8

When using Mitsubishi Mr. Slim air conditioner with MA
Remote controller

Connect the interlocking cable connector side to CN2L on the circuit
board for the indoor Mr. Slim unit, then connect the lead wire side to
the 

1

 and 

2

 of the input terminal block (TM2) for the Lossnay exter-

nal controller input. (No polarity)

Always separate the power supply cable and the Slim-Lossnay
connection cable by 5 cm or more to prevent the unit from
malfunctioning.

The Slim-Lossnay connection cable is 0.25 m long. When wiring,
extend it as far as necessary.

Note

The Lossnay remote controller (PZ-60DR-E, PZ-41SLB-E)
cannot be used with this system.

Use MA remote controller of Mr. Slim for switching Lossnay
ON/OFF or the fan speed.

The ventilation mode is “automatic ventilation”.

The Slim-Lossnay connection cable may be extended to a
maximum length of 500m. (Extension cable specifications
are as detailed below)
Ensure that all connections are secure and that the appro-
priate insulation is provided.
Use extension cable sheathed PVC cable or cable 0.5 mm

2

to 1.0 mm

2

.

12 3

123

1 2 3

Installation method (continued)

Lossnay External control input (TM2)

0.5 mm

2

 to 1 mm

2

 sheathed PVC cable

External device

12 or 24 VDC

Overall connection extension length

(Follow the operation manual for the external equipment.)

Lossnay External controller input (TM2)

0.5 mm

2

 to 1 mm

2

 sheathed PVC cable

External device

Uncharge a-contact

Lossnay
External controller input (TM2)

Slim-Lossnay connection cable
(Enclosed accessory)

Red

Printed circuit board

Within 500 m

CN2L

Mr. Slim (Indoor unit)

White

When interlocking with a pulse output device

3

When operating multiple Lossnay units

4

Operating switch for
external device

Power supply

External

device

Lossnay

Power supply

Within 500 m

When the external device has an uncharged a-contact signal

Connect the operating signal (wire) from the external device via
the remote output to 

1

 and 

3

 on the external control input

terminal block (TM2).

CAUTION

If an optocoupler or any other type of polar coupler is used at
the uncharged a-contact, connect the positive side to 

3

3

3

3

3

 and

the negative side to 

1

1

1

1

1

.

(2) Confirm that the pulse input switch (SW2-2) is set to “OFF”.

(Set to “OFF” at time of shipment.)

When the external device has a charged operating signal of
12 VDC or 24 VDC

Connect the operating signal (wire) from the external device via
the remote output to 

1

 

and

 

2

 

on the external control input

terminal block (TM2).  (No polarity)

(1) Move the pulse input switch [SW2-2] to the ON position.

(Refer to function settings 

1

 “Settings for pulse input”.)

(2) Connect the pulse output device (i.e., building management sys-

tem) to the external control input terminal block [TM2].

A pulse width of at least 200 msec will be needed.

When using PZ-60DR-E, it can be set also from the remote controller.

Connecting methods vary depending on the types of pulse signal

Refer to Section 

2

 “When the external device has a charged

operation signal of 12 VDC or 24 VDC” or “When the external
device has an uncharged a-contact signal”.

(1) Connect from Lossnay Unit 1 to Lossnay Unit 2, and from Unit 2 to

Unit 3 and so on up to a maximum of 15 units using a transmission
cable (PVC insulated PVC jacketed and either between 

φ

 0.65

and 

φ

 1.2, or between 0.3 mm

2

 and 1.25 mm

2

 in cross section).

(2) Change the setting on the main/sub switch (SW1) on the second

and subsequent Lossnay units to “Sub”.

CAUTION

Don’t tighten screws of terminal block with a torque larger than
0.5 Nm. It could damage the PCB.

Note

Up to four 0.3 mm

2

 stranded wires or 

φ

 0.65 PVC wires can

be connected to one input terminal.

For other types of wire, up to two can be connected.

The operation signal and pulse signal can be connected to
the external device of the main Lossnay only.

Connect the power to each respective Lossnay unit.

When the LGH-150RX

5

 and LGH-200RX

5

 types are connected, they

operate at low fan speed even if extra low fan speed is selected.

Remote controller
(PZ-60DR-E or
PZ-41SLB-E)

Lossnay

(Main)

Remote controller
(PZ-60DR-E or PZ-41SLB-E)

Power
supply

External

device

Operating switch
for external device

Lossnay (Sub)

MAX 15 units

Power
supply

Lossnay (Sub)

Power
supply

Power
supply

Connect to
remote
controller
(PZ-60DR-E)

Connect
to third
Lossnay

Main/Sub selection

switch
(SW1)

Main

Sub

2

1

2

1

Transmission cable

First Lossnay

Second
Lossnay

TM4

(Factory setting: main)

TM4

1

2

SW2

3

4

5

6

7

8

9 10

ON

ON
OFF

Summary of Contents for Lossnay LGH-150RX5-E

Page 1: ...s a result of incomplete combustion Do not use at a place where it is exposed to high temperatures 40 C or higher naked flames or in environment with combustible fumes It could cause fire Do not use in an environment such as a chemical factory where hazardous gases such as acidic gases alkaline gases organic solvent fumes paint fumes or gases containing corrosive components are generated It could ...

Page 2: ...200 RX5 Model A B C D Weight kg LGH 150 RX5 1004 690 690 1045 105 LGH 200 RX5 1231 917 917 1272 118 Unit mm Accessory parts Duct connecting flanges x4 Mounting screws x16 Slim Lossnay connection cable gray two wires x1 Ceiling suspension fixture 4 15 x 30 oval SA supply air RA return air EA exhaust air outlet OA outside air intake Core air filter High Efficiency filter fan maintenance space Lossna...

Page 3: ...de air intake Supply air grille not included Except the 150 and 200 RX5 Remote controller optional parts EA exhaust air outlet OA outside air intake It can be installed by inverting the top and the bottom After installing the duct connecting flange remove the maintenance cover Turn the cover by 180 and then reinstall it Maintenance space Lossnay unit Inspection opening EA exhaust air outlet OA out...

Page 4: ...is recommended that the indoor ductwork be covered with insulation material Do not carry out the following types of duct construction Doing so could cause a drop in the air volume and generate abnormal noises 5 When changing the direction of the out door side duct EA OA Except for LGH 150 and 200 RX5 1 Removal of flange cover Unscrewing the flange cover mounting screws 4 pcs remove the flange cove...

Page 5: ...is product the wiring installation method will vary according to the design of the system Perform electrical installation to meet local electrical regulations Always use double insulated PVC cable for the transmission cables Wiring work must be performed by qualified professionals All supply circuits must be disconnected before obtaining access to the terminal devices M1 Motor for exhaust fan M2 M...

Page 6: ...onnector of control board 2 1 TM4 S B A TB5 M NET When the optional Remote Controller PZ 60DR E is used as the M NET System connect it to 1 2 of TM4 terminal block and connect M NET transmission wire to A B on TB5 terminal block 2nd remote controller Max 2 remote controllers installable 2 PZ 41SLB E and PZ 52SF E cannot be used when using PZ 60DR E M NET Transmission cable Shielded wire 2nd or lat...

Page 7: ...nnected to single input terminal is up to 4 wires for ø0 65 PVC wire or 0 3 mm2 stranded wire It is up to 2 wires for any other wires PZ 41SLB E cannot be used when MELANS centralized control of the Lossnay is used PZ 60DR E and PZ 41SLB E cannot be installed simultaneously 1 Connect the output signal cable from the external device to the input terminal block TM2 of the external controller CAUTION...

Page 8: ...3 3 and the negative side to 1 1 1 1 1 2 Confirm that the pulse input switch SW2 2 is set to OFF Set to OFF at time of shipment When the external device has a charged operating signal of 12 VDC or 24 VDC Connect the operating signal wire from the external device via the remote output to 1 and 2 on the external control input terminal block TM2 No polarity 1 Move the pulse input switch SW2 2 to the ...

Page 9: ...y Contactor rating DC 1 mA When connecting to the City Multi Lossnay remote controller PZ 52SF E or Mitsubishi Electric Air Conditioner Network System MELANS 10 Remote ON OFF adaptor Optional PAC SA88HA E When SW1 is ON fan speed of the Lossnay will be set to Low regardless of the remote control setting Use this in such a way that it ventilates at High fan speed normally and when the external sens...

Page 10: ...roller When interlocking with Mitsubishi Free Plan air conditioner Incase of PZ 60DR E Limit the total length of transmission wires no longer than 500 m Limit the wiring length between Lossnay and the power supply unit Optional or the outdoor unit no longer than 200 m M NET transmission cable Lossnay M NET transmission cable Power supply unit Lossnay MELANS M NET transmission cable Air conditioner...

Page 11: ...door OA air temperatures and automatically select the Lossnay ventilation or Bypass ventilation With this mode however priority is given to the Bypass ventilation This setting reflects to the night purge operation condition Bypass automatic ventilation priority setting 5 OFF ON 7 7 SW2 Operation When outdoor temperature OA is 28 C or higher within 24 hours then Bypass ventilation starts by the com...

Page 12: ...pply fan is stopped during defrosting of the air conditioner when Mr Slim or City Multi indoor unit is connected to a duct When the outdoor air is lower than 15 C stop the operation of exhaust fan OA stop operation at cold region Operation Exhaust fan operation factory setting Exhaust fan stop exhaust fan operation at Low speed at outdoor air lower than 15 C OFF ON 3 3 SW5 Settings for automatic r...

Page 13: ...the external device has come off of the external control input terminal Check in the case of multiple units whether the Main Sub selection switch on the Lossnay unit which is connected to the external control input terminal is set on the Master setting and check whether the Main Sub selection switch on other Lossnay units are set to Sub Check that the trial operation switch SW2 1 is set to off Cha...