CHAPTER
6
Other Functions
Set the selection switches to perform the appropriate function.
Shut down the power supply before setting the switches except function
No.5 No.6
.
Depending on system configuration, some functions might not be available.
When replacing to new PCB, set the same setting as old one.
1. Function setting
No.
Function outline
PCB
Switch No.
1
Selecting of RA temp. control or SA temp. control
PCB A of Dx-coil unit
SW1-7
2
Fixed operation mode
SW2-1, 2-2
3
Fixed set temperature
SW2-3, 2-4, 2-5
4
Thermo OFF point by the inlet air temp. (Only in SA temp. control mode)
SW3-4, 3-5
5
Test run of the drain pump
PCB B of Dx-coil unit
SW11-1
6
Resetting the operation hour of the drain pump
SW11-2
7
Selecting of the operation when an error occurs
SW11-3
8
Model selection (For PCB replacement)
SW11-9, 11-10
9
Setting about whether or not Dx-coil unit is connected
PCB of Lossnay unit
SW7-1
10
Selecting of the operation mode from “Temp. priority mode” or “Fan speed priority mode”
SW7-2
Selecting of the operation mode from “Temp. priority mode” , “Fan speed priority mode”
or “Fan priority mode after temp. priority mode” .
SW7-2, 7-3
No. 1
Selecting of RA temp. control or SA temp. control
Set the SW1-7 as below.
PCB
SW1-7
Setting check
Contents
PCB A of
Dx-coil unit
OFF
SA temp. control
ON
(Factory setting)
RA temp. control
[RA (Return Air) temperature control (Factory setting)]
The system of the Lossnay unit and Dx-coil unit is designed to maintain the return air temperature close to the setting
temperature.
[SA (Supply Air) temperature control]
The system of the Lossnay unit and Dx-coil unit is designed to maintain the supply air temperature close to the setting
temperature.
GUG-01SL-E cannot be used for SA temperature control.
The setting temperature is recommended to be the same as or close to the setting temperature of the air conditioning unit.
No. 2
Fixed operation mode
Set the SW2-1 and SW2-2 as below.
PCB
SW2-1
SW2-2
Setting check
Contents
PCB A of
Dx-coil unit
OFF
OFF
Not fixed (Depending on remote controller)
(Factory setting)
ON
OFF
[Cooling] fixed
OFF
ON
[Heating] fixed
ON
ON
Do not set
When the operation mode is fixed, the mode cannot be changed from the remote controller PZ-01RC.
Wiring
Wire No. × size (mm²)
Dx-coil unit - Outdoor unit *3
4 × 0.75 (polar)
Dx-coil unit - Outdoor unit earth *3
Circuit rating
x
×
Dx-coil unit - Outdoor unit S1-S2 *4
230 V AC
Dx-coil unit - Outdoor unit S2-S3 *4
24 V DC