6 Allocation of Buffer Memories
6.23 [BFM #750 to #859] Emergency Message Buffer
122
FX
3U
-CAN User's Manual
*1.
Emergency error codes
In different CiA
®
Device/Application Profiles, more EMCY Error Codes are defined.
→
For EMCY Error Codes that are not in the following table,
refer to the manual of the device which sent the message
*2.
EMCY Manufacturer specific error codes
EMCY Manufacturer specific error codes of the FX
3U
-CAN are shown below. EMCY Manufacturer
Specific error codes are expressed by five ASCII code characters. However, the lower 2 bytes of the
Manufacturer Specific Error code corresponding to Emergency Error Code "8250" uses four
hexadecimal digits instead of ASCII code.
Error
Code
(hex)
Description
Error
Code
(hex)
Description
0000 Error reset or no error
7000 Additional modules – generic error
0010
CiA
®
417: CAN warning level
8000 Monitoring – generic error
1000 Generic error
8100 Communication – generic
2000 Current – generic error
8110 CAN overrun (objects lost)
2100
Current, CANopen
®
device input side – generic
8120 CAN in error passive mode
2200
Current inside the CANopen
®
device – generic
8130 Life guard error or heartbeat error
2300
Current, CANopen
®
device output side –
generic
8140 Recovered from bus off
3000 Voltage – generic error
8150 CAN-ID collision
3100 Mains voltage – generic
8F01
to
8F7F
Life guard error or heartbeat error caused by Node-ID 1 to
Node-ID 127.
3111
CiA
®
417: Mains Over voltage
8200 Protocol error – generic
3121
CiA
®
417: Mains Under voltage
8210 PDO not processed due to length error
3200
Voltage inside the CANopen
®
device – generic
8220 PDO length exceeded
3211
CiA
®
417: Over voltage (device internal)
8230 DAM MPDO not processed, destination object not available
3221
CiA
®
417: Under voltage (device internal)
8240 Unexpected SYNC data length
3300 Output voltage – generic
8250 RPDO timeout
4000 Temperature – generic error
9000 External error – generic error
4100 Ambient temperature – generic
F000 Additional functions – generic error
4200 Device temperature – generic
FF00 Device specific – generic error
*2
5000
CANopen
®
device hardware – generic error
FF01 CiA
®
417: Light barrier defect
*2
6000
CANopen
®
device software – generic error
FF02 CiA
®
417: Finger protector defect
*2
6100 Internal software – generic
FF03 CiA
®
417: Motion detection defect
*2
6200 User software – generic
FF04
CiA
®
417: Application error, Manufacturer-specific error
code: Byte 0 and 1 contain a Text error code, Byte 2 to 4 are
reserved
*2
6300 Data set – generic
Emergency
Error Code
(hex)
Manufacturer Specific Error code (hex)
Description
5th Byte 4th Byte 3rd Byte 2nd Byte 1st Byte
FF00
46
58
30
30
31
"FX001": Main unit/CPU error occurs
FF00
46
58
30
30
32
"FX002": Main unit state changed from RUN to STOP
Also occurs when the main unit is powered ON
in the STOP state.
6200
46
58
30
30
33
"FX003": FROM/TO Watchdog expired
6200
46
58
30
30
34
"FX004": Module reset by BFM #25 bit 0
→
For module reset, refer to Section 6.8
8250
50
44
4F
XX
XX
"PDO"X: RPDO Nr HXXXX Event Timer expired
Summary of Contents for FX3U-CAN
Page 1: ...FX3U CAN USER S MANUAL ...
Page 2: ......
Page 6: ...Safety Precautions Read these precautions before use 4 MEMO ...