OCH790 _102
SW1
setting
Contents
LED1, 2
No.
12345678
1
2
3
4
5
6
7
8
52 00101100 Outdoor LEV-A
opening pulse
0–2000 (pulse)
Note: Display of opening pulse of outdoor LEV
53 10101100 Outdoor LEV-A
opening pulse
abnormality delay
54 01101100 Outdoor LEV-A
opening pulse
abnormality
55 11101100 Outdoor LEV-B
opening pulse
56 00011100 Outdoor LEV-B
opening pulse
abnormality delay
57 10011100 Outdoor LEV-B
opening pulse
abnormality
58 01011100 63LS (Low
pressure)
−99.9–999.9 (kgf/cm²)
Note: Display of data from sensor and thermistor
59 11011100 63LS abnormality
delay
60
00111100 63 LS abnormality
61 10111100
TH2 (HIC pipe)
−99.9–999.9 (°C)
Note: Display of data from sensor and thermistor
62
01111100
TH2 (HIC)
abnormality delay
63
11111100
TH2 (HIC)
abnormality
64 00000010
Operational
frequency
0–255 (Hz)
Note: Display of actual operating frequency
65 10000010 Target frequency 0–255 (Hz)
Note: Display of target frequency
66
01000010
Outdoor fan
control step
number
0–15
Note: Display of number of outdoor fan control steps (target)
69
10100010 IC1 LEV Opening
pulse
0–2000 (pulse)
Note: Display of opening pulse of indoor LEV
70
01100010
IC2 LEV Opening
pulse
71 11100010
IC3 LEV Opening
pulse
72
00010010 IC4 LEV Opening
pulse
73
10010010 IC5 LEV Opening
pulse
74 01010010
High pressure
sensor (Pd)
−99.9–999.9 (kgf/cm²)
Note: Display detected data of outdoor unit sensors and thermistors
75 11010010 TH4(Compressor)
(Td) data
−99.9–999.9 (°C)
Note: Display detected data of outdoor unit sensors and thermistors
76
00110010
TH6(Suction pipe)
(ET) data
77
10110010 TH7 (Ambient)
data
78
01110010
TH3 (Outdoor
liquid pipe) data
80
00001010 TH8 (Heat sink)
data
81 10001010 IC1 TH23 (Gas)
−99.9–999.9 (°C)
(When indoor unit is not connected, it is displayed as 0.)
Note: Display detected data of indoor unit thermistors
82
01001010
IC2 TH23 (Gas)
83
11001010
IC3 TH23 (Gas)
84 00101010 IC4 TH23 (Gas)
85 10101010 IC5 TH23 (Gas)
86
01101010 IC1 TH22 (Liquid)
87
11101010
IC2 TH22 (Liquid)
88
00011010
IC3 TH22 (Liquid)
89
10011010 IC4 TH22 (Liquid)
90
01011010 IC5 TH22 (Liquid)
91 11011010 IC1 TH21 (Intake)
92
00111010 IC2 TH21 (Intake)
93
10111010 IC3 TH21 (Intake)
94 01111010 IC4 TH21 (Intake)
95 11111010 IC5 TH21 (Intake)
96
00000110
Outdoor SC
(cooling)
−99.9–999.9 (°C)
Note: Display of outdoor subcool (SC) data
97
10000110 Target subcool
step
−2–4
Note: Display of target subcool step data
98
01000110 IC1 SC/SH
−99.9–999.9 (°C)
During heating: subcool (SC)
During cooling: superheat (SH) (Fixed to “0” during cooling operation)
Note: Display of indoor SC/SH data
99
11000110 IC2 SC/SH
100 00100110 IC3 SC/SH
101 10100110 IC4 SC/SH
102 01100110 IC5 SC/SH
103 11100110
Discharge
superheat (SHd)
−99.9–999.9 (°C)
Note: Display of outdoor discharge superheat (SHd) data
105 10010110 Target Pd display
(heating) kgf/cm²
Pdm (0.0–30.0) (kgf/cm²)
Note: Display of all control target data
106 01010110 Target ET display
(cooling)
ETm (−2.0–23.0) (°C)
Note: Display of all control target data