Frequency setting by analog input (terminal 2, 4)
(4) Frequency setting signal (current) bias/gain adjustment method
(a) Method to adjust any point by application of a voltage (current) to across terminals 2-5 (4-5).
Operation Display
1.
Confirmation of the RUN indication and
operation mode indication
The inverter should be at a stop.
The inverter should be in the PU operation
mode.
(Using )
2.
Press
to choose the parameter setting
mode.
PRM indication is lit.
(The parameter number read previously appears.)
3.
Turn
until
appears.
4.
Turn
until
appears.
5.
Turn
until
(
) appears.
Set to
C4
Terminal 2 frequency setting gain.
Terminal 2 input is
selected
Terminal 4 input is
selected
6.
Press
to display the analog voltage
(current) value (%).
Analog voltage (current)
value (%) across terminals 2-
5 (across terminals 4-5)
7.
Apply a 5V (20mA) voltage (current).
(Turn the external potentiometer connected
across terminals 2-5 (across terminals 4-5) to
maximum (any position).)
∗
* The value is nearly 100 (%) in the maximum position of
the potentiometer.
8.
Press
to set.
Terminal 2 input is
selected
Terminal 4 input is
selected
Flicker...Parameter setting complete!!
* The value is nearly 100 (%) in the maximum position of
the potentiometer.
Turn
to read another parameter.
Press
to return to the
indication (step 4).
Press
twice to show the next parameter (
).
REMARKS
If the frequency meter (display meter) connected across the terminals AM-5 does not indicate just 50Hz, set the
calibration
parameter C1 AM terminal calibration
.
If the gain and bias of frequency setting voltage (current) are too close, an error (
) may be displayed at setting.
C1 to C7 setting
is enabled.
NOTE
After performing operation in step 6, do not touch
until completion of calibration.
∗