16 External FX Device – FNC 80 to FNC 89
16.6 FNC 85 - VRRD / Volume Read
11
FN
C30
-FN
C3
9
R
ota
tion and
Shi
ft
12
FN
C40-FN
C49
D
ata O
perati
on
13
FNC
50-FNC
59
High-Speed
Proc
essing
14
FM
C60-FN
C69
H
andy
In
struction
15
FN
C70-FN
C79
E
xternal
F
X
I/O
De
vice
16
FNC
80-FNC
89
External
FX
Dev
ice
17
FNC1
00-
FNC10
9
Dat
a
Transfer 2
18
FNC1
10-
FNC139
Fl
oa
ting Poi
nt
19
FNC14
0-F
N
C
149
Da
ta
Operation 2
20
FNC1
50-
FNC159
Pos
itioning
Control
2. Example in which the analog values of the variable analog potentiometers Nos. 0 to 7 are read in
turn, and used as analog timers
K0 to K7 are specified in
of the VRRD instruction in accordance with the values of the variable potentiometers
VR0 to VR7.
Index (Z = 0 to 7) is used for indexing in the sequence below, and K0Z indicates K0 to K7.
Cautions
• In 14-point and 24-point type FX
3G
PLCs, the variable analog potentiometer board can be connected to the option
connector 1, and occupies communication channel ch1.
In this case, the communication function using communication channel ch1 is not available when the VRRD or
VRSC instruction is used.
• In 40-point and 60-point type FX
3G
PLCs, the variable analog potentiometer board can be connected only to the
option connector 2, and occupies communication channel ch2.
In this case, the communication function using communication channel ch2 is not available when the VRRD or
VRSC instruction is used.
• The communication function is not available for ch1 when the VRRD or VRSC instruction is used in the program in
FX
3U
/FX
3UC
PLCs.
→
For details, refer to the Communication Control Edition manual.
• FX
3G
PLCs support the FX
3G
-8AV-BD.
• FX
3U
/FX
3UC
-32MT-LT(-2) PLCs support the FX
3U
-8AV-BD.
S
1
S
M8000
RST
Z
FNC 08
FOR
K8
FNC 85
VRRD
K0Z
D200Z
Z
M8000
FNC 24
INC
FNC 09
NEXT
RUN
monitor
X000
T0
D200
T0
Y000
X001
T1
D201
T1
Y001
X007
T7
D207
T7
Y007
Because T0 to T7 are 100
ms timers, 0 to 25.5 sec are
obtained from the set values
0 to 255.
The index register Z is reset.
The routine "FOR ~ NEXT" is repeated 8 times.
Z + 1
→
Z
Analog values of variable
potentiometers are stored in data
registers D200 to D207.
0
4
7
16
17
21
23
27
59
63
Analog timer of VR0
Analog timer of VR1
Analog timer of VR7