90
Frequency setting by external terminals
REMARKS
During jog operation or PID control operation, the remote setting function is invalid.
CAUTION
When selecting this function, re-set the maximum frequency according to the machine.
Parameters referred to
Pr. 1 Maximum frequency, Pr. 18 High speed maximum frequency
Pr. 7 Acceleration time, Pr. 8 Deceleration time, Pr. 44 Second acceleration/deceleration time, Pr. 45 Second deceleration time
Pr. 178 to Pr. 182
(input terminal function selection)
Setting frequency is "0"
Even when the remotely-set
frequency is cleared by turning on
the RL (clear) signal after turn off
(on) of both the RH and RM
signals, the inverter operates at
the remotely-set frequency stored
in the last operation if power is
reapplied before one minute has
elapsed since turn off (on) of both
the RH and RM signals
When the remotely-set frequency
is cleared by turning on the RL
(clear) signal after turn off (on) of
both the RH and RM signals, the
inverter operates at the frequency
in the remotely-set frequency
cleared state if power is reapplied
after one minute has elapsed
since turn off (on) of both the RH
and RM signals.
Clear (RL)
Acceleration (RH)
Forward rotation (STF)
(Hz)
ON
Power supply
ON
ON
ON
ON
ON
Within 1 minute
Time
Remotely-set frequency
stored last time
Remotely-set frequency stored last time
Deceleration (RM)
OFF
Output frequency
Clear (RL)
Acceleration (RH)
Forward rotation (STF)
(Hz)
ON
Power supply
ON
ON
ON
ON
ON
More than 1 minute
Operation is performed
at the set frequency 0Hz.
Remotely-set frequency
stored last time
1 minute
Time
Deceleration (RM)
OFF
Output frequency