3U
-CAN User's Manual
1. Object H1014: COB-ID EMCY
→
For the resulting COB-ID, refer to Subsection 5.6.1
Note
On the FX
3U
-CAN, the setting is fixed and can not be changed.
2. Object H1015: Inhibit time EMCY
This object configures the minimum time between two EMCY messages. The unit of the 16 bit value is 100
μ
s. The value 0 disables the inhibit time.
The FX
3U
-CAN counting resolution is 1ms, values smaller than 1ms will set internally to 1ms, values starting
from 1ms will be divided by 1000.
3. Object H1028 sub-index H01 to H7F: Emergency consumer object
This Object configures the COB-IDs for the EMCY objects that the module is consuming. The Sub-index
refers to the related node-ID.
→
For the resulting COB-ID, refer to Subsection 5.6.1
Bit No.
Item
Description
Bit 0 to 10
11-bit CAN-ID
11-bit CAN-ID of the CAN base frame
Bit 11 to 28
-
Bit 11 to 28 fixed to OFF (0).
Bit 29
-
Bit 29 fixed to OFF (0).
Bit 30
-
Bit 30 fixed to OFF (0).
Bit 31
valid
OFF (0): EMCY producing is valid
ON (1):
EMCY producing is not valid
Bit No.
Item
Description
Bit 0 to 10
11-bit CAN-ID
11-bit CAN-ID of the CAN base frame
Bit 11 to 28
-
Bit 11 to 28 fixed to OFF (0).
Bit 29
-
Bit 29 fixed to OFF (0).
Bit 30
-
Bit 30 fixed to OFF (0).
Bit 31
valid
OFF (0): EMCY consuming of remote Node is valid
ON (1):
EMCY consuming of remote Node is not valid
11-bit CAN-ID
H00000
H0
H0
valid
31
29
28 ... 11
10 ... 0
30
11-bit CAN-ID
H00000
H0
H0
valid
31
29
28 ... 11
10 ... 0
30