outlet OA outside air intake It can be installed by inverting the top and the bottom After installing the duct connecting flange remove the maintenance cover Turn the cover by 180 and then reinstall it Maintenance space Lossnay unit Inspection opening EA exhaust air outlet OA out...

Page 4: ...is recommended that the indoor ductwork be covered with insulation material Do not carry out the following types of duct construction Doing so could cause a drop in the air volume and generate abnormal noises 5 When changing the direction of the out door side duct EA OA Except for LGH 150 and 200 RX5 1 Removal of flange cover Unscrewing the flange cover mounting screws 4 pcs remove the flange cove...

Page 5: ...is product the wiring installation method will vary according to the design of the system Perform electrical installation to meet local electrical regulations Always use double insulated PVC cable for the transmission cables Wiring work must be performed by qualified professionals All supply circuits must be disconnected before obtaining access to the terminal devices M1 Motor for exhaust fan M2 M...

Page 6: ...onnector of control board 2 1 TM4 S B A TB5 M NET When the optional Remote Controller PZ 60DR E is used as the M NET System connect it to 1 2 of TM4 terminal block and connect M NET transmission wire to A B on TB5 terminal block 2nd remote controller Max 2 remote controllers installable 2 PZ 41SLB E and PZ 52SF E cannot be used when using PZ 60DR E M NET Transmission cable Shielded wire 2nd or lat...

Page 7: ...nnected to single input terminal is up to 4 wires for ø0 65 PVC wire or 0 3 mm2 stranded wire It is up to 2 wires for any other wires PZ 41SLB E cannot be used when MELANS centralized control of the Lossnay is used PZ 60DR E and PZ 41SLB E cannot be installed simultaneously 1 Connect the output signal cable from the external device to the input terminal block TM2 of the external controller CAUTION...

Page 8: ...3 3 and the negative side to 1 1 1 1 1 2 Confirm that the pulse input switch SW2 2 is set to OFF Set to OFF at time of shipment When the external device has a charged operating signal of 12 VDC or 24 VDC Connect the operating signal wire from the external device via the remote output to 1 and 2 on the external control input terminal block TM2 No polarity 1 Move the pulse input switch SW2 2 to the ...

Page 9: ...y Contactor rating DC 1 mA When connecting to the City Multi Lossnay remote controller PZ 52SF E or Mitsubishi Electric Air Conditioner Network System MELANS 10 Remote ON OFF adaptor Optional PAC SA88HA E When SW1 is ON fan speed of the Lossnay will be set to Low regardless of the remote control setting Use this in such a way that it ventilates at High fan speed normally and when the external sens...

Page 10: ...roller When interlocking with Mitsubishi Free Plan air conditioner Incase of PZ 60DR E Limit the total length of transmission wires no longer than 500 m Limit the wiring length between Lossnay and the power supply unit Optional or the outdoor unit no longer than 200 m M NET transmission cable Lossnay M NET transmission cable Power supply unit Lossnay MELANS M NET transmission cable Air conditioner...

Page 11: ...door OA air temperatures and automatically select the Lossnay ventilation or Bypass ventilation With this mode however priority is given to the Bypass ventilation This setting reflects to the night purge operation condition Bypass automatic ventilation priority setting 5 OFF ON 7 7 SW2 Operation When outdoor temperature OA is 28 C or higher within 24 hours then Bypass ventilation starts by the com...

Page 12: ...pply fan is stopped during defrosting of the air conditioner when Mr Slim or City Multi indoor unit is connected to a duct When the outdoor air is lower than 15 C stop the operation of exhaust fan OA stop operation at cold region Operation Exhaust fan operation factory setting Exhaust fan stop exhaust fan operation at Low speed at outdoor air lower than 15 C OFF ON 3 3 SW5 Settings for automatic r...

Page 13: ...the external device has come off of the external control input terminal Check in the case of multiple units whether the Main Sub selection switch on the Lossnay unit which is connected to the external control input terminal is set on the Master setting and check whether the Main Sub selection switch on other Lossnay units are set to Sub Check that the trial operation switch SW2 1 is set to off Cha...

Reviews: