2 Overview (Sequence Program)
2.7 Types and Setting of Parameters
1
Introdu
ction
2
Ov
ervi
ew
3
Instruction
Li
st
4
D
evices
in Det
ail
5
Specifi
ed the
De
vice
&
C
onst
ant
6
Bef
ore
Pr
og
ra
mmi
ng
7
Bas
ic
Instruction
8
FN
C00-FN
C0
9
Program Fl
ow
9
FNC
10-FN
C19
Mov
e & Com
pare
10
FNC
20-FNC
29
Arith. & Lo
gi
c
Operati
on
3
Setting devices
1. Click "Device" tab, and set devices.
The "Device" tab is available only in FX
3U
/FX
3UC
PLCs.
4
Setting the PC name
1. Click "PLC name" tab, and input the program title.
Set item
Contents of setting
Setting range
Supplemental relay
Set the latched (battery backed) auxiliary relay range. Initial value: 500 to 1023
0 to 1023
State
Set the latched (battery backed) state relay range. Initial value: 500 to 999
0 to 999
Timer
The setting displayed here cannot be changed.
–
Counter (16bit)
Set the latched (battery backed) 16-bit counter range. Initial value: 100 to 199
0 to 199
Counter (32bit)
Set the latched (battery backed) 32-bit counter range. Initial value: 220 to 255
220 to 255
Data register
Set the data register range (battery backed). Initial value: 200 to 511
0 to 511
Extended register
All extension registers are latched (battery backed).
This setting is fixed, and cannot be changed.
–
Set item
Contents of setting
Setting range
Title
Input the program title in up to 32 half-width characters
(or 16 full-width characters).
32 half-width characters
(or 16 full-width characters)
This example shows a window in an
FX
3U
/FX
3UC
PLC.