130
Monitor display and monitor output signal
(2) How to calibrate the terminal AM when using the operation panel
Operation Display
1.
Confirmation of the RUN indication and
operation mode indication
(When
Pr. 158
= 1)
2.
Press
to choose the parameter setting
mode.
PRM indication is lit.
(The parameter number read previously appears.)
3.
Turn
until
appears.
4.
Turn
until
appears.
5.
Turn
until
appears.
Set to
C1 AM terminal calibration.
6.
Press
to enable setting.
7.
If the inverter is at a stop, press the
key
to start the inverter.
(Motor needs not be connected.)
8.
Turn
to adjust the indicator needle to the
desired position.
Analog indicator
9.
Press
.
Setting is complete.
Flicker...Parameter setting complete!!
Turn
to read another parameter.
Press
to return to the
indication (step 4).
Press
twice to show the next parameter (
).
REMARKS
Calibration can also be made for external operation. Set the frequency in the external operation mode, and make calibration in
the above procedure.
Calibration can be made even during operation.
For operation from the parameter unit (FR-PU04/FR-PU07), refer to the instruction manual of the parameter unit.
Parameters referred to
Pr. 55 Frequency monitoring reference
Pr. 56 Current monitoring reference
Pr. 158 AM terminal function selection
C1 to C7 setting
is enabled.
The monitor set to
Pr. 158
AM terminal function selection
is displayed.