151
Frequency setting by analog input (terminal 2, 4)
(b) Method to adjust any point without application of a voltage (current) to across terminals 2-5 (4-5)
(To change from 4V (80%) to 5V (100%))
Operation Display
1.
Confirmation of the RUN indication and operation
mode indication
The inverter should be at a stop.
The inverter should be in the PU operation mode.
(Use )
2.
Press
to choose the parameter setting
mode.
PRM indication is lit.
(The parameter number read previously appears.)
3.
Turn
until
appears.
4.
Turn
until
appears.
5.
Turn
until
(
) appears.
Set to
C4 Terminal 2 frequency setting gain
.
Terminal 2 input is
selected
Terminal 4 input
is selected
6.
Press
to display the analog voltage
(current) value (%).
Analog voltage (current) value (%)
across terminals 2-5 (across
terminals 4-5)
7.
Turn
to set gain voltage (%).
"0V(0mA) is 0%, 10V(5V, 20mA) is 100%"
The gain frequency is reached
when the analog voltage (current)
value across terminals 2-5 (across
terminals 4-5) is 100%.
8.
Press
to set.
Terminal 2 input
is selected
Terminal 4 input
is selected
Flicker...Parameter setting complete!!
(Adjustment completed)
Turn
to read another parameter.
Press
to return to the
indication (step 4).
Press
twice to show the next parameter (
).
REMARKS
By pressing
after step 6, you can confirm the current frequency setting bias/gain setting.
You can not check after performing operation in step 7.
C1 to C7 setting
is enabled.
REMARKS
The current setting at the instant of turning
is
displayed.
You can not check after performing operation in step 7.