Symptom

Will not operate even when the
operation switch for the remote
controller (PZ-60DR-E, PZ-41SLB-E)
and/or operation switch for the
Lossnay remote controller (PZ-52SF-
E) is pressed.

Remedy

• Check the power supply. (The specified power supply is single-phase 220-240V ~ 50Hz.)

• Check for a short circuit or disconnection in the transmission cable. (Check that the voltage between terminals in the

transmission cables is 9 to 15 VDC for the PZ-60DR-E or PZ-41SLB-E and 20 to 30 VDC for the PZ-52SF-E.)

• Check that the there is 5 cm or more separating the transmission cable from the power supply cable and any other

transmission cables.

• Run the Lossnay independently using the trial operation switch (SW2-1) and check if it runs.

Lossnay runs

Check the signal lines

Lossnay doesn’t run

Check the power supply

• Check if there are three or more remote controller connected (PZ-60DR-E or PZ-41SLB-E). (The maximum is two.)

• Perform the registration operation using the remote controller for the Lossnay (PZ-52SF-E) or MELANS. (Refer to the

installation instructions for the remote controller for the Lossnay or MELANS.)

• Check the power supply. (Specified power supply: single-phase 220-240V, wire dia. ø1.6, switch capacity

• Check if the power supply unit is connected or not, and if the power is supplied or not (For a system with Lossnay only, it is necessary to install the power supply unit.)

• Check the transmission wire for short-circuit or broken wire (Check if DC 20 - 30 V is detected between the terminals of transmission wire).

• Check if a clearance of 5 cm is secured between the transmission wire and the power cable and other transmission wires.

• Run Lossnay independently to see if it operates properly or not.

Lossnay operates

Inspect the transmission wire

Lossnay doesn’t operate

Check the power supply

• Check whether or not there is a power supply unit and that the power has been turned on. (On systems with only a

Lossnay, a power supply unit is required.)

• Check if the pulse input switch (SW2-2) is off. (Can be set from PZ-60DR-E)

• Check the overall cable length between the indoor unit or external device and Lossnay. (Refer to technical publications

or other such documents.)

• Check the connections at the external control input terminal block (TM2).

In the case of voltage charged 12 or 24 VDC output device: Connect to external control input terminals 

1

 and 

2

.

In the case of uncharged a-contact output device: Connect to external control input terminals 

1

 and 

3

.

In the case of Mr. Slim (A control or K control): Connect to external control input terminals 

1

 and 

2

.

• Perform the registration operation using the remote control for the air conditioner or MELANS. (Refer to the installation

instructions for the remote controller for the indoor unit or MELANS.)

• Check if the delay has been set.

• Check the overall length of the transmission cable between the external device and Lossnay. (Refer to technical

publications or other such documents.)

• Check if the transmission cable from the external device has come off of the external control input terminal.

• Check, in the case of multiple units, whether the Main/Sub selection switch on the Lossnay unit which is connected to

the external control input terminal is set on the Master setting, and check whether the Main/Sub selection switch on other
Lossnay units are set to Sub.

• Check that the trial operation switch (SW2-1) is set to off.

Charged 12 or 24 VDC output device

Uncharged a-contact output device

Mr. Slim

Stop signal

0 VDC

Unlimited resistance 

2 to 6 VDC (pulse signal)

Operation signal

12 or 24 VDC

Resistance: 0 

2 to 6 VDC (pulse signal)

2 flashes

3 flashes

4 flashes

5 flashes

8 flashes

On

Turn the power off and consult your dealer.

Fault on Lossnay circuit

Fault on Damper devices

Fault on Lossnay thermostat (OA side)

Fault on Lossnay thermostat (RA side)

Improper OA temperature (outside the range)

Operating

Unless the Remote Controller (PZ-60DR-E) or remote
controller switch (PZ-41SLB-E, etc) is used, the lamp
extinguishes (operation stops) 30 minutes later.

“HO” flashes in remote controller for
Lossnay (PZ-52SF-E).

When using M-NET, the operation
switch of Remote Controller (PZ-
60DR-E), Lossnay remote
controller (PZ-52SF-E) or
MELANS is dead.

Does not operate even when the
operation switch for remote
controller for Lossnay (PZ-52SF-E)
or MELANS is pressed.

Indoor unit or external device does
not interlock.

Lossnay does not stop.

The inspection indicator lamp (LED
1 Green) in the control box flashes.

Trial operation (continued)

4. If trouble occurs during trial operation

When an inspection number blinks on the remote controller, follow the procedures shown in the installation and operating manuals
provided with the remote controller.

If the remote controller is not used, operate after approximately 45 seconds of turning on the power for the Lossnay.

3. Complete system trial operation

Interlock system containing an indoor unit and/or external device

Use the remote controller for the indoor unit or the operating switches
for the external device and confirm that the indoor unit and Lossnay
are interlocked.

If delay time has been set, check that the Lossnay operates after
the delay time has passed.

If MELANS System

Use MELANS to confirm the operation of the Lossnay.

The inspection indicator lamp (LED
2 Red ) in the control box flashes.

1 to 8

flashes

On

Turn off the power and immediately contact your
dealer.

Use the controller to perform the registration.

Error in M-NET communication

Registration operation has not been performed.

Operation

Power will be supplied to the motor for the Lossnay fan and
operation will be performed at the “High” setting. Power will be
supplied to the motor for the Lossnay by-pass and operation of
the damper plate will be performed. (Approximately 1 minute)

2. Stand-alone Lossnay trial operation

(1) Supply power to the Lossnay unit.
(2) Turn the trial operation switch (SW2-1) “On.”

Operation will start with the “High” setting and with Bypass
ventilation operating. (This will take approximately 1 minute
after the power is turned on.)

(3) Confirm that the Bypass damper plate in the Lossnay unit is operated.
(4) Turn the trial operation switch (SW2-1) “Off.”

OFF

ON

1

SW2

Summary of Contents for Lossnay LGH-150RX5-E

Page 1: ...s a result of incomplete combustion Do not use at a place where it is exposed to high temperatures 40 C or higher naked flames or in environment with combustible fumes It could cause fire Do not use in an environment such as a chemical factory where hazardous gases such as acidic gases alkaline gases organic solvent fumes paint fumes or gases containing corrosive components are generated It could ...

Page 2: ...200 RX5 Model A B C D Weight kg LGH 150 RX5 1004 690 690 1045 105 LGH 200 RX5 1231 917 917 1272 118 Unit mm Accessory parts Duct connecting flanges x4 Mounting screws x16 Slim Lossnay connection cable gray two wires x1 Ceiling suspension fixture 4 15 x 30 oval SA supply air RA return air EA exhaust air outlet OA outside air intake Core air filter High Efficiency filter fan maintenance space Lossna...

Page 3: ...de air intake Supply air grille not included Except the 150 and 200 RX5 Remote controller optional parts EA exhaust air outlet OA outside air intake It can be installed by inverting the top and the bottom After installing the duct connecting flange remove the maintenance cover Turn the cover by 180 and then reinstall it Maintenance space Lossnay unit Inspection opening EA exhaust air outlet OA out...

Page 4: ...is recommended that the indoor ductwork be covered with insulation material Do not carry out the following types of duct construction Doing so could cause a drop in the air volume and generate abnormal noises 5 When changing the direction of the out door side duct EA OA Except for LGH 150 and 200 RX5 1 Removal of flange cover Unscrewing the flange cover mounting screws 4 pcs remove the flange cove...

Page 5: ...is product the wiring installation method will vary according to the design of the system Perform electrical installation to meet local electrical regulations Always use double insulated PVC cable for the transmission cables Wiring work must be performed by qualified professionals All supply circuits must be disconnected before obtaining access to the terminal devices M1 Motor for exhaust fan M2 M...

Page 6: ...onnector of control board 2 1 TM4 S B A TB5 M NET When the optional Remote Controller PZ 60DR E is used as the M NET System connect it to 1 2 of TM4 terminal block and connect M NET transmission wire to A B on TB5 terminal block 2nd remote controller Max 2 remote controllers installable 2 PZ 41SLB E and PZ 52SF E cannot be used when using PZ 60DR E M NET Transmission cable Shielded wire 2nd or lat...

Page 7: ...nnected to single input terminal is up to 4 wires for ø0 65 PVC wire or 0 3 mm2 stranded wire It is up to 2 wires for any other wires PZ 41SLB E cannot be used when MELANS centralized control of the Lossnay is used PZ 60DR E and PZ 41SLB E cannot be installed simultaneously 1 Connect the output signal cable from the external device to the input terminal block TM2 of the external controller CAUTION...

Page 8: ...3 3 and the negative side to 1 1 1 1 1 2 Confirm that the pulse input switch SW2 2 is set to OFF Set to OFF at time of shipment When the external device has a charged operating signal of 12 VDC or 24 VDC Connect the operating signal wire from the external device via the remote output to 1 and 2 on the external control input terminal block TM2 No polarity 1 Move the pulse input switch SW2 2 to the ...

Page 9: ...y Contactor rating DC 1 mA When connecting to the City Multi Lossnay remote controller PZ 52SF E or Mitsubishi Electric Air Conditioner Network System MELANS 10 Remote ON OFF adaptor Optional PAC SA88HA E When SW1 is ON fan speed of the Lossnay will be set to Low regardless of the remote control setting Use this in such a way that it ventilates at High fan speed normally and when the external sens...

Page 10: ...roller When interlocking with Mitsubishi Free Plan air conditioner Incase of PZ 60DR E Limit the total length of transmission wires no longer than 500 m Limit the wiring length between Lossnay and the power supply unit Optional or the outdoor unit no longer than 200 m M NET transmission cable Lossnay M NET transmission cable Power supply unit Lossnay MELANS M NET transmission cable Air conditioner...

Page 11: ...door OA air temperatures and automatically select the Lossnay ventilation or Bypass ventilation With this mode however priority is given to the Bypass ventilation This setting reflects to the night purge operation condition Bypass automatic ventilation priority setting 5 OFF ON 7 7 SW2 Operation When outdoor temperature OA is 28 C or higher within 24 hours then Bypass ventilation starts by the com...

Page 12: ...pply fan is stopped during defrosting of the air conditioner when Mr Slim or City Multi indoor unit is connected to a duct When the outdoor air is lower than 15 C stop the operation of exhaust fan OA stop operation at cold region Operation Exhaust fan operation factory setting Exhaust fan stop exhaust fan operation at Low speed at outdoor air lower than 15 C OFF ON 3 3 SW5 Settings for automatic r...

Page 13: ...the external device has come off of the external control input terminal Check in the case of multiple units whether the Main Sub selection switch on the Lossnay unit which is connected to the external control input terminal is set on the Master setting and check whether the Main Sub selection switch on other Lossnay units are set to Sub Check that the trial operation switch SW2 1 is set to off Cha...