When using Mitsubishi Mr. Slim air conditioner with MA
Remote controller
Connect the interlocking cable connector side to CN2L on the circuit
board for the indoor Mr. Slim unit, then connect the lead wire side to
the
1
and
2
of the input terminal block (TM2) for the Lossnay exter-
nal controller input. (No polarity)
•
Always separate the power supply cable and the Slim-Lossnay
connection cable by 5 cm or more to prevent the unit from
malfunctioning.
•
The Slim-Lossnay connection cable is 0.25 m long. When wiring,
extend it as far as necessary.
Note
•
The Lossnay remote controller (PZ-60DR-E, PZ-41SLB-E)
cannot be used with this system.
•
Use MA remote controller of Mr. Slim for switching Lossnay
ON/OFF or the fan speed.
•
The ventilation mode is “automatic ventilation”.
•
The Slim-Lossnay connection cable may be extended to a
maximum length of 500m. (Extension cable specifications
are as detailed below)
Ensure that all connections are secure and that the appro-
priate insulation is provided.
Use extension cable sheathed PVC cable or cable 0.5 mm
2
to 1.0 mm
2
.
12 3
123
1 2 3
Installation method (continued)
Lossnay External control input (TM2)
0.5 mm
2
to 1 mm
2
sheathed PVC cable
External device
12 or 24 VDC
Overall connection extension length
(Follow the operation manual for the external equipment.)
Lossnay External controller input (TM2)
0.5 mm
2
to 1 mm
2
sheathed PVC cable
External device
Uncharge a-contact
Lossnay
External controller input (TM2)
Slim-Lossnay connection cable
(Enclosed accessory)
Red
Printed circuit board
Within 500 m
CN2L
Mr. Slim (Indoor unit)
White
When interlocking with a pulse output device
3
When operating multiple Lossnay units
4
Operating switch for
external device
Power supply
External
device
Lossnay
Power supply
Within 500 m
When the external device has an uncharged a-contact signal
•
Connect the operating signal (wire) from the external device via
the remote output to
1
and
3
on the external control input
terminal block (TM2).
CAUTION
•
If an optocoupler or any other type of polar coupler is used at
the uncharged a-contact, connect the positive side to
3
3
3
3
3
and
the negative side to
1
1
1
1
1
.
(2) Confirm that the pulse input switch (SW2-2) is set to “OFF”.
(Set to “OFF” at time of shipment.)
When the external device has a charged operating signal of
12 VDC or 24 VDC
•
Connect the operating signal (wire) from the external device via
the remote output to
1
and
2
on the external control input
terminal block (TM2). (No polarity)
(1) Move the pulse input switch [SW2-2] to the ON position.
(Refer to function settings
1
“Settings for pulse input”.)
(2) Connect the pulse output device (i.e., building management sys-
tem) to the external control input terminal block [TM2].
•
A pulse width of at least 200 msec will be needed.
•
When using PZ-60DR-E, it can be set also from the remote controller.
Connecting methods vary depending on the types of pulse signal
Refer to Section
2
“When the external device has a charged
operation signal of 12 VDC or 24 VDC” or “When the external
device has an uncharged a-contact signal”.
(1) Connect from Lossnay Unit 1 to Lossnay Unit 2, and from Unit 2 to
Unit 3 and so on up to a maximum of 15 units using a transmission
cable (PVC insulated PVC jacketed and either between
φ
0.65
and
φ
1.2, or between 0.3 mm
2
and 1.25 mm
2
in cross section).
(2) Change the setting on the main/sub switch (SW1) on the second
and subsequent Lossnay units to “Sub”.
CAUTION
Don’t tighten screws of terminal block with a torque larger than
0.5 Nm. It could damage the PCB.
Note
•
Up to four 0.3 mm
2
stranded wires or
φ
0.65 PVC wires can
be connected to one input terminal.
•
For other types of wire, up to two can be connected.
•
The operation signal and pulse signal can be connected to
the external device of the main Lossnay only.
•
Connect the power to each respective Lossnay unit.
•
When the LGH-150RX
5
and LGH-200RX
5
types are connected, they
operate at low fan speed even if extra low fan speed is selected.
Remote controller
(PZ-60DR-E or
PZ-41SLB-E)
Lossnay
(Main)
Remote controller
(PZ-60DR-E or PZ-41SLB-E)
Power
supply
External
device
Operating switch
for external device
Lossnay (Sub)
MAX 15 units
Power
supply
Lossnay (Sub)
Power
supply
Power
supply
Connect to
remote
controller
(PZ-60DR-E)
Connect
to third
Lossnay
Main/Sub selection
switch
(SW1)
Main
Sub
2
1
2
1
Transmission cable
First Lossnay
Second
Lossnay
TM4
(Factory setting: main)
TM4
1
2
SW2
3
4
5
6
7
8
9 10
ON
ON
OFF