OCH790 _38
1302 (UE): High pressure trouble
Chart 3 of 4
Diagnosis of failure
Yes
Yes
Yes
No
No
No
Replace the indoor controller board.
Check the voltage(*) and appearance of the
indoor controller board.
Check the resistance of SV1.
*For the voltage, refer to "How to check the components".
Continued from the previous page.
Replace the TH7.
Replace the indoor LEV.
Disconnect the indoor LEV wiring to check the
resistance.
Continue to the next page.
Is the resistance detected?
Is the resistance detected?
Is the voltage normal?
Is it free from any trace of overheating
or burning?