21
CHAPTER
5
Wiring Diagram /
2. Connecting the power supply cable / 3. Connecting PZ-01RC / 4. Connecting Lossnay unit
3. Connecting PZ-01RC
4. Connecting Lossnay unit
Securely connect the transmission cable from the remote controller to the input terminal block (TM104). (No polarity)
Wire type: two-core sheathed cable
Wire diameter: 0.3 mm
2
Keep the overall length of the transmission cable between Dx-coil unit and the remote controller within 200 m.
Note:
• Do not tighten screws of terminal block with a torque larger than 0.5 Nm. It could damage the PCB.
• Do not connect the power supply cable.
• Remote controller cable should be rotated 3 times around the ferrite.
• Single wires such as PVC wires cannot be connected.
Connect the lead wire cable (accessory) to CN120 (GREEN) on PCB B of Dx-coil unit and CN20 (GREEN) on PCB of Lossnay unit.
Ferrite
Dx-coil unit side
Lossnay unit side
CN120(GREEN)
Connection cable
(accessory)
CN20(GREEN)
Connection cable
(accessory)
Pass the power supply cable through the bush* and connect to the TB6 terminal
block using the round terminals. Connect the ground wire to the screw and secure
tightening the bush.
(* Use an item that can firmly secure the cable such as a PG connector.)
A Outdoor unit power supply
B Earth leakage breaker *1, *2
C Wiring circuit breaker or isolating switch
D Outdoor unit
E Dx-coil unit/outdoor unit connecting cables
F Dx-coil unit
*1: If the installed earth leakage circuit breaker does not have a function to protect over-current, install a breaker with
that function along the same power line.
*2: A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
The breaker shall be provided to ensure disconnection of all active phase conductors of the supply.
2. Connecting the power supply cable
<CAUTION>
• Always separate the power supply cable and transmission cable by 5 cm or more to prevent malfunctioning of the unit.
• If the length of the stripped Power supply cable is too long, the conductors may touch and short out.
• Do not tighten screws of terminal block with a torque larger than 0.5 Nm. It could damage the PCB.
Power supply cable
Insert the cutting
Screw for earth lead
TM1
Bush
PG connector
S1
S2
L
N
S1
S2
S3
S3
A
B
C
D
E
F
TB6
Note:
In accordance with IEE regulations the circuit breaker/isolating switch located on the outdoor unit should be installed with lockable devices (health and safety).
Wiring
Wire No. × size (mm²)
Dx-coil unit - Outdoor unit *3
4 × 0.75 (polar)
Dx-coil unit - Outdoor unit earth *3
Circuit rating
x
×
Dx-coil unit - Outdoor unit S1-S2 *4
230 V AC
Dx-coil unit - Outdoor unit S2-S3 *4
24 V DC
*3: Max. 45 m
*4: The values given in the table are not always measured against the ground value.
Notes:
1. Wiring size must comply with the applicable local and national code.
2. Dx-coil unit/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60245 IEC 57)
Dx-coil unit power supply cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60227 IEC 53)
3. Install an earth longer than other cables.