Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
37 Operation of Special Devices (M8000 -, D8000 -)
37.1 Special Device List (M8000 -, D8000 -)
31
FNC276
-F
NC2
79
Da
ta
Trans
fer 3
32
FNC28
0-F
NC
289
H
igh-Speed
Process
ing 2
33
FNC2
90-
FNC299
Ex
tensi
on Fi
le
Register
34
FN
C300-
FNC30
5
FX
3U
-C
F-
AD
P
35
SFC
•STL
Programming
36
Interrupt
Function
37
Sp
ec
ia
l D
evi
ce
38
E
rror Code
A
Ve
rsi
on U
p
Inform
ati
on
B
Ex
ecuti
on
T
imes
Step Ladder and Annunciator (Refer to ANS (FNC 46), ANR (FNC 47), IST (FNC 60), and Chapter 35 for details.)
M 8040
Transfer disable
While M8040 is turned ON, transfer between states is
disabled.
3
3
3
–
3
3
3
3
3
[M]8041
*1
Transfer start
Transfer from initial state is enabled in automatic
operation mode.
3
3
3
–
3
3
3
3
3
[M]8042
Start pulse
Pulse output is given in response to a start input.
3
3
3
–
3
3
3
3
3
M 8043
*1
Zero return complete
Set this in the last state of zero return mode.
3
3
3
–
3
3
3
3
3
M 8044
*1
Zero point condition
Set this when machine zero return is detected.
3
3
3
–
3
3
3
3
3
M 8045
All output reset
disable
Disables the ’all output reset’ function when the
operation mode is changed.
3
3
3
–
3
3
3
3
3
[M]8046
*2
STL state ON
ON when M8047 is ON and any state S0 to S899 or
S1000 to S4095
*3
is active.
3
3
3
M8047
3
3
3
3
3
M 8047
*2
STL monitoring
enable
D8040 to D8047 are enabled when M8047 is ON.
3
3
3
D8040 to
D8047
3
3
3
3
3
[M]8048
*2
Annunciator operate
ON when M8049 is ON and any annunciator S900 to
S999 is ON.
3
3
3
–
–
–
3
–
3
M 8049
*1
Annunciator enable
D8049 is enabled when M8049 is ON.
3
3
3
D8049
M8048
–
–
3
–
3
*1.
Cleared when the PLC switches from RUN to STOP.
*2.
Executed at END instruction.
*3.
S1000 to S4095 are available only in the FX
3G
/FX
3U
/FX
3UC
Series PLC.
Interrupt Disable (Refer to Subsection 36.2.1.) for details.
M8050 (input interrupt)
I00
disable
*4
•
If an input interrupt or timer interrupt occurs while a
special auxiliary relay for that interrupt (M8050 -
M8058) is ON, the interrupt will not operate.
For example, turning M8050 ON disables the I00
interrupt; hence, the interrupt routine is not
processed even in an allowable program area.
•
If an input interrupt or timer interrupt occurs while a
special auxiliary relay for that interrupt (M8050 -
M8058) is OFF,
a) The interrupt will be accepted.
b) The interrupt routine will be processed promptly
if it is permitted by the EI (FNC 04) instruction.
However, if the DI (FNC 05) instruction disables
interrupts, the interrupt program will not be
processed until EI (FNC 04) permits the
interrupts.
3
3
3
–
3
3
3
3
3
M8051 (input interrupt)
I10
disable
*4
3
3
3
–
3
3
3
3
3
M8052 (input interrupt)
I20
disable
*4
3
3
3
–
3
3
3
3
3
M8053 (input interrupt)
I30
disable
*4
3
3
3
–
3
3
3
3
3
M8054 (input interrupt)
I40
disable
*4
3
3
3
–
3
3
3
3
3
M8055 (input interrupt)
I50
disable
*4
3
3
3
–
3
3
3
3
3
M8056
(Timer interrupt)
I6
disable
*4
3
3
3
–
–
–
3
–
3
M8057
(Timer interrupt)
I7
disable
*4
3
3
3
–
–
–
3
–
3
M8058
(Timer interrupt)
I8
disable
*4
3
3
3
–
–
–
3
–
3
M8059
Counter interrupt
disable
*4
Interrupt of I010 to I060 disabled
–
3
3
–
–
–
3
–
3
*4.
Cleared when the PLC switches from RUN to STOP.
Number and name
Operation and function
Applicable model
FX
3G
FX
3U
FX
3UC
Correspond-
ing special
device
FX
1S
FX
1N
FX
2N
FX
1NC
FX