![Mitsubishi Electric FX3G SERIES Programming Manual Download Page 854](http://html.mh-extra.com/html/mitsubishi-electric/fx3g-series/fx3g-series_programming-manual_238902854.webp)
852
FX
3G
/FX
3U
/FX
3UC
Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
37 Operation of Special Devices (M8000 -, D8000 -)
37.1 Special Device List (M8000 -, D8000 -)
Timing Clock (Refer to Section 24.3 for details.) and Positioning [FX
3U
and FX
3UC
PLCs] (Refer to Positioning Control Edition for details.)
D 8360
Lower [Y002] Current value register
Default: 0
3
3
3
–
–
–
–
–
–
D 8361
Upper
3
3
3
D 8362
[Y002] Bias speed Default: 0
3
3
3
–
–
–
–
–
–
D 8363
Lower [Y002] Maximum speed
Default: 100000
3
3
3
–
–
–
–
–
–
D 8364
Upper
3
3
3
D 8365
[Y002] Creep speed Default: 1000
3
3
3
–
–
–
–
–
–
D 8366
Lower [Y002] Zero return speed
Default: 50000
3
3
3
–
–
–
–
–
–
D 8367
Upper
3
3
3
D 8368
[Y002] Acceleration time Default: 100
3
3
3
–
–
–
–
–
–
D 8369
[Y002] Deceleration time Default: 100
3
3
3
–
–
–
–
–
–
D 8370
Lower [Y003] Current value register
Default: 0
–
3
*2
–
–
–
–
–
–
–
D 8371
Upper
–
–
–
–
–
–
–
D 8372
[Y003] Bias speed Default: 0
–
3
*2
–
–
–
–
–
–
–
D 8373
Lower [Y003] Maximum speed
Default: 100000
–
3
*2
–
–
–
–
–
–
–
D 8374
Upper
–
–
–
–
–
–
–
D 8375
[Y003] Creep speed Default: 1000
–
3
*2
–
–
–
–
–
–
–
D 8376
Lower [Y003] Zero return speed
Default: 50000
–
3
*2
–
–
–
–
–
–
–
D 8377
Upper
–
–
–
–
–
–
–
D 8378
[Y003] Acceleration time Default: 100
–
3
*2
–
–
–
–
–
–
–
D 8379
[Y003] Deceleration time Default: 100
–
3
*2
–
–
–
–
–
–
–
[D]8380 to [D]8392
Not used
–
–
–
–
–
–
–
–
RS2 (FNC 87) [ch0] [FX
3G
PLCs] (Refer to Data Communication Edition for details.)
D 8370
RS2 (FNC 87) [ch0] Communication format setting
3
–
–
–
–
–
–
–
–
D 8371
Not used
–
–
–
–
–
–
–
–
–
[D]8372
*1
RS2 (FNC 87) [ch0] Remaining points of transmit data
3
–
–
–
–
–
–
–
–
[D]8373
*1
RS2 (FNC 87) [ch0] Monitoring receive data points
3
–
–
–
–
–
–
–
–
D 8374
Not used
–
–
–
–
–
–
–
–
–
[D]8375 to [D]8378
–
–
–
–
–
–
–
–
–
D 8379
RS2 (FNC 87) [ch0] Time-out time setting
3
–
–
–
–
–
–
–
–
D 8380
RS2 (FNC 87) [ch0] Header 1 and 2 <Default: STX>
3
–
–
–
–
–
–
–
–
D 8381
RS2 (FNC 87) [ch1] Header 3 and 4
3
–
–
–
–
–
–
–
–
D 8382
RS2 (FNC 87) [ch0] Terminator 1 and 2
<Default: ETX>
3
–
–
–
–
–
–
–
–
D 8383
RS2 (FNC 87) [ch0] Terminator 3 and 4
3
–
–
–
–
–
–
–
–
[D]8384
RS2 (FNC 87) [ch0] Receive sum (received data)
3
–
–
–
–
–
–
–
–
[D]8385
RS2 (FNC 87) [ch0] Receive sum (calculated result)
3
–
–
–
–
–
–
–
–
[D]8386
RS2 (FNC 87) [ch0] Send sum
3
–
–
–
–
–
–
–
–
[D] 8387 to [D] 8388
Not used
–
–
–
–
–
–
–
–
–
[D]8389
Operation mode display [ch0]
3
–
–
–
–
–
–
–
–
[D] 8390 to [D] 8392
Not used
–
–
–
–
–
–
–
–
–
*1.
Cleared when the PLC switches from RUN to STOP.
*2.
Available only when two FX
3U
-2HSY-ADP adapters are connected to an FX
3U
PLC.
Number and name
Content of register
Applicable model
FX
3G
FX
3U
FX
3UC
Correspond-
ing special
device
FX
1S
FX
1N
FX
2N
FX
1NC
FX
2NC