7
CHAPTER
2
System configurations /
2
.Technical notes
Following configurations are bad examples. Do not construct systems same as below.
Prohibition for TM2 connection of Lossnay.
Two PZ-01RC
connection is prohibited.
Two PZ-61DR-E
connection is prohibited.
Dx-coil unit
PZ-60DR-E
PZ-60DR-E connection is prohibited.
PZ-43SMF-E connection is prohibited.
PZ-43SMF-E
Dx-coil unit
PZ-01RC
Lossnay unit
Power supply
Outdoor unit
Power supply
PZ-01RC
PZ-01RC
Lossnay unit
Power supply
Power supply
Outdoor unit
PZ-61DR-E
PZ-61DR-E
Mr. Slim indoor unit
MA remote controller
Interlocking Mr. Slim indoor unit with Lossnay unit by using CN2L connector is prohibited.
CN2L
Dx-coil unit
Externaldevice
Interlocking external device with Lossnay unit by using TM2
①
and
③
is available.
OK
e.g. Non-Mitsubishi
Air-conditioner
Dx-coil unit
TM2
①③
TM2
①③
Mr. Slim indoor unit
MA remote controller
CN2L
Dx-coil unit
PZ-01RC
Lossnay unit
Power supply
Outdoor unit
Power supply
PZ-01RC
PZ-01RC
Lossnay unit
Power supply
Power supply
Power supply
Power supply
(Optional)
Interlocking Mr. Slim indoor unit with Lossnay unit by using PAC-SF40RM-E is available.
OK
PAC-SF40RM-E
Lossnay unit
Outdoor unit
Outdoor unit
Prohibition for Lossnay remote controller.