8
CHAPTER
2
System configurations /
2
.Technical notes
<CAUTION>
When interlocking with Mr.Slim or external device through TM2 and , there is a restriction to use “ON interlock mode” ,
“OFF interlock mode” and “External priority ON/OFF interlock mode” of Lossnay unit.
DIP-SW
PZ-61DR-E
Interlock setting
SW No.
Setting
Function No.
Setting Data
SW5-7
SW5-8
-
15
0
(Factory setting)
DIP-SW priority
5-7 OFF
5-8 OFF
(Factory setting)
1
a) ON/OFF interlock mode
5-7 ON
5-8 OFF
2
b) ON interlock mode
5-7 OFF
5-8 ON
3
c) OFF interlock mode
5-7 ON
5-8 ON
4
d) External priority ON/
OFF interlock mode
Not available at anytime
with Dx-coil unit.
Available only when
PZ-61DR-E is connected
or M-NET system
controller is connected.
Following diagrams are bad examples. Do not construct systems same as below.
M-NET system
controller
Lossnay unit
Lossnay unit
Lossnay unit
Dx-coil unit
Outdoor unit
PZ-01RC
PZ-01RC
Lossnay remote controller
(PZ-61DR-E, if necessary)
Indoor unit
Power supply
Power supply
MA remote controller
(If necessary)
Group 1
Group 2
Lossnay remote controller
PZ-61DR-E, if necessary)
Lossnay remote controller
(PZ-61DR-E, if necessary)
M-NET
adapter
To use M-NET adapter for the
outdoor unit is prohibited.
Lossnay and Dx-coil system
and normal Lossnay unit(s)
cannot be set in same group.
Multiple systems of Lossnay
unit and Dx-coil unit in one
group is prohibited.
Outdoor unit
Dx-coil unit
Prohibition for M-NET system.