9
English
SW1
CN16
SW1
CN16
SW1
CN16
SW1
CN16
0
9
Installation method (continued)
S
B
A
TB5
M-NET transmission cable
Shielded wire
M-NET transmission cable input terminal block
*
If centralized control is performed according the wire connection
shown in this section, the remote controller (PZ-41SLB-E) can-
not be used.
Note
*
Don’t tighten screws of terminal block with a torque
larger than 0.5Nm. It could damage the PCB.
*
Response times to external input signals are
as shown in the following table.
Connect the power supply cable from the Electrically operated
damper to
9
and
0
of the monitor output terminal block (TM4)
with reference to the wire connection diagram.
Operation monitor output with delay function 1 can be possible.
(Refer to function settings
6
“Setting for TM4
90
”)
Electrically
operated
damper
Power Supply
Lamp
When connect to an Electrically operated damper, or take
Operation monitor output
6
Contactor rating
Max 240 VAC, 2 A
24 VDC, 2 A
Min 220 VAC, 100 mA
5 VDC,
100 mA
When switching High/Low/Extra-Low fan speed externally
(when CO
2
sensor or other equipment is connected)
7
Using marketed CO
2
sensor, etc., make connection by inserting the
optional remote ON/OFF adaptor (PAC-SA88HA-E) in the connector
CN16 (High/Low selector) as shown by the figure.
■
To force High fan speed externally
When SW1 is "ON", fan speed of the Lossnay will be set to
"High"(Extra-High) regardless of the remote control setting.
Use this in such a way that it ventilates at Low or Extra-Low fan
speed normally, and when the external sensor detects contamination
of indoor air, it changes to High (Extra High) fan speed operation.
CO
2
sensor, etc.
(When CO
2
increases: Closed)
SW1: High fan speed operation switch
(When closed: For High fan speed operation)
■
To force Low fan speed externally
When switching Bypass externally.
8
Establish the wire connection by inserting the optional remote ON/OFF
adaptor (PAC-SA88HA-E) in the connector CN16 (Ventilation mode selector).
With SW1 is “ON”, the ventilation mode of Lossnay is changed to
the Bypass ventilation regardless of the setting on the remote
controller.
*
When the outdoor air temperature drops lower than 8˚C, it
changes to the heat exchanger ventilation. (Display of the remote
controller does not change.)
When using the remote/local switching and the ON/OFF
input (level signal)
9
The remoto controller (PZ-41SLB-E) cannot be used.
Insert the optional remote ON/OFF adaptor (PAC-SE55RA-E) in
CN32 on the Lossnay control PCB.
CN32
SW1
SW2
Y
X
Y
X
SW1: When this is ON, Lossnay cannot turn ON/OFF by the Remote
Controller (PZ-60DR-E, PZ-52SF-E).
SW2: When SW1 is ON, Lossnay can be turned ON by setting SW2
at ON or turned OFF by setting SW2 at OFF.
SW1: Remote/local selector switch
SW2: ON/OFF switch
X, Y : Relay (Contactor rating DC 1 mA)
When connecting to the City Multi, Lossnay remote controller (PZ-52SF-E)
or Mitsubishi Electric Air-Conditioner Network System (MELANS)
10
Remote ON/OFF adaptor
(Optional) PAC-SA88HA-E
When SW1 is "ON", fan speed of the Lossnay will be set to "Low"
regardless of the remote control setting.
Use this in such a way that it ventilates at High fan speed normally,
and when the external sensor detect that the indoor air contamination
is low, it changes to Low fan speed operation.
Connect to
6
and
7
, or
7
and
8
of the monitor output terminal
block (TM3) with reference to the wire connection diagram.
When take Malfunction monitor output, or take Bypass
operation monitor output.
6
7
8
Lamp or
monitoring unit
Power
Supply
Monitor output terminal
TM3
5
Monitor output
terminal (TM4)
Brown 1
Red 2
Orange 3
Yellow 4
Green 5
Not used. Insulate completely.
Max wiring length 10 m
Lossnay
control board
Fan speed/
Ventilation
mode selection
CO
2
sensor, etc.
(When CO
2
decreases: Closed)
SW1: Low fan speed operation switch
(When closed: For Low fan speed operation)
Remote ON/OFF adaptor
(Optional) PAC-SA88HA-E
Brown 1
Red 2
Orange 3
Yellow 4
Green 5
Not used. Insulate completely.
Max wiring length 10 m
Lossnay
control board
Fan speed/
Ventilation
mode selection
■
To force Extra-Low fan speed externally
CO
2
sensor, etc.
(When CO
2
decveases: Closed)
SW1: Low fan speed operation switch
(When closed: For Low fan speed operation)
Remote ON/OFF adaptor
(Optional) PAC-SA88HA-E
Brown 1
Red 2
Orange 3
Yellow 4
Green 5
Not used. Insulate completely.
Lossnay
control board
Fan speed/
Ventilation
mode selection
When SW1 is "ON", fan speed of the Lossnay will be set to "Extra-
Low" regardless of the remote control setting.
Use this in such a way that it ventilates at High fan speed normally,
and when the external sensor detects that the indoor air
contamination is low, it changes to Extra-Low fan speed operation.
*
For the LGH-150RX
5
and LGH-200RX
5
types, fan speed of the
Lossnay will be “Low”.
Max wiring length 10 m
SW1: Bypass ventilation operation switch
(When closed: For Bypass ventilation operation)
Remote ON/OFF adaptor
(Optional) PAC-SA88HA-E
Brown 1
Red 2
Orange 3
Yellow 4
Green 5
Not used. Insulate completely.
Lossnay
control board
Fan speed/
Ventilation
mode selection
Max wiring length 10 m
Remote control
board
Max wiring length 10 m
Remote ON/OFF adaptor
(Optional) PAC-SE55RA-E
Lossnay
control board
Relay circuit
Orange 1
Red 2
Brown 3
Relay power supply
Bypass operation signal
contactor rating
Max 240 VAC, 1 A
24 VDC, 1 A
Min 220 VAC, 100 mA
5 VDC,
100 mA
Malfunction signal
Malfunction indicator
Bypass operation indicator
Note
*
Don’t tighten screws of terminal block with a torque larger than
0.5Nm. It could damage the PCB.
Bypass or Delay 2 monitor output with delay function 2 can be possible.
(Refer to function settings
C
“Setting for TM3
67
”)
External Signal Response Time
Level Signal
Max. 7 sec.
Pulse Signal Max. 200 msec