4

If the suspension bolts are short, change the
mounting hardware.

For the models LGH-80 and 100 RX

5

(1) Remove the suspension fixture and mount it to the upper mounting

position.

(2) Replace screws in the holes for the suspension fixture that has been

removed to prevent air leakage.

4. Connecting the ducts

(1) Fasten the duct securely to the duct connecting flange, and wrap

aluminum tape (not included) around the joints so that there is
no air leakage.

(2) Suspend the ducts from the ceiling so that their weight will not

be applied to the Lossnay unit.

(3) The two outdoor ducts must be covered with heat-insulating ma-

terial in order to prevent condensation from forming.

CAUTION

Before attaching the ducts, check that no (debris or any other)
foreign matter (scraps of paper, vinyl, etc.) has found its way
inside the ducts.

Do not touch the damper plate inside Lossnay unit when con-
necting the ducts.

If it is expected that the ambient temperature around the place
where the Lossnay unit is installed will be high during the
summer air conditioning season, it is recommended that the
indoor ductwork be covered with insulation material.

Do not carry out the following types of duct construction. (Doing so
could cause a drop in the air volume and generate abnormal noises.)

5. When changing the direction of the out door

side duct (EA/OA)·····Except for LGH-150 and
200 RX

5

(1) Removal of flange cover

Unscrewing the flange cover mounting screws (4 pcs), remove
the flange cover.

Flange cover

Installation method (continued)

• Extremely

sharp bends

• Multiple bends

• Bends right next to

the outlet

• Extreme reduction in

the diameter of the
connected ducts

Models LGH-80 and 100 RX

5

Suspension fixture

Screws

Models LGH-15 to 100 RX

5

Models LGH-150 and 200 RX

5

Taping

Duct

Heat-insulating
material

Duct connecting flange

Duct

Taping

(2) Installation of duct connecting flange

1. Install the duct connecting flange using attached mounting

screws.

2. Fix the removed flange cover with the removed mounting

screws (4 pcs).

Mounting screw
(for flange cover)

Mounting screw
(Accessory parts)

Duct connection flange

Ceiling suspension fixture

Ceiling
suspension fixture

Aluminum tape

Duct connecting flange

Outdoor duct

Heat-insulating
material

Lossnay
unit

Aluminum tape

Duct connecting
flange

Outdoor duct

Heat-insulating
material

Lossnay
unit

Summary of Contents for Lossnay LGH-150RX5-E

Page 1: ...s a result of incomplete combustion Do not use at a place where it is exposed to high temperatures 40 C or higher naked flames or in environment with combustible fumes It could cause fire Do not use in an environment such as a chemical factory where hazardous gases such as acidic gases alkaline gases organic solvent fumes paint fumes or gases containing corrosive components are generated It could ...

Page 2: ...200 RX5 Model A B C D Weight kg LGH 150 RX5 1004 690 690 1045 105 LGH 200 RX5 1231 917 917 1272 118 Unit mm Accessory parts Duct connecting flanges x4 Mounting screws x16 Slim Lossnay connection cable gray two wires x1 Ceiling suspension fixture 4 15 x 30 oval SA supply air RA return air EA exhaust air outlet OA outside air intake Core air filter High Efficiency filter fan maintenance space Lossna...

Page 3: ...de air intake Supply air grille not included Except the 150 and 200 RX5 Remote controller optional parts EA exhaust air outlet OA outside air intake It can be installed by inverting the top and the bottom After installing the duct connecting flange remove the maintenance cover Turn the cover by 180 and then reinstall it Maintenance space Lossnay unit Inspection opening EA exhaust air outlet OA out...

Page 4: ...is recommended that the indoor ductwork be covered with insulation material Do not carry out the following types of duct construction Doing so could cause a drop in the air volume and generate abnormal noises 5 When changing the direction of the out door side duct EA OA Except for LGH 150 and 200 RX5 1 Removal of flange cover Unscrewing the flange cover mounting screws 4 pcs remove the flange cove...

Page 5: ...is product the wiring installation method will vary according to the design of the system Perform electrical installation to meet local electrical regulations Always use double insulated PVC cable for the transmission cables Wiring work must be performed by qualified professionals All supply circuits must be disconnected before obtaining access to the terminal devices M1 Motor for exhaust fan M2 M...

Page 6: ...onnector of control board 2 1 TM4 S B A TB5 M NET When the optional Remote Controller PZ 60DR E is used as the M NET System connect it to 1 2 of TM4 terminal block and connect M NET transmission wire to A B on TB5 terminal block 2nd remote controller Max 2 remote controllers installable 2 PZ 41SLB E and PZ 52SF E cannot be used when using PZ 60DR E M NET Transmission cable Shielded wire 2nd or lat...

Page 7: ...nnected to single input terminal is up to 4 wires for ø0 65 PVC wire or 0 3 mm2 stranded wire It is up to 2 wires for any other wires PZ 41SLB E cannot be used when MELANS centralized control of the Lossnay is used PZ 60DR E and PZ 41SLB E cannot be installed simultaneously 1 Connect the output signal cable from the external device to the input terminal block TM2 of the external controller CAUTION...

Page 8: ...3 3 and the negative side to 1 1 1 1 1 2 Confirm that the pulse input switch SW2 2 is set to OFF Set to OFF at time of shipment When the external device has a charged operating signal of 12 VDC or 24 VDC Connect the operating signal wire from the external device via the remote output to 1 and 2 on the external control input terminal block TM2 No polarity 1 Move the pulse input switch SW2 2 to the ...

Page 9: ...y Contactor rating DC 1 mA When connecting to the City Multi Lossnay remote controller PZ 52SF E or Mitsubishi Electric Air Conditioner Network System MELANS 10 Remote ON OFF adaptor Optional PAC SA88HA E When SW1 is ON fan speed of the Lossnay will be set to Low regardless of the remote control setting Use this in such a way that it ventilates at High fan speed normally and when the external sens...

Page 10: ...roller When interlocking with Mitsubishi Free Plan air conditioner Incase of PZ 60DR E Limit the total length of transmission wires no longer than 500 m Limit the wiring length between Lossnay and the power supply unit Optional or the outdoor unit no longer than 200 m M NET transmission cable Lossnay M NET transmission cable Power supply unit Lossnay MELANS M NET transmission cable Air conditioner...

Page 11: ...door OA air temperatures and automatically select the Lossnay ventilation or Bypass ventilation With this mode however priority is given to the Bypass ventilation This setting reflects to the night purge operation condition Bypass automatic ventilation priority setting 5 OFF ON 7 7 SW2 Operation When outdoor temperature OA is 28 C or higher within 24 hours then Bypass ventilation starts by the com...

Page 12: ...pply fan is stopped during defrosting of the air conditioner when Mr Slim or City Multi indoor unit is connected to a duct When the outdoor air is lower than 15 C stop the operation of exhaust fan OA stop operation at cold region Operation Exhaust fan operation factory setting Exhaust fan stop exhaust fan operation at Low speed at outdoor air lower than 15 C OFF ON 3 3 SW5 Settings for automatic r...

Page 13: ...the external device has come off of the external control input terminal Check in the case of multiple units whether the Main Sub selection switch on the Lossnay unit which is connected to the external control input terminal is set on the Master setting and check whether the Main Sub selection switch on other Lossnay units are set to Sub Check that the trial operation switch SW2 1 is set to off Cha...

Reviews: