63
CHAPTER
10
Performance Data /
3
. Capacity ratio against refrigerant pipe length
4. Quick reference for the air condition difference factor C
2
3. Capacity ratio against corrected refrigerant pipe length
Cooling
Heating
100
95
90
85
80
75
70
Cooling ZRP71 model
Cooling ZRP35, model
Cooling ZRP50,100 models
Cooling ZRP125 model
Heating ZRP35, 50,
71, 100 and 125 models
(Up to 55m for ZRP35,
50, 60, 71 models)
Capacity ratio
C
3
[%]
Corrected pipe length [m]
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
Note:
The permitted pipe length is up to 55m for ZRP35, 50, 71 model.
The permitted pipe length is up to 80m for ZRP100 ~ 125 model.
The following table shows the air condition difference factor C
2
of each models against some outdoor air temperature range.
Return air conditions are assumed that is stable at 21°CDB, 50%RH or 24°CDB, 50%RH.
And outdoor air relative humidity is also assumed that is stable.
Return air 21°CDB, 50%RH
Outdoor air dry-bulb temperature [°CDB] / 50%RH
30
31
32
33
34
35
36
37
38
39
40
LGH-50RVX-E + GUG-01SL-E
0.90
0.91
0.92
0.92
0.93
0.94
0.95
0.95
0.96
0.97
0.97
LGH-65RVX-E + GUG-01SL-E
0.90
0.91
0.92
0.93
0.93
0.94
0.95
0.96
0.96
0.97
0.98
LGH-80RVX-E + GUG-02SL-E
0.89
0.90
0.90
0.91
0.92
0.92
0.93
0.94
0.94
0.95
0.95
LGH-100RVX-E + GUG-02SL-E
0.89
0.89
0.90
0.91
0.91
0.92
0.92
0.93
0.94
0.94
0.95
LGH-150RVX-E + GUG-03SL-E
0.89
0.90
0.90
0.91
0.91
0.92
0.93
0.93
0.94
0.94
0.95
LGH-150RVXT-E + GUG-03SL-E
0.89
0.90
0.91
0.91
0.92
0.93
0.93
0.94
0.95
0.95
0.96
LGH-200RVX-E + GUG-03SL-E
0.89
0.89
0.90
0.91
0.91
0.92
0.92
0.93
0.94
0.94
0.95
LGH-200RVXT-E + GUG-03SL-E
0.89
0.90
0.90
0.91
0.92
0.92
0.93
0.94
0.94
0.95
0.95
LGH-250RVXT-E + GUG-03SL-E
0.90
0.91
0.92
0.93
0.94
0.94
0.95
0.96
0.97
0.97
0.98
Return air 24°CDB, 50%RH
Outdoor air dry-bulb temperature [°CDB] / 50%RH
30
31
32
33
34
35
36
37
38
39
40
LGH-50RVX-E + GUG-01SL-E
0.96
0.96
0.97
0.98
0.98
0.99
1.00
1.00
1.01
1.02
1.02
LGH-65RVX-E + GUG-01SL-E
0.96
0.96
0.97
0.98
0.99
0.99
1.00
1.01
1.01
1.02
1.02
LGH-80RVX-E + GUG-02SL-E
0.95
0.96
0.96
0.97
0.97
0.98
0.98
0.99
0.99
1.00
1.00
LGH-100RVX-E + GUG-02SL-E
0.95
0.96
0.96
0.96
0.97
0.97
0.98
0.98
0.99
0.99
1.00
LGH-150RVX-E + GUG-03SL-E
0.95
0.96
0.96
0.97
0.97
0.98
0.98
0.99
0.99
1.00
1.00
LGH-150RVXT-E + GUG-03SL-E
0.95
0.96
0.96
0.97
0.98
0.98
0.99
0.99
1.00
1.00
1.01
LGH-200RVX-E + GUG-03SL-E
0.95
0.95
0.96
0.96
0.97
0.97
0.98
0.98
0.99
0.99
1.00
LGH-200RVXT-E + GUG-03SL-E
0.95
0.96
0.96
0.97
0.97
0.98
0.98
0.99
0.99
1.00
1.00
LGH-250RVXT-E + GUG-03SL-E
0.96
0.97
0.97
0.98
0.99
0.99
1.00
1.01
1.01
1.02
1.03
(1) Cooling