![Mitsubishi Electric FX3G SERIES Programming Manual Download Page 753](http://html.mh-extra.com/html/mitsubishi-electric/fx3g-series/fx3g-series_programming-manual_238902753.webp)
751
FX
3G
/FX
3U
/FX
3UC
Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
34 FX3U-CF-ADP Applied Instructions – FNC300 to FNC305
34.5 FNC 304 – FLCMD / FX3U-CF-ADP command
31
FNC276
-F
NC2
79
Da
ta
Trans
fer 3
32
FNC28
0-F
NC
289
H
igh-Speed
Process
ing 2
33
FNC2
90-
FNC299
Ex
tensi
on Fi
le
Register
34
FN
C300-
FNC30
5
FX
3U
-C
F-
AD
P
35
SFC
•STL
Programming
36
Interrupt
Function
37
Sp
ec
ia
l D
evi
ce
38
E
rror Code
A
Ve
rsi
on U
p
Inform
ati
on
B
Ex
ecuti
on
T
imes
34.5.1 Detailed explanation of setting data
Details on the setting data in the FLCMD instruction are as shown below.
*1.
The CompactFlash
TM
card is available in the "mounted" status.
*2.
The CompactFlash
TM
card is unavailable in the "unmounted" status.
Cautions
• It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)"/"IVCK (FNC270) to IVMC (FNC275)" instruction and an
"FLCRT (FNC300) to FLSTRD (FNC305)" instruction for the same port.
Setting items
Description
Data Type
Contents of instruction for operation
K0 to K63 : Forcibly writes the buffered data of the specified file ID to the CompactFlash
TM
card.
K-1 : Forcibly writes all buffered data to the CompactFlash
TM
card.
K256(H100) : Sets the CompactFlash
TM
card to the mounted status
*1
.
K512(H200) : Sets the CompactFlash
TM
card to the unmounted status
*2
.
K1280(H500) : Clears error codes stored in the CF-ADP.
16-bit binary
n
Channel number used by the CF-ADP
K1 : ch1
K2 : ch2
16-bit binary
S