Address setting is requiered when connecting to City Multi, Lossnay
remote controller (PZ-52SF-E) and MELANS.

Setting the address

Use the following procedure when setting the address for dedicated
Lossnay.
(The method in determining the addresses will depend on the existing
system. Refer to the appropriate technical documents for details.)
(1) Remove the control box cover.
(2) Use a flatblade screwdriver to turn the address setting switch on the

circuit board.

SA1 indicates the 10 digit and SA2 indicates the 1 digit.

The factory setting is "00"

*

When the address number has been changed, the data in the
memory is automatically reset.

SA1

SA2

Function settings

Installation method (continued)

10 digit

1 digit

One shielded wire is connected to TB5 

S

 on the PCB on terminal.

Address setting is required. (Refer to function setting section.)
M-NET transmission cable: Connect any of the City Multi indoor

unit, or Mitsubishi Electric Air-Condi-
tioner Network System (MELANS) - to
the Lossnay.

Connecting positions are different for the Remote Controller PZ-
60DR-E and PZ-52SF-E.
PZ-60DR-E:

Connect to TM4 

1

2

 on the PCB. (See Section 

1

 “When

connecting with Remote Controller (PZ-60DR-E)”.)

PZ-52SF-E:

Connect to TB5 

A

,

 

B

 on the same terminal block as for the

M-NET transmission wires.

Securely connect the M-NET transmission wires to TB5 

AB

.

(No-Polar)
Type: (Shielded wire, CVVS/CPEVS)
Wire diameter: 1.25 mm

2

 to 2.0 mm

2

CAUTION

Don’t tighten screws on the terminal block with a torque larger
than 0.5 Nm. It may damage the PCB.

Always use shielded wires only for the M-NET transmission
wires, and finish the shield properly.

Changing the function selection switches
(SW-2 and 5)

Set the selection switches (SW-2 and 5) to perform the appropriate
function.
*

The function marked (*) above can be set also from the remote
controller (PZ-60DR-E). If the function is switched later using the
remote controller, it operates according to the setting on the remote
controller.

When interlocking with Mitsubishi Free Plan air conditioner

Incase of PZ-60DR-E

*

Limit the total length of transmission wires no longer than 500 m.
Limit the wiring length between Lossnay and the power supply
unit (Optional) or the outdoor unit no longer than 200 m.

M-NET transmission cable

Lossnay

M-NET transmission cable

Power

supply unit

Lossnay

MELANS

M-NET transmission cable

Air

conditioner

Air

conditioner

MA remote
controller

Lossnay

When connecting to PZ-60DR-E and MELANS

Incase of PZ-52SF-E

Connect the power feeding unit.

1

2

3

4

5

6

7

8

9

10

(SW2)

1

2

3

4

5

6

7

8

9

10

(SW5)

1

Settings for pulse input

2

Switching to power supply/exhaust when operation starts

3

Switching to the multi ventilation mode

4

Power supply ON/OFF function (cannot be set when PZ-41SLB-E is used)

5

Bypass automatic ventilation priority setting *

6

Setting for TM4 

90

 output

7

Extra High/High switch setting

8

Set for delay operation at heating or cooling start-up

9

Operation output monitor

0

Exhaust fan stop during defrosting, exhaust fan Low speed operation at outdoor air lower than -15˚C

A

Settings for automatic recovery following power supply interruption
(cannot be set when PZ-41SLB-E is used)

B

Settings for filter cleaning (cannot be set when PZ-41SLB-E is used)

C

Setting for TM3 

67

 output

D

Settings for interlock mode

E

Exhaust fan stop at outdoor air lower than -15˚C *

Trial operation

Pulse input setting *

Power supply/exhaust when operation starts *

SA fan fixed at Low speed *

EA fan fixed at Low speed *

Power supply ON/OFF *

Bypass ventilation priority at Automatic mode *

Setting for TM4 

90

 output

Supply Extra High/High *

Exhaust Extra High/High *

Air

conditioner

Air

conditioner

(Optional)

Delay setting *

Operation monitor output *

Auto restoration after power failure *

Filter maintenance indication setting *

Setting for TM3 

67

 output

Interlock mode setting *

Exhaust fan stop at outdoor air lower than -15˚C *

Not used OFF: LGH-15 to 100RX

5

ON  : LGH-150 and 200RX

5

Exhaust fan stop during defrosting *

Exhaust fan at Low speed at outdoor air lower than -15˚C

 *

}

PZ-60DR-E

PZ-52SF-E

PZ-60DR-E

Address setting switch

MA remote
controller

Summary of Contents for Lossnay LGH-150RX5-E

Page 1: ...s a result of incomplete combustion Do not use at a place where it is exposed to high temperatures 40 C or higher naked flames or in environment with combustible fumes It could cause fire Do not use in an environment such as a chemical factory where hazardous gases such as acidic gases alkaline gases organic solvent fumes paint fumes or gases containing corrosive components are generated It could ...

Page 2: ...200 RX5 Model A B C D Weight kg LGH 150 RX5 1004 690 690 1045 105 LGH 200 RX5 1231 917 917 1272 118 Unit mm Accessory parts Duct connecting flanges x4 Mounting screws x16 Slim Lossnay connection cable gray two wires x1 Ceiling suspension fixture 4 15 x 30 oval SA supply air RA return air EA exhaust air outlet OA outside air intake Core air filter High Efficiency filter fan maintenance space Lossna...

Page 3: ...de air intake Supply air grille not included Except the 150 and 200 RX5 Remote controller optional parts EA exhaust air outlet OA outside air intake It can be installed by inverting the top and the bottom After installing the duct connecting flange remove the maintenance cover Turn the cover by 180 and then reinstall it Maintenance space Lossnay unit Inspection opening EA exhaust air outlet OA out...

Page 4: ...is recommended that the indoor ductwork be covered with insulation material Do not carry out the following types of duct construction Doing so could cause a drop in the air volume and generate abnormal noises 5 When changing the direction of the out door side duct EA OA Except for LGH 150 and 200 RX5 1 Removal of flange cover Unscrewing the flange cover mounting screws 4 pcs remove the flange cove...

Page 5: ...is product the wiring installation method will vary according to the design of the system Perform electrical installation to meet local electrical regulations Always use double insulated PVC cable for the transmission cables Wiring work must be performed by qualified professionals All supply circuits must be disconnected before obtaining access to the terminal devices M1 Motor for exhaust fan M2 M...

Page 6: ...onnector of control board 2 1 TM4 S B A TB5 M NET When the optional Remote Controller PZ 60DR E is used as the M NET System connect it to 1 2 of TM4 terminal block and connect M NET transmission wire to A B on TB5 terminal block 2nd remote controller Max 2 remote controllers installable 2 PZ 41SLB E and PZ 52SF E cannot be used when using PZ 60DR E M NET Transmission cable Shielded wire 2nd or lat...

Page 7: ...nnected to single input terminal is up to 4 wires for ø0 65 PVC wire or 0 3 mm2 stranded wire It is up to 2 wires for any other wires PZ 41SLB E cannot be used when MELANS centralized control of the Lossnay is used PZ 60DR E and PZ 41SLB E cannot be installed simultaneously 1 Connect the output signal cable from the external device to the input terminal block TM2 of the external controller CAUTION...

Page 8: ...3 3 and the negative side to 1 1 1 1 1 2 Confirm that the pulse input switch SW2 2 is set to OFF Set to OFF at time of shipment When the external device has a charged operating signal of 12 VDC or 24 VDC Connect the operating signal wire from the external device via the remote output to 1 and 2 on the external control input terminal block TM2 No polarity 1 Move the pulse input switch SW2 2 to the ...

Page 9: ...y Contactor rating DC 1 mA When connecting to the City Multi Lossnay remote controller PZ 52SF E or Mitsubishi Electric Air Conditioner Network System MELANS 10 Remote ON OFF adaptor Optional PAC SA88HA E When SW1 is ON fan speed of the Lossnay will be set to Low regardless of the remote control setting Use this in such a way that it ventilates at High fan speed normally and when the external sens...

Page 10: ...roller When interlocking with Mitsubishi Free Plan air conditioner Incase of PZ 60DR E Limit the total length of transmission wires no longer than 500 m Limit the wiring length between Lossnay and the power supply unit Optional or the outdoor unit no longer than 200 m M NET transmission cable Lossnay M NET transmission cable Power supply unit Lossnay MELANS M NET transmission cable Air conditioner...

Page 11: ...door OA air temperatures and automatically select the Lossnay ventilation or Bypass ventilation With this mode however priority is given to the Bypass ventilation This setting reflects to the night purge operation condition Bypass automatic ventilation priority setting 5 OFF ON 7 7 SW2 Operation When outdoor temperature OA is 28 C or higher within 24 hours then Bypass ventilation starts by the com...

Page 12: ...pply fan is stopped during defrosting of the air conditioner when Mr Slim or City Multi indoor unit is connected to a duct When the outdoor air is lower than 15 C stop the operation of exhaust fan OA stop operation at cold region Operation Exhaust fan operation factory setting Exhaust fan stop exhaust fan operation at Low speed at outdoor air lower than 15 C OFF ON 3 3 SW5 Settings for automatic r...

Page 13: ...the external device has come off of the external control input terminal Check in the case of multiple units whether the Main Sub selection switch on the Lossnay unit which is connected to the external control input terminal is set on the Master setting and check whether the Main Sub selection switch on other Lossnay units are set to Sub Check that the trial operation switch SW2 1 is set to off Cha...

Reviews: