Screw
LGH-150 and 200 RX
5
Control box cover
Control box cover
LGH-15 to 100 RX
5
LGH-15 to 100 RX
5
Control box cover
Screw
The following system configuration can
be created. Connect the necessary parts.
1
When connecting with remote controller (PZ-60DR-E, PZ-41SLB-E).
2
When interlocked with indoor unit of air conditioner or other
external device including other manufactures.
3
When interlocking with a pulse output device.
4
When operating multiple Lossnay units.
5
When take malfunction monitor output, or take Bypass
operation monitor output.
6
When connect to an Electrically operated damper, or take
operation monitor output.
7
When switching High / Low / Extra-Low speed externally (when
CO
2
sensor or other device is connected).
8
When switching Bypass externally.
9
When using the remote/local switching and the ON/OFF input (level signal)
0
When connecting to the City Multi, Lossnay remote controller (PZ-52SF-
E) or Mitsubishi Electric Air-Conditioner Network System (MELANS).
CAUTION
•
When connecting external devices (electrically operated damper,
lamp, monitoring unit, etc.) using output signals of the Lossnay
unit, make sure to install safety equipment for the external devices.
(It could cause fire, damage, etc. without safety equipment.)
*
When controlling Lossnay units with the central control, connect
wires according to
0
.
Securely connect the transmission cable (PVC insulated PVC jack-
eted and either between
φ
0.65 and
φ
1.2, or between 0.3 mm
2
and
1.25 mm
2
in cross section) from the remote controller to
1
and
2
of
the input terminal block (TM4). (No polarity)
•
If there are two remote controllers, connect them in the same way.
Note
•
Don’t tighten screws of terminal block with a torque larger
than 0.5 Nm. It could damage the PCB.
•
Number of transmission wires which can be connected to
single input terminal is up to 4 wires for ø0.65 PVC wire or
0.3 mm
2
stranded wire. It is up to 2 wires for any other wires.
•
PZ-41SLB-E cannot be used when MELANS centralized
control of the Lossnay is used.
•
PZ-60DR-E and PZ-41SLB-E cannot be installed simultaneously.
(1) Connect the output signal cable from the external device to the
input terminal block (TM2) of the external controller.
CAUTION
•
The connection may vary according to the output signal type
of the external unit.
•
Don’t tighten screws of terminal block with a torque larger than
0.5 Nm. It could damage the PCB.
When connecting with remote controller (PZ-60DR-E, PZ-
41SLB-E)
1
TM4
2
1
Remote controller input terminal
Transmission wires
When interlocked with indoor unit of air conditioner or
other external device including other manufactures
2
Installation method (continued)
Connecting the power supply cable
1. Remove the screws and the control box cover
2. Connecting the power supply cable and
transmission cable
Pass the power cable through the bush* and connect to the TM1
terminal block using the round terminals. Connect the ground wire
to the ground terminal and secure tightening the bush. (*: for PG
connector or the like)
CAUTION
•
Always separate the power supply cable and transmission ca-
ble by 5 cm or more to prevent malfunctioning of the unit.
•
If the length of the stripped power cables wires is too long, the
conductors may touch and short out.
•
Power supply cable size : 1.5mm
2
or more.
(1) Tighten the ground wire and transmission cables to the terminal
block.
(2) Secure the transmission cables using the cord clips.
Upon completion of the wiring connections, replace the control box cover.
Ground wire
LGH-150 and 200 RX
5
TM1
Insert the cutting
Bush
Power supply cable
PG connector
Cord clips
Power supply cable
Power supply cable
Cord clip
Insert the cutting
TM1
Bush
PG connector
Ground wire
Transmission cable
Power supply
Up to two remote controllers
(PZ-60DR-E or PZ-41SLB-E) can be used.
Lossnay