OCH790 _13
Model
PUMY-P112YKM5(-BS)
PUMY-P112YKM5-ER(BS)
PUMY-P125YKM5(-BS)
PUMY-P125YKM5-ER(-BS)
PUMY-P140YKM5(-BS)
PUMY-P140YKM5-ER(BS)
Power source
3-phase 380-400-415 V, 50 Hz; 3-phase 380 V, 60 Hz
Cooling capacity (Nominal)
*1
kW
12.5
14.0
15.5
kcal/h
10,750
12,040
13,330
Btu/h
42,650
47,768
52,886
Power input
kW
4.34
5.00
5.17
Current input
A
7.76 - 6.97 - 6.36. 7.76
8.94 - 8.02 - 7.33, 8.94
9.25 - 8.30 - 7.58, 9.25
COP
kW/kW
2.88
2.80
3.00
Temp. range of
cooling
Indoor
W.B.
15 to 24°C
Outdoor
D.B.
−5 to 52°C
*3*4
Heating capacity (Nominal)
*2
kW
14.0
16.0
18.0
kcal/h
12,040
13,760
15,480
Btu/h
47,768
54,592
61,416
Power input
kW
4.34
5.00
5.17
Current input
A
6.24 - 5.60 - 5.12, 6.24
7.26 - 6.52 - 5.95, 7.26
8.28 - 7.43 - 6.79, 8.28
COP
kW/kW
4.01
3.94
3.89
Temp. range of
heating
Indoor
D.B.
15 to 27°C
Outdoor
W.B.
−20 to 15°C
Indoor unit
connectable
Total capacity
50 to 130% of outdoor unit capacity
Model/ Quantity CITY MULTI
P10 - P140 / 9
P10 - P140 / 10
P10 - P140 / 12
Branch box
*6
P15 - P100 / 8
P15 - P100 / 8
P15 - P100 / 8
Mixed
system
Branch box
1 unit
*6
CITY MULTI
P15 - P140 / 5
P15 - P140 / 5
P15 - P140 / 5
Branch box
P15 - P100 / 5
P15 - P100 / 5
P15 - P100 / 5
Branch box
2 units
*6
CITY MULTI
P15 - P140 / 3 or 2
*5
P15 - P140 / 3
P15 - P140 / 3
Branch box
P15 - P100 / 7 or 8
*5
P15 - P100 / 8
P15 - P100 / 8
Sound pressure level (SPL)
(measured in anechoic room)
dB <A>
49/51
50/52
51/53
Sound power level (PWL)
(measured in anechoic room)
dB <A>
69/71
70/72
71/73
Refrigerant piping
diameter
Liquid pipe
mm (in)
9.52 (3/8)
Gas pipe
mm (in)
15.88 (5/8)
Fan
Type × Quantity
Propeller Fan × 2
Airflow rate
m³/min
110
L/s
1,833
cfm
3,884
Control, Driving mechanism
DC control
Motor output
kW
0.074 + 0.074
External static press.
0
Compressor
Type × Quantity
Scroll hermetic compressor × 1
Manufacturer
Mitsubishi Electric Corporation
Starting method
Inverter
Capacity control %
Cooling 26 to 100
Heating 20 to 100
Cooling 24 to100
Heating 18 to 100
Cooling 21 to 100
Heating 17 to 100
Motor output
kW
2.9
3.5
3.9
Case heater
kW
0
Lubricant
FV50S (2.3liter)
External finish
Galvanized Steel Sheet Munsell No. 3Y 7.8/1.1
External dimension H × W × D
mm
1338 × 1050 × 330 (+40)
in
52-11/16 × 41-11/32 × 13 (+1-9/16)
Protection
devices
High pressure protection
High pressure switch
Inverter circuit (COMP./FAN)
Overcurrent detection, Overheat detection(Heat sink thermistor)
Compressor
Compressor thermistor, Over current detection
Fan motor
Overheating, Voltage protection, Over current detection
Refrigerant
Type × original charge
R410A 4.8 kg
Control
Linear expansion valve
Net weight
kg (lb)
125 (276)
Heat exchanger
Cross Fin and Copper tube
HIC circuit (HIC: Heat Inter-Changer)
Double pipe heat exchanger
Defrosting method
Reversed refrigerant circuit
Standard
attachment
Document
Installation Manual
Accessory
Grounded lead wire ×1
Optional parts
Joint: CMY-Y62-G-E, Header: CMY-Y64/68-G-E, Branch box: PAC-MK34/54BC
Remarks
*1.
Nominal cooling conditions:
Indoor:
27°C D.B./19°C W.B. [81°F D.B/66°F W.B.]
Outdoor:
35°C D.B. [95°F D.B.]
Pipe length:
7.5 m [24-9/16 ft]
Level difference: 0 m [0 ft]
*2. Nominal heating conditions:
Indoor:
20°C D.B. [68°F D.B.]
Outdoor:
7°C DB/6°C W.B. [45°F D.B./43°F W.B.]
Pipe length:
7.5 m [24-9/16 ft]
Level difference: 0 m [0 ft]
*3.
10 to 52°C D.B. [50 to 126°F D.B.], when connecting following models: PKFY-P10/15/20/25/32VLM, PFFY-P20/25/32VLEM, PFFY-P20/25/32VL-
RM(M), PFFY-P20/25/32VKM, PFFY-P20/25/32VCM; and M series, S series, and P series type indoor unit.
*4. −15 to 52°C D.B. [50 to 126°F D.B.], when using an optional air protect guide [PAC-SH95AG-E]. However, this condition does not apply to the indoor
unit listed in *3.
*5. When connecting 7 indoor units via branch box, connectable CITY MULTI indoor units are 3; connecting 8 indoor units via branch box, connectable
CITY MULTI indoor units are 2.
*6.
At least two indoor units must be connected when using branch box.
Notes:
•
Nominal conditions *1, *2 are subject to ISO 15042.
•
Due to continuing improvement, above specifications are subject to change without notice.
•
See the following for unit conversion: kcal/h = kW × 860, Btu/h = kW × 3,412, cfm = m³/min × 35.31, lb = kg/0.4536