Other Functions /
1. Function setting
No. 3
Fixed set temperature
Set the SW2-3, SW2-4 and SW2-5 as below.
PCB
SW2-3
SW2-4
SW2-5
Setting check
Contents
PCB A of
Dx-coil unit
OFF
OFF
OFF
Not fixed (Remote controller setting)
(Factory setting)
ON
OFF
OFF
Cooling, Auto 19 ˚C fixed
Heating 17 ˚C fixed
OFF
ON
OFF
20 ˚C fixed
ON
ON
OFF
22 ˚C fixed
OFF
OFF
ON
24 ˚C fixed
ON
OFF
ON
26 ˚C fixed
OFF
ON
ON
28 ˚C fixed
ON
ON
ON
Cooling 30 ˚C fixed
Heating, Auto 28 ˚C fixed
When the target temperature is fixed, the setting temp. cannot be changed from the remote controller PZ-01RC.
No. 4
Thermo OFF point by the inlet air temp. (Only in SA temp. control mode)
This setting is only activate when SA temperature control is selected. The compressor of outdoor unit is forced to stop when the
inlet air temp. is close to the setting temp. to reduce frequent ON/OFF cycling under low heating/cooling load conditions.
The thermo OFF point can be set by the SW3-4 and SW3-5 as below.
PCB
SW3-4
SW3-5
Setting check
Contents
PCB A of
Dx-coil unit
OFF
OFF
1 ˚C
OFF
ON
2 ˚C
ON
OFF
3 ˚C (Factory setting)
ON
ON
4 ˚C
When the differential is small, Dx-coil unit is likely to be thermo-ON but also the ON/OFF cycling is likely to happen.
Dx-coil unit
Inlet air temp.
Setting temp.
SA
Usage example
Following example shows when set thermo OFF point as 3
˚C
, factory setting.
Setting temp.
Supply air temp.
Inlet air temp.
Morning
Daytime
Evening
Operation
Temperature
Time
Setting temp.+3
℃
Setting temp.
Supply air temp.
Setting temp.
‒
3
˚C
Inlet air temp.
Morning
Daytime
Evening
Thermo ON
Thermo ON
Thermo OFF
Thermo ON
Thermo ON
Thermo OFF
Operation
Temperature
Time
[ Heating ]
[ Cooling ]